Bryant 558D Installation, Start-Up And Service Instructions Manual page 22

Single package rooftop electric heating/electric cooling units sizes 036-072 3 to 6 tons
Hide thumbs Also See for 558D:
Table of Contents

Advertisement

Table 8 — 558D048 Air Delivery — Vertical Discharge Units (Alternate Motor)
AIRFLOW
(Cfm)
0.1
Rpm
Watts
1200
542
168
1300
576
210
1400
610
252
1500
646
294
1600
681
347
1700
718
410
1800
754
473
1900
791
546
2000
828
630
AIRFLOW
(Cfm)
1.1
Rpm
Watts
1200
1052
762
1300
1065
846
1400
1087
890
1500
1111
980
1600
1134
1069
1700
1158
1164
1800
1182
1263
1900
1205
1363
2000
1228
1472
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable watts of a factory-supplied motor.
4. Maximum usable watts input is 1000. Extensive motor and electrical testing on these units ensures that the full range of the motor can be
utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.
5. Values include losses for filters, unit casing, and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your distributor to verify.
7. Alternate motor drive range: 840 to 1185 rpm. All other rpms require field-supplied drive.
8. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .75
Table 9 — 558D060 Air Delivery — Vertical Discharge Units (Standard Motor)
AIRFLOW
(Cfm)
208 v
ESP
Watts
1500
0.88
750
1600
0.68
780
1700
0.51
810
1800
0.35
839
1900
0.26
873
2000
0.18
905
2100
0.08
940
2200
2300
2400
2500
LEGEND
ESP — External Static Pressure (in. wg)
NOTES:
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your
fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be af-
fected. For additional information on motor performance, refer to Table 4.
3. Use of field-supplied motor may affect wire sizing. Contact your distributor to verify.
4. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .67
0.2
0.3
Rpm
Watts
Rpm
Watts
616
221
678
278
644
263
704
326
673
315
732
378
704
368
761
436
735
420
790
494
768
483
836
562
801
557
851
641
836
630
832
720
870
714
864
809
ALTERNATE BELT DRIVE MOTOR
External Static Pressure (in. wg)
1.2
1.4
Rpm
Watts
Rpm
Watts
1096
820
1134
835
1101
904
1174
1040
1121
918
1183
1042
1145
1014
1208
1138
1168
1100
1232
1253
1192
1196
1255
1358
1217
1301
1279
1473
1240
1406
1303
1588
1262
1511
1327
1702
Low Speed
230, 460, 575 v
ESP
Watts
ESP
1.20
791
1.19
1.04
824
1.04
0.89
857
0.89
0.73
891
0.74
0.58
924
0.59
0.42
957
0.44
0.27
990
0.29
0.19
1023
0.19
0.11
1056
0.11
0.03
1096
0.04
ALTERNATE BELT DRIVE MOTOR
External Static Pressure (in. wg)
0.4
0.6
Rpm
Watts
Rpm
Watts
739
336
842
764
389
867
791
441
889
818
504
912
845
567
920
873
641
965
900
725
992
828
809
1019
858
904
1046
1.6
1.8
Rpm
Watts
Rpm
Watts
1203
885
1242
1229
1100
1277
1255
1167
1305
1274
1272
1337
1291
1396
1350
1314
1511
1370
1381
1635
1393
1408
1769
1417
1436
1894
1440
STANDARD DIRECT DRIVE MOTOR
Medium Speed
208 v
230, 460, 575 v
Watts
ESP
782
1.36
821
1.22
861
1.09
900
0.96
940
0.86
979
0.73
1018
0.59
1035
0.46
1076
0.34
1113
0.19
0.09
—22—
0.7
Rpm
Watts
Rpm
462
886
525
929
525
910
588
952
578
933
651
976
641
957
720
1001
695
931
772
1023
777
1005
853
1045
858
1032
940
1071
950
1058
1037
1097
1053
1085
1139
1124
969
1029
1190
1350
1558
1738
1907
2068
2229
High Speed
208 v
Watts
ESP
Watts
845
1.38
875
883
1.25
913
921
1.13
950
959
1.00
988
997
0.88
1025
1035
0.78
1063
1073
0.63
1101
1111
0.49
1138
1149
0.41
1176
1187
0.22
1213
1225
0.12
1251
0.8
1.0
Watts
Rpm
Watts
588
1008
704
651
1029
788
725
1052
826
777
1076
905
848
1100
995
930
1124
1084
1022
1147
1174
1124
1169
1263
1237
1194
1373
230, 460, 575 v
ESP
Watts
1.44
949
1.33
988
1.22
1027
1.11
1066
1.00
1105
0.92
1144
0.81
1183
0.69
1222
0.59
1261
0.43
1300
0.34
1340

Advertisement