Elimko 1. INTRODUCTION This user manual is released for E-48P, E-72P, E-96P series controllers and contains detailed information about common features and common parameter explanations. Depending on the controller, some parameters may not be exist because of different hardware and IO properties.
Elimko 2. POWER ON AND CONTROL MODES During first couple of seconds after power on, all segments and LED indicators light. After that, upper display shows controller model and lower display shows firmware version for a duration of 3 seconds and eventually Process Screen are displayed.
Elimko 3. FRONT PANEL KEYS AND PROGRAMMING Pressing key returns to the Process Screen Pressing key accesses to next available screen. keys are used to adjust parameter values. In order to reach and adjust a parameter, the operator needs to know in which page the parameter is located.
Page 6
Elimko 3. FRONT PANEL KEYS AND PROGRAMMING Alarm General Set Point Output Security Security Configuration Configuration Configuration Configuration Configuration Configuration Code PAGE PAGE PAGE PAGE PAGE PAGE GCNF SETP ACNF OCNF TUNE PRTC INP1 SPSR A1TP CTYP SCOD A1SP CFRM...
Elimko 3.1. Process Screen and Operation Parameters Unit Screen Definition Access 200. 1 Process Screen Always 200. 0 Pro es s Screen is the power on screen of the controllers and pressing returns to this screen anytime. In this screen, upper display always shows process value Lower display shows either control set point or manual output value depending on selected control mode.
Page 8
Elimko 3.1. Process Screen and Operation Parameters When an error is detected in process value measurement (Analog Input measurement value is non displayable, upper display shows one of the following messages. OPEN : Sens or broken or not connected Input signal is above sensor limits...
Page 9
Elimko 3.2. Accessing Configuration Pages In order to access configuration pages, the operator needs to reach security entry screen by pressing keys together as the first step. Factory settings of Security Code is 10. Screen Definition Unit Access Security Code Entry...
Page 10
Elimko 3.3. Gene ral Configuration Page GCNF Unit Access Screen Definition INP1 Analog Input Always Input Type Standard Min. Ma . x B: T p B T hermocouple IEC 60584-1 1820 °C E: T p y e E hermocouple IEC 60584-1 -200 840 °C...
Elimko 3.3. General Conf gurat on Page ( GCNF Screen Def n t on Un t Access UNIT Analog Input 1 Temperature Un t °C Temperature Sensor Th s parameter s mon tored when INP1 ( Analog Input 1 Type ) s selected as Thermocouple or Res stance Thermometer.
Page 12
Elimko 3.3. General Conf gurat on Page ( GCNF Screen Def nt on Un t Access S2LO Analog Input 2 Dev ces have -199.9 999.9 L near Scale Lower Value 0. 0 2 Analog Inputs Analog Input 2 S2HI Dev ces have -199.9 999.9...
Elimko 3.4. Control Set Po nt Conf gurat on ( SETP Screen Def n t on Un t Access SPSR ontrol Set Point Source Always : Internal. Adjusted us ng front panel keys PRFL : Def ned by Prof le Parameters...
Page 14
Elimko 3.4. Control Set Po nt Conf gurat on ( SETP Screen Def n t on Un t Access Step Set Value ( = 1 .. 3) SPLL SPHL SPSR PRFL 50. 0 Step T me ( = 1 .. 3) 999.9...
Page 15
Elimko 3.4. Control Set Po nt Conf gurat on ( SETP Screen Def n t on Un t Access Set Values are selected w th SETx SPLL SPHL SPSR DINP D g tal Inputs ( = 1 .. 4) 0. 1...
Elimko 3.5. Alarm Conf gurat on Page ( ACNF Four alarms are def ned n the dev ce. Alarm Type, Set Value, Hysteres s and Alarm Lock paremeters can be set for each alarms. The alarm s ngnals can be ass gned to requ red relays ava lable on the dev ce.
Page 17
Elimko 3.5. Alarm Conf gurat on Page ( ACNF EXPLANATION A tp Not active when set to Alarm A HY Alarm A SP Alarm A HY High Alarm A SP Alarm A HY Deviation SP + A SP Alarm A HY...
Elimko 3.6. Output Conf gurat on Page ( OCNF Screen Def n t on Un t Access CTYP Control Type Always None : Off : S ngle Control Output (+) Heat : Double Control Output (+ / -) Heