Download Print this page

Advertisement

Quick Links

PID TEMPERATURE CONTROL UNIT
PID
E
co
Eco PID, PID Temperature Control Un�t
- 3 d�g�t process (PV) and 4 d�g�t set (SV) d�splay
- Temperature sensor �nput (TC,RTD)
- Programmable ON/OFF, P, PI, PD and PID control forms
- Adaptat�on of PID Coeff�c�ents to the system w�th Self-Tune and Auto-Tune
- Programmable Heat�ng or Cool�ng Funct�ons for Control Output
- Selectable Alarm Funct�ons for Alarm Output
- Ser�al RS485 Commun�cat�on (opt�onal)
Eco ser�es temperature controllers are des�gned for measur�ng and controll�ng a
temperature value. They can be used �n many appl�cat�ons w�th the�r TC and RTD
temperature measurement �nput, mult�-funct�on control outputs, selectable alarm
funct�ons.
They are ma�nly used �n glass, plast�c, petro-chem�stry, text�le, automot�ve and mach�ne
product�on �ndustr�es. Accurate and advanced controll�ng �s performed w�th selectable
ON-OFF, P, PI, PD, PID and Self Tune/Auto Tune PID funct�ons.
SPECIFICATIONS
Process Input: TC, RTD
Thermocouple (TC): J, K, R, S, T and L (IEC584.1)(ITS90)
Thermores�stance (RTD): Cu-50 and PT-100 (IEC751)(ITS90)
Measurement Range: Please refer to process �nput type select�on �n process menu
parameters sect�on.
Accuracy:
Thermocouple (TC):( ± 0.25% of full scale or ± 3ºC, wh�ch one �s greater) ±1 d�g�t max.
Thermores�stance (RTD):( ± 0.25% of full scale or ± 2ºC, wh�ch one �s greater) ±1 d�g�t
max.
Cold Junct�on Compensat�on: Automat�cally ±0.1°C/1°C
L�ne Compensat�on: Max�mum 10 Ohm
Sensor Break Protect�on: Upscale
Sampl�ng Cycle: 0.1 second
Input F�lter: Programmable
Control Form: ON/OFF, P, PI, PD or PID (Control form can be programmed by the user)
OUTPUT
Process Output: Relay (5A@250VV at res�st�ve load) or SSR Dr�ver Output
(Max�mum 10mA, Max. 12VZ )
Alarm Output: Relay (5A@250VV at res�st�ve load)
SUPPLY VOLTAGE
230VV (±15%) 50/60Hz - 2VA
115VV (±15%) 50/60Hz - 2VA
10...30VZ - 2W
(It must be determ�ned �n order)
DISPLAY
Process D�splay: 16 mm Red 3 d�g�t LED D�splay
Set Value D�splay: 9 mm Orange 4 d�g�t LED D�splay
Led Ind�cators: PO1 (SSR Process Output Status Led), PO2 (Relay
Process Output Status Led), AL1, AL2 (Alarm Output Status Leds),
ºC, ºF LEDs
ENVIRONMENTAL RATINGS and PHYSICAL SPECIFICATIONS
Operat�ng Temperature: 0...50ºC
Hum�d�ty : 0-90%RH (none condens�ng)
Protect�on Class: IP65 at front, IP20 at rear
We�ght: 150 gr.
D�mens�on: 48 x 48 mm, Depth: 86,5 mm
Panel CutOut: 46 x 46 mm

Advertisement

loading
Need help?

Need help?

Do you have a question about the Eco PID and is the answer not in the manual?

Questions and answers

Summary of Contents for EMKO Eco PID

  • Page 1 PID TEMPERATURE CONTROL UNIT Eco PID, PID Temperature Control Un�t - 3 d�g�t process (PV) and 4 d�g�t set (SV) d�splay - Temperature sensor �nput (TC,RTD) - Programmable ON/OFF, P, PI, PD and PID control forms - Adaptat�on of PID Coeff�c�ents to the system w�th Self-Tune and Auto-Tune - Programmable Heat�ng or Cool�ng Funct�ons for Control Output...
  • Page 2 Electr�cal W�r�ngs The Dev�ce w�th One Relay: Ser�al Commun�cat�on (RS485, Modbus RTU) AL1 / PO2 (Alarm Output 1 or Process Output 2) SSR Output (Process Output 1) Max. 10mA Process Supply Input Voltage Supply Fuse Sw�tch The Dev�ce w�th Two Relays: AL2 / PO2 Ser�al Commun�cat�on (Alarm Output 2 or...
  • Page 3 Easy Access D�agram For Program Parameters Ma�n Screen Password Screen °C °C °C °F °F °F Press Program button Enter Password w�th �ncrement Approve password to access password screen. or decrement buttons. w�th Enter button °C °C °C °C °C °C °C °F...
  • Page 4 Easy Access D�agram For Sensor Break Output Value From Ma�n Screen °C °F Ma�n Screen Ma�n Screen °C °C °C °C °F °F °F °F °C °F Press Enter button to save Change the sensor break new sensor break output value output value w�th �ncrement and ex�t.
  • Page 5 : Process Menu Parameters : Process �nput type select�on; (Default: ) Modbus Address: 40004 : J type (Fe,Cu,N�) Thermocouple , -199ºC,900ºC ; -199ºF,999ºF : J type (Fe,Cu,N�) Thermocouple , -19.9ºC,99.9ºC ; -19.9ºF,99.9ºF : K type (N�,Cr,N�) Thermocouple , -199ºC,999ºC ; -199ºF,999ºF : K type (N�,Cr,N�) Thermocouple , -19.9ºC,99.9ºC ;...
  • Page 6: Alarm Types

    : Alarm-2 Menu Parameters (Only for dev�ces w�th two relays) Alarm-2 menu parameters can be seen only �f parameter �s : Alarm-2 set value. (Default: 400) Modbus Address: 40046 : Alarm-2 hysteres�s value. It can be adjusted from %0 to %50 of the Scale ).
  • Page 7: Error Messages

    Alarm Output Process Alarm Process Alarm Process Dev�at�on Band Alarm Alarm Alarm Hysteres�s Hysteres�s Process Value Alarm Output Process Alarm Process Alarm Process Dev�at�on Range Alarm Alarm Alarm Hysteres�s Hysteres�s Process Value Alarm Output Process Alarm Process Dev�at�on Range H�gh Alarm Alarm Hysteres�s Process Value...
  • Page 8 Warranty EMKO Elektron�k warrants that the equ�pment del�vered �s free from defects �n mater�al and workmansh�p. Th�s warranty �s prov�ded for a per�od of two years. The warranty per�od starts from the del�very date. Th�s warranty �s �n force �f duty and respons�b�l�t�es wh�ch are determ�ned �n warranty document and �nstruct�on manual performs...