Built-in single-zone expander keypad

Advertisement

SPECIFICATIONS
Dimensions:
4-7/8"H x 6-1/4"W x 1"D
Wiring
Terminals:
Description
GM
Data In to Control Panel
– Ground (12 VDC –)
+
+ 12 VDC Power Input
LY
Data Out from Control Panel
ZN1
+ Wired Zone 1
- Wired Zone 1
LEGEND
= -
Note: The keypad will display "OC" and beep
periodically when there is a fault that prevents
data from reaching the keypad.
Display:
Fixed word LCD, backlit.
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS
DEVICE IS USED FOR WARRANTY INFORMATION AND FOR LIMITATIONS OF THE ENTIRE ALARM
SYSTEM.
‡K6206V1EŠ
K6206V1 6/06 Rev. B
WWW.DIYALARMFORUM.COM
165 Eileen Way, Syosset, New York 11791
Copyright © 2006 Honeywell International Inc.
www.honeywell.com/security
WWW.DIYALARMFORUM.COM
Sounder:
Piezo (fire alarm sound is loud, temporal pattern
pulsed tone; burglary alarm sound is loud, continuous,
dual tone).
Voltage:
+12 VDC
Current:
Alarm rating: 80mA (LCD backlight on, sounder on)
Standby rating: 50mA (LCD backlight on, sounder off);
35mA (LCD backlight off, sounder off)
The
control
panel
backlighting is on or off. When determining the
capacity of the control panel's backup battery, use the
following chart:
If Backlighting is . . .
On steadily
Off
when
keypad
inactive
determines
whether
Then . . .
Use the 50mA current
rating
is
Use the 35mA current
rating.