Elimko 1. INTRODUCTION This user manual is released for E-48, E-49, E-72, E-94, E-200, E-2000M series controllers and contains detailed information about common features and common parameter explanations. Depending on the controller, some parameters may not be exist because of different hardware and IO properties.
Elimko 2. POWER ON AND CONTROL MODES During first couple of seconds after power on, all segments and LED indicators light. After that, upper display shows controller model and lower display shows firmware version for a duration of 3 seconds and eventually Process Screen are displayed.
Elimko 3. FRONT PANEL KEYS AND PROGRAMMING Pressing 4 key returns to the Process Screen. Pressing 3 key accesses to next available screen. 12 keys are used to adjust parameter values. In order to reach and adjust a parameter, the operator needs to know in which page the parameter is located.
Page 6
Elimko 3. FRONT PANEL KEYS AND PROGRAMMING General Set Point Alarm Output Security Security Configuration Configuration Configuration Configuration Configuration Configuration Code PAGE PAGE PAGE PAGE PAGE PAGE GCNF SETP ACNF OCNF TUNE PRTC INP1 SPSR A1TP CTYP SCOD A1SP CFRM...
Elimko 3.1. Process Screen and Operation Parameters Unit Screen Definition Access 200. 1 Process Screen Always 200. 0 Process Screen is the power on screen of the controllers and pressing 4 key returns to this screen anytime. In this screen, upper display always shows process value.
Elimko 3.2. Accessing Configuration Pages In order to access configuration pages, the operator needs to reach security Cod entry screen by pressing 4 and 3 keys together as the first step. Factory settings of Security Code is 10. Screen Definition...
Page 9
Elimko 3.1. Process Screen and Operation Parameters When an error is detected in process value measurement (Analog Input 1) or measurement value is non displayable, upper display shows one of the following messages. OPEN : Sensor broken or not connected.
Elimko 3.3. General Configuration Page (GCNF) Unit Access Screen Definition INP1 Analog Input 1 Type Always Input Type Max. Standard Min. B: Type B Thermocouple IEC 60584-1 1820 °C E: Type E Thermocouple IEC 60584-1 -200 840 °C J: Type J Thermocouple...
Page 11
Elimko 3.3. General Configuration Page (GCNF) Screen Definition Unit Access UNIT Analog Input 1 Temperature Unit °C Temperature Sensor This parameter is monitored when INP1 (Analog Input 1 Type) is selected as Thermocouple or Resistance Thermometer. OFST Analog Input 1 Offset Value -100.0 100.0...
Page 12
Elimko 3.3. General Configuration Page (GCNF) Screen Defintion Unit Access S2LO Analog Input 2 Devices have -199.9 999.9 Linear Scale Lower Value 2 Analog Inputs 0. 0 Analog Input 2 S2HI Devices have -199.9 999.9 Linear Scale Upper Value 2 Analog Inputs 400.
Elimko 3.4. Control Set Point Configuration (SETP) Screen Definition Unit Access SPSR Control Set Point Source Always : Internal. Adjusted using front panel keys PRFL : Defined by Profile Parameters : Defined by Analog Input 2 measurement DINP : Selected by Digital Inputs (Available only in devices with digital inputs.)
Page 14
Elimko 3.4. Control Set Point Configuration (SETP) Screen Definition Unit Access Step Set Value (X = 1 .. 3) SPLL SPHL SPSR = PRFL 50. 0 Step Time (X = 1 .. 3) 999.9 SPSR = PRFL 2. 0 These are the parameters that needs to be set when the control set point source SPSR is set to PRFL.
Page 15
Elimko 3.4. Control Set Point Configuration (SETP) Screen Definition Unit Access SETx Set Values are selected with SPLL SPHL SPSR = DINP Digital Inputs (X = 1 .. 4) 0. 1 Four control set point (SET1, SET2, SET3, Digital Set1...
Elimko 3.5. Alarm Configuration Page (ACNF) Four alarms are defined in the device. Alarm Type, Set Value, Hysteresis and Alarm Lock paremeters can be set for each alarms. The alarm singnals can be assigned to required relays available on the device.
Page 17
Elimko 3.5. Alarm Configuration Page (ACNF) EXPLANATION Axtp Not active when set to OFF. Alarm AxHY Alarm AxSP Alarm AxHY High Alarm AxSP Alarm AxHY Deviation SP + AxSP Alarm AxHY High Deviation SP + AxSP Alarm AxHY AxHY In Band...
Elimko 3.6. Output Configuration Page (OCNF) Screen Definition Unit Access CTYP Control Type Always None : Off : Single Control Output (+) Heat : Double Control Output (+ / -) Heat /Cool : Floating Valve Control : Feedback Controlled Valve Control (Available only in the devices with servo feedback input.)
