Page 1
Electromotoric actuators SSB.. For globe/control valves VVP45.., VXP45.., VMP45.. in zone and room applications ● SSB131.09.. operating voltage AC 24 V, 3-position control signal ● SSB331.09.. operating voltage AC 230 V, 3-position control signal ● SSB161.05.. Operating voltage AC/DC 24 V, positioning signal DC 0...10 V ●...
Page 2
For water-side control of hot and chilled water in heating, ventilation and air conditioning systems with: ● Siemens VVP45.., VXP45.. and VMP45.. valve series (DN ≤ 25, Kvs ≤ 6.3 m Technical design When the actuator is driven by a 3-position or DC 0…10 V control signal, it produces a stroke which is transmitted to the valve spindle.
Flashing green (LED2): 100 ms on, 100 ms off Error* Constant red (LED2) Manual operation Flashing green/red alternatively (LED2): Green 500 ms, red 500 ms * Error caused by mechanical jam or calibration failure. Calibration through resetting the operating voltage required. Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 5
● Threaded connections with coupling nut: – SSB..: ¾”; open dimension X ≥ 8.8 mm; closed dimension Y ≤ 14.3 mm ● Nominal force F ≤ 200 N – SSB..: 200 N Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 7
The mounting instructions are enclosed with the product. Related documents such as the environmental declarations, declarations of conformity, etc., can be downloaded from the following Internet address: www.siemens.com/bt/download Notes Engineering The actuators must be electrically connected in accordance with local regulations (see "Connection diagrams...
Page 8
CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. ● Observe national provisions and comply with the appropriate safety regulations. Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 9
The actuator must be commissioned only with a correctly mounted valve in place! Self-calibration When operating voltage is applied, the actuator self-calibrates (fully retracted ➙ fully extended ➙ setpoint). Fully retracted Fully extended Calibration Power CAUTION Never intervene manually during self-calibration. Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 10
– The actuator spindle moves down if you rotate clockwise; it moves up if you rotate counter-clockwise. The manually set position is retained. 3. Close the cover to ensure IP54 protection. 3 mm Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 11
Cabling operation SSB..H, SSB..H/00 1. Unscrew cover screw* 2. Remove cover* 3. Select the desired ASY.. cable kit to be plugged-in 4. Install the cover 5. Screw in the cover screw * Not applicable for SSB..H/00 Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 12
● If necessary, disconnect electrical connections from the terminals. ● The actuator must be commissioned only with a correctly mounted valve in place! Repair The actuators cannot be repaired; the complete unit must be replaced. Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 13
Comply with all local and currently applicable laws and regulations. Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used.
Page 14
Electrical connection (connecting cable integral) (SSB..UT) Cable length <20 m Cross section of prewired connection cables 0.5...1.5 mm Cable diameter <5.5 mm Mounting SSB..H SSB..UT ¾” plastic threaded coupling nut Fixing on valve Orientation 360° 270°, cable down Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 15
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Housing color Cover/base 2003, Ti-Gray Coupling nut Plastic Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Y2 = Control signal CLOSE (AC 230 V) N = Neutral SSB161.05HF, SSB161.05HF/00 G = System potential (AC/DC 24 V) Y = Positioning signal DC 0…10 V U = Positioning feedback signal M = Measurement reference G0 = System neutral Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 17
Neutral switch Hot switch N = Controller Y = Actuator SP, G = System potential AC 24 V SN, G0 = System neutral Y1, Y2 = Control signal OPEN, CLOSE Q1, Q2 = Controller contacts Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 18
N = Controller Y = Positioning signal (DC 0…10 V) SP, G = System potential (AC/DC 24 V) SN, G0 = System neutral (U) (M) U = Positioning feedback signal M = Measurement reference SN (-) Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...
Page 19
Dimensions SSB..H, SSB..H/00 SSB..UT *: The maximum cable gland thread length is 11 mm. Revision numbers Type Valid from rev. no. Type Valid from rev. no. SSB331.09H SSB131.09H SSB331.09H/00 SSB131.09H/00 SSB131.09UT SSB161.05HF SSB161.05HF/00 SSB161.05UT SSB331.09UT Siemens A6V15348908_en--_a Smart Infrastructure 2024-12-06...