Installation And Wiring Terminals; Enrolling; Iv. Enrolling - GE NX-1710E - Single Door Control Module Installation And Start-Up Manual

Single door control networx series
Table of Contents

Advertisement

III.
WIRING TERMINALS
To install the door control, simply wire it into the system. Refer to the following wiring table for details.
For the purpose of these instructions, the term "door control" refers to the NX-1710E module, and
the term "reader" refers to the specific card reader attached to the system.
Connect to the NetworX control panel DATA terminal. Data-signaling terminal to all the
DATA
devices on the bus.
Connect to the NetworX control panel COMMON terminal. Supplies the common side of the
COM
power to the door control module.
Connect to NetworX control panel AUX POWER + terminal. Supplies power to the door
POS
control module.
+12
Power to reader module, if required.
+5
Power to reader module, if required.
COM
Connect to common terminal of box tamper.
TMPR
Box Tamper
N/C
Normally closed relay contact to activate door strike.
C
Closed relay contact to activate door strike.
N/O
Normally open relay contact to activate door strike.
Egress input. To use this feature, connect the normally open egress switch between this
A-EG
terminal and COM.
Tamper input (from Reader "A")
A-TM
Red LED (
A-LR
reader.
Green LED (
A-LG
reader.
A-BZ
Buzzer control (to Reader "A").
A-D1
Wiegand Data 1 terminal (from Reader "A").
A-D0
Wiegand Data 0 terminal (from Reader "A").
COM
Common dry contact
Egress input. To use this feature, connect the normally open egress switch between this
B-EG
terminal and COM.
B-RM
Tamper input (from Reader "B")
Red LED (
B-LR
reader.
Green LED (
B-LG
reader.
B-BZ
Buzzer control (to Reader "B").
B-D1
Wiegand Data 1 terminal (from Reader "B").
B-D0
Wiegand Data 0 terminal (from Reader "B").
COM
Common terminal.
DOOR
Door contact (requires 3.3K end-of-line resistor).
IV.

ENROLLING

The NetworX control panels have the ability to automatically find and store in memory the presence of all
keypads, zone expanders, wireless receivers, output modules, and any other device on the keypad buss. This
allows these devices to be supervised by the control panel. To enroll the devices, enter the Program Mode
using the procedure outlined in the control panel Installation Manual. When the Program Mode is exited, the
NX-8 control will automatically enroll the devices. The enrolling process takes about 12 seconds, during which
time the Service LED will illuminate. User codes will not be accepted during the enrolling process. Once a
module is enrolled, if it is not detected by the control, the Service LED will illuminate.
6
DESCRIPTION
) control (to Reader "A"). Relay. If available, connect to LED control on
LED2
) control (to Reader "A"). Relay. If available, connect to LED control on
LED1
) control (to Reader "B"). Relay. If available, connect to LED control on
LED2
) control (to Reader "B"). Relay. If available, connect to LED control on
LED1
Rating:
5A 125, 277V AC
5A 30V DC
NX-1710E Single Door Control

Advertisement