Alarm Codes - Carrier PRO-DIALOG Plus 30GK Series Installation, Operation & Maintenance Instructions Manual

Air-cooled liquid chillers
Table of Contents

Advertisement

6.4 - Alarm codes

The following list gives a complete description of each alarm
code and its possible cause.
ALARM CODE DESCRIPTIONS
Code
Alarm name
1
Evaporator leaving water thermistor fault
2
Evaporator entering water thermistor fault
3
Condenser leaving water thermistor fault
4
Condenser entering water thermistor fault
5
Heat reclaim entering water thermistor fault
6
Heat reclaim leaving water thermistor fault
7
Outdoor temperature sensor fault
8
CHWS (master/slave) fluid thermistor fault
9
Suction thermistor fault, compressor A1
10
Suction thermistor fault, compressor B1
11
External 0-10 V dc signal fault
12
Discharge pressure sensor fault, circuit A
13
Discharge pressure sensor fault, circuit B
14
Suction pressure sensor fault, circuit A
15
Suction pressure sensor fault, circuit B
16
Oil pressure sensor fault, compressor A1
17
Oil pressure sensor fault, compressor B1
18
Oil pressure sensor fault, compressor A2
19
Oil pressure sensor fault, compressor B2
20
Oil pressure sensor fault, compressor A3
21
Oil pressure sensor fault, compressor B3
22
Oil pressure sensor fault, compressor A4
23
Oil pressure sensor fault, compressor B4
24
Pumpdown pressure sensor fault, circuit A
25
Pumpdown pressure sensor fault, circuit B
26
Loss of communication with compressor board A1
27
Loss of communication with compressor board A2
28
Loss of communication with compressor board A3
29
Loss of communication with compressor board A4
30
Loss of communication with compressor board B1
31
Loss of communication with compressor board B2
32
Loss of communication with compressor board B3
33
Loss of communication with compressor board B4
34
Loss of communication with EXV board
35
Loss of communication with NRCP board
36
Loss of communication with fan board 1
37
Loss of communication with fan board 2
38
Loss of communication with 4xAI - 2xAO board 1
39
Loss of communication with 4xAI - 2xAO board 2
40
Pumpdown fault, circuit A
41
Pumpdown fault, circuit B
42
Evaporator frost protection
43
Low evaporator water flow rate.
44
Low suction temperature, circuit A
45
Low suction temperature, circuit B
46
High suction overheat, circuit A
47
High suction overheat, circuit B
48
Low suction overheat, circuit A
Description
Action
Thermistor outside range
Unit shut down
Ditto
Unit shut down
Ditto
Heating mode: Unit shut down,
if control on leaving water.
Cooling mode: no action
Ditto
Heating mode: Unit shut down,
if control on entering water.
Cooling mode: no action
Ditto
Unit with heat recalaim option:
heat reclaim mode shut down,
unit changes over to standard
cooling mode. If not: no action
Ditto
None
Ditto
Reset: normal setpoint used.
Limitation or reset deactivated.
Ditto
Deactivated
Ditto
Circuit A shut down
Ditto
Circuit B shut down
Reset signal outside range
Reset: normal setpoint used
Limitation or reset deactivated
Voltage transmitted by incorrect sensor Circuit A shut down
Ditto
Circuit B shut down
Ditto
Circuit A shut down
Ditto
Circuit B shut down
Ditto
Circuit A shut down
Ditto
Circuit B shut down
Ditto
Compressor A2 shut down
Ditto
Compressor B2 shut down
Ditto
Compressor A3 shut down
Ditto
Compressor B3 shut down
Ditto
Compressor A4 shut down
Ditto
Compressor B4 shut down
Ditto
If circuit is in heat reclaim
mode, it goes to cooling mode.
If not, no action
Ditto
Ditto
Communication with the compressor
Circuit A shut down
board is lost
Ditto
Compressor A2 shut down
Ditto
Compressor A3 shut down
Ditto
Compressor A4 shut down
Ditto
Circuit B shut down
Ditto
Compressor B2 shut down
Ditto
Compressor B3 shut down
Ditto
Compressor B4 shut down
Ditto
Unit shut down
The board does not respond
Unit shut down, if heat reclaim mode No
is selected
Ditto
Unit shut down, if the number of
fan stages per circuit is less than 3.
If not, circuit A shut down
Ditto
Circuit B shut down
Ditto
Unit shut down or no action
Ditto
Compressors or circuit shut down
End of pumpdown conditions not
Circuit A shut down
satisfied
Ditto
Circuit B shut down
Unit operating: units shut down if
Unit shut down
temp. < defrost threshold.
Unit shut down: if temp < threshold
and evaporator heater on for more
than 10 mins.
Unit shut down
Circuit operating: saturated suction
Circuit A shut down
temp. < defrost threshold and < leaving
water -16°C for more than 10 mins.
Ditto
Circuit B shut down
EXV fully open
Circuit A shut down
Ditto
Circuit B shut down
EXV in min. position, and circuit
Circuit A shut down
superheat below superheat setpoint
-5.5 K, saturated suction temp. above
MOP for 5 mins.
Pumpdown
Reset type
Probable cause
Yes
Auto
Thermistor or wiring fault or
bad connection
Yes
Auto
Ditto
Yes
Auto
Ditto
-
Auto
Ditto
-
Auto
Ditto
-
Auto
Ditto
-
Auto, if temp. mea-
Thermistor faulty
sured by sensor
returns to normal
-
Ditto
Themistor faulty
Yes
Auto
Ditto
Yes
Auto
Ditto
No
Auto
Signal incorrect, wiring error
Yes
Auto
Sensor fault or wiring error
Yes
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
-
Auto
Ditto
-
Auto
Ditto
-
Auto
Ditto
-
Auto
Ditto
-
Auto
Ditto
-
Auto
Ditto
-
Auto, if press. mea-
sured by sensor
returns to normal
-
Ditto
Ditto
No
Auto
Wiring fault, faulty module,
incorrect module address
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
-
Auto
Ditto
-
Auto
Ditto
No
Auto
Wiring bus faulty, incorrect
address or board faulty
Auto, if board is
NRCP board faulty
again detected
No
Auto
Wiring bus faulty, incorrect
address or board faulty
No
Auto
Ditto
No
Auto
Ditto, depending on
configuration
No
Auto
Ditto, depending on
configuration
No
Manual
EXV or sensor faulty
No
Manual
Ditto
No
Auto first time,
Low water flow or
then manual
thermistor defective
No
Manual
Water pump faulty
No
Manual
Low charge, filter dirty
ot thermistor faulty
No
Manual
Ditto
Yes
Manual
Ditto
Yes
Manual
Ditto
Yes
Manual
EXV or thermistor or
transducer defective
33