Floor Plan Grid; Power Plug Configuration - HP Rp3440-4 - 9000 - 0 MB RAM Manual

Generic site preparation guide
Hide thumbs Also See for Rp3440-4 - 9000 - 0 MB RAM:
Table of Contents

Advertisement

Table 1-5 Product Technical Requirements Based on Customer Environments (continued)
Environment
Portable/Mobile
Special (or Contract)
1
The values in each row meet or exceed the stated industry equivalent class specifications.
2
The maximum elevation for all operating environmental classes is 3,050 m (10,007 ft).
3
Dry bulb temperature is the regular ambient temperature. Derate maximum dry bulb temperature 1 ºC/300 m (34
ºF/984 ft) above 900 m (2,953 ft).
4
Must be noncondensing environment.
5
With installed media, the minimum temperature is 10 ºC (50 ºF) and the maximum relative humidity is limited to
80%. Specific media requirements may vary.
6
Equipment design extremes as measured at the equipment inlet.
7
Target facility design and operational range.
8
For all values listed as "NA": local product groups must make business decisions for the appropriate values.
Include the possible addition of equipment or other changes in space requirements to the space
plan and create an equipment layout plan which contains provisions for the following:
Channels or fixtures used for routing data cables and power cables
Access to air-conditioning ducts, filters, lighting, and electrical power hardware
Power conditioning equipment
Cabinets for cleaning materials
Maintenance area and spare parts

Floor Plan Grid

Use a floor plan grid designing the location of equipment in the computer room. Also use the
floor plan grid when arranging the locations of the following items:
Air-conditioning vents
Lighting fixtures
Utility outlets
Access areas for power wiring and air-conditioning filters
Equipment cable routing
Doors

Power Plug Configuration

Several power cables are designed for use with HP servers. The region the server ships to will
determine which power cable ships with the server.
an overview of the power plug configurations available.
26
General Site Preparation Guidelines
Industry
Operating Environment (ambient)
1
Equivalent:
Temp ºC, dry bulb
ASHRAE
(ºF)
5
Allowable
4
5 to 40
(41 to 104)
Product specifications controlled by contract or other requirements.
2
3
Relative Humidity %:
Noncondensing
6
Recommended
Allowable
NA
8 to 90
Figure 1-2
to
Dew-point
4
(max)
7
Recommended
NA
28
Figure 1-11 (page 29)
provide
Rate of
Chg
ºC/hr,
max
(ºF/hr,
max)
NA