Tandberg Data MSERIES Installation Manual page 44

M-series
Hide thumbs Also See for MSERIES:
Table of Contents

Advertisement

Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Table 8 AC Distribution
Unit Requirements, M2500
Distribution Unit Requirements
# of
Library
200-240V 50-60Hz supply voltage (Europe
Modules
& international, etc.)
1
Connect the library to an AC wall outlet rated
minimum 10A, minimum 1.00mm
cord with minimum 10A plug. Must be three
wire grounding plug and wall outlet.
2
Connect each library to a separate wall outlet
rated minimum 10A, minimum 1.00mm
<HAR> cord with minimum 10A plug. Must
be three wire grounding plug and wall outlet.
3
Select one of the following options:
• Connect each library to a separate wall
outlet rated minimum 10A, minimum
1.00mm
plug. Must be three wire grounding plug
and wall outlet.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
wire IEC60309 rated 16A. Must be three
wire ground plug and wall outlet and have
a ground warning label.
• Connect all libraries to one distribution unit
rated minimum 10A, minimum 1.00mm
<HAR> three wire cord permanently wired
to the electrical supply. Must be connected
with a three wire cable and have a ground
warning label.
44
2
<HAR> cord with minimum 10A
2
<HAR> three wire cord with three
Connecting the Library to AC Power
100-120V 50-60Hz supply voltage (USA,
Canada, Japan, etc.)
Connect the library to one UL listed AC
2
<HAR>
distribution unit rated 15A or 20A, with a
minimum 14AWG three wire cord, and a 15A
or 20A plug. Must be three wire grounding
plug and wall outlet.
Connect both libraries to one UL listed AC
2
distribution unit rated 15A or 20A, with a
minimum 14AWG three wire cord, and a 15A
or 20A plug. Must be three wire grounding
plug and wall outlet.
Select one of the following options:
• Connect no more than two libraries to each
of two AC distribution units rated 15A or
20A, with a minimum 14AWG three wire
cord, and a 15A or 20A plug. Must be three
wire grounding plug and wall outlet. The
AC distribution units must be plugged into
separate outlets served by separate circuit
breakers or fuses.
• Connect all libraries to one AC distribution
unit rated 20A, with a minimum 14AWG
three wire cord, with a 20A plug. Must be
three wire grounding plug and wall outlet.
2
• Connect all libraries to one AC distribution
unit rated minimum 20A, with a minimum
14AWG three wire cord, permanently
wired to the electrical supply.