Page 19
Elimko 3.6. Output Configuration Page (OCNF) Screen Definition Min. Max. Unit Access Control Output Lower Limit 0.0* CTYP ≠ NONE 0. 0 * CTYP = DCO, the lower value that can be set is -100.0. Negative values indicate cooling. Control Output Upper Limit 100.0...
Page 20
Elimko 3.6. Output Configuration Page (OCNF) Screen Min. Max. Unit Definition Access RLxD Relay Functions (x = 1..4 Relasy) Always CO-1 Parameters that determine the functions of the relays in the device. (RL1D, RL2D, RL3D, RL4D) CO-1 : PID + signal (Heating)
Elimko 3.7. PID Configuration Page (TUNE) Screen Min. Max. Unit Definition Access PID Auto Tune CTYP ≠ NONE OFF : Cancels the automatic tuning in progress. : Starts automatic tuning. All PID parameters can be calculated automatically using the Auto PID Tuning feature.
Page 22
Elimko 3.7. PID Configuration Page (TUNE) Screen Min. Max. Unit Definition Access PID Parameter Type CTYP ≠ NONE STD : Standard PID parameters ADV : Advanced PID parameters If selected as ADV, different values can be used for the integral time and derivative time, depending on the state and level of the process value with respect to the control setpoint.
Page 23
Elimko 3.7. PID Configuration Page (TUNE) Screen Min. Max. Unit Definition Access PB-2 Proportional Band - 999.9 CTYP = DCO 20. 0 Proportional band for PID output in the negative (cooling) direction. Integral Time + saniye 9999 CTYP ≠ NONE Integral time used when the process value is below the setpoint.
Elimko 3.8. Security Configuration Page (PRTC) Screen Min. Max. Unit Definition Access SCOD Security Code 9999 Always This is the security code that is asked when accessing the configuration pages. DPRL Always Parameter Access Level Determines the pages that can be monitored in case the security code is entered incorrectly when accessing the configuration pages.
Page 25
Elimko 3.8. Security Configuration Page (PRTC) Screen Min. Max. Unit Definition Access FCST Factory Settings Always OFF : It does not perform any operation. LOAD : Loads the settings previously backed up with SAVE operation. SAVE : Backs up the device settings.
Elimko 4. CONFIGURATION STEPS AND APPLICATIONS The recommended configuration sequence is given below. It is not obligatory to perform the configuration in the order described. Detailed descriptions of all parameters described can be found on the relevant configuration pages. Device configuration should be started from the General Configuration page (GCNF).
Elimko 4. CONFIGURATION STEPS AND APPLICATIONS The device has 4 alarms that can be used for different purposes. For each alarm, the alarm type parameters (A1TP, A2TP, A3TP, and A4TP) can be configured according to the desired alarm type, and the relevant set point (A1SP, A2SP, A3SP, and A4SP), hysteresis (A1HY, A2HY, A3HY, and A4HY), and lock (A1LT, A2LT, A3LT, and A4LT) parameters can be adjusted.
Elimko Open-Loop Valve Control (Floating Control) The control type should be selected as Close (CO-2) CTYP = bnd. In this control type, the valve is controlled using Open and Close signals without feedback. The 250 V AC Floating Open Open signal is assigned to the CO-1...
Elimko 5. MODBUS COMMUNICATION Devices with communication feature operate as Modbus RTU Slaves. The supported functions are listed below. All data, except for the status bits, is in signed, word (2-byte) and big-endian format. 03 : Read Holding Registers 05 : Write Single Coil...
Page 30
Elimko 5. MODBUS COMMUNICATION Register Address Table Address Access Parameter Explanation Max. Min. Status Bits 1 Status Bits 2 Process Value Progressive Set Point Reserved Reserved Reserved Remainning Step Time Decimal Point SPSR Control Set Point Source Control Type CTYP...
Page 31
Elimko 5. MODBUS COMMUNICATION Register Address Table Address Access Parameter Explanation Max. Min. Hysteresis 9999 SPSR Control Set Point Source Control Set Point Lower Limit SPLL -1999 9999 Control Set Point Upper Limit SPHL -1999 9999 SPRR Control Set Point Ramping Rate...
Page 32
Elimko 5. MODBUS COMMUNICATION Register Address Table Address Access Parameter Explanation Max. Min. RL2D Relay 2 Function RL3D Relay 3 Function Relay 4 Function RL4D Analog Output 1 Function AO1D AO2D Analog Output 2 Function AO1R Analog Output 1 Type...
Page 33
Elimko 5. MODBUS COMMUNICATION Register Address Table Address Access Parameter Explanation Max. Min. Reserved 3. Step Set Value -1999 9999 3. Step Time 9999 Reserved Reserved Coil Address Table 0 (Reset) 1 (Set) Adrress Access Parameter Explanation Manual Manual/Auto Mod...