Installer Setup; Thermostat Key Locations - Honeywell T7351F2010 - Digital Thermostat, 3h Installation Instructions Manual

Commercial programmable thermostat for single- or multi-stage conventional/heat pump systems
Table of Contents

Advertisement

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT

INSTALLER SETUP

For most applications, the thermostat factory settings do
not need to be changed. Review the factory settings in
Table 2.
NOTE: When power is first applied to the thermostat, the
display will show all segments (see Fig. 6).
Table 2. Default Setpoints.
Control
Occupied
Heating
70° F (21° C) 55° F (13° C)
Cooling
75° F (24° C) 85° F (29° C)
Temporary Standby
Not Occupied12
StartTime
MonTueWedThuFri
System
Em Heat
Off Cool Auto
Fig. 6. LCD display of all segments.
CAUTION
Possible Equipment Damage.
Fan must be running when system is
operating.
Heat pump and electric heat systems must be
configured correctly to prevent equipment damage
caused by the system running without the fan.
Setup Using Keypad
The installer uses the Installer Setup to customize the
thermostat to specific systems
Text
Default
DEGREES 0
0 -1
CLOCK
0
0 - 1
KEYLOCK 0
0 - 3
62-0258—05
Temperature
Occupied
Not Occupied
HEAT
COOL
HEAT
Schedule
Day
Occupied
Not Occupied
Fig. 5. Thermostat key locations.
Not Occupied
Standby
67° F (19° C)
78° F (26° C)
Set
Set Schedule
Room
AM
PM
MinsDays
SatSunHol
Fan
Dehumid
OnAuto
Table 3. Installer Setup.
Choices
Degree Temperature Format
0: Degrees F
1: Degrees C
Clock Display Format
0: 12 hour
1: 24 hour
Keypad Lockout Level
0: None
1: Lockout all keys except Set Day, Set Time, Set Date, Set Holidays, Temporary
Occupied, Temporary Not Occupied, System, Fan, Up, Down and Information
2: Lockout all keys except Set Day, Set Time. Set Date, Set Holidays, Temporary
Occupied, Temporary Not Occupied, Up, Down and Information
3: Lockout all keys except Information
Set Day/Time
Day
Time
COOL
System
Clear
Start Time
Copy
HEAT COOL
A combination of key presses are required to use the
Installer Setup feature:
1. To enter the Installer Setup, press and hold both the
Run Schedule and the Copy keys until DEGREES
00 (or DEGREES 01) displays.
NOTE: Installer Setup will display WAIT and is
2. To advance to the next Installer Setup number,
press
NOTE: Pressing Run/Copy again while in this
3. To return to a Setup item, cycle through the options.
4. To change a setting, use the up
5. To exit the Installer Setup, press Run Schedule.
%
6. Display prompts SAV CFG (save configuration).
a. If you want to save the new configuration, use
the up
YES before pressing Run Schedule.
M19611
b. If you want the configuration to remain as it was
before starting this change, ensure the
display indicates SAV CFG NO and press Run
Schedule.
NOTE: Installer Setup is automatically exited after five
minutes with no key pressed. Upon this auto-
matic exit, all changes are lost.
Configuration
Configuration can be done with the keypad using the
Installer Setup (ISU).
4
Override
Temporary
Temporary
Occupied
Not Occupied
Fan
Run
Schedule
ON AUTO
M19610
unavailable for 30 seconds after power up.
.
mode displays the T7351 firmware version
number.
or down
key to change NO to
Notes
or down
key.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T7351

Table of Contents