Viessmann Vitodens series Technician Manual page 18

Flue systems for gas condensing boilers 3.8 to 105.0 kw
Hide thumbs Also See for Vitodens series:
Table of Contents

Advertisement

Design and sizing information for connection on the flue gas side
b
B
2
A
3
6
2
5
2
C
4
1
A Ventilation air
B Flue gas
C Inspection port
Max. total length of the flue pipe
Vitodens 200-W, 222-F, 222-W, 242-F and Vitosolar 200-F
Rated output range
a
max. length - system size 60
a
max. length - system size 80
a
max. length - system size 100
b
min.
Vitodens 300-W, 333-F and 343-F
Rated output range
a
max. length - system size 60
a
max. length - system size 80
b
min.
2 x 87º balanced flue bends are taken into consideration for the max-
imum flue lengths.
*1
Alternative system size: order balanced flue adaptor separately.
VIESMANN
18
b
B
2
A
3
6
2
4
C
5
C
4
1
kW
4.8–19.0
m
m
m
mm
kW
m
m
mm
1
Boiler flue connection (part of the
standard boiler delivery)
2
Balanced flue roof outlet with fixing
clamp
Colour: black
or
Colour: terracotta
Above roof extension with clamp
(brace on site)
Colour: black
0.5 m long
1 m long, with bracing clamp
Colour: terracotta
0.5 m long
1 m long, with bracing clamp
3
Universal roof tile
– For Roman tiles, pantiles, plain tiles,
slate and other types of roof cover
− Colour: black or terracotta
or
Flat roof collar
or
Pipe outlet for Klöber roof tiles
Colour: black or terracotta (provide
the corresponding Klöber tile on site
to match the roof outlet selected for
the particular type of roof)
4
Balanced flue inspection piece,
straight
(1 pce)
5
Balanced flue slide coupling
6
Universal cover plate
Balanced flue bend
87º (1 pce)
45º (2 pce)
Balanced flue pipe
1 m long
0.5 m long
Fixing clamp, white
(1 pce)
Balanced flue adaptor
– Ø 80/125 mm to Ø 60/100 mm
– Ø 60/100 mm to Ø 80/125 mm
– Ø 80/125 mm to Ø 100/150 mm
6.5–26.0
8.8–35.0
13.0–
10
10
10
*1
*1
*1
13
13
11
400
400
400
3.8–13.0
3.8–19.0
10
*1
13
400
Subtract other bends, tees and straight lengths from the maximum
length using the following values:
■ Balanced flue bends 45º: 0.5 m
■ Balanced flue bends 87º: 1 m
■ Balanced flue inspection tee: 0.5 m
(cont.)
System size Ø mm
60
80
100
60
80
100
60
80
100
60
80
60
80
100
60
80
60
80
100
60
80
100
60
80
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
60
80
80
100
17.0–
30.0–
30.0–
45.0
60.0
80.0
105.0
10
6
*1
*1
15
13
9
400
1000
1000
5.2–26.0
7.0–35.0
10
10
*1
*1
13
13
400
400
VITODENS
15
1000
10
*1
11
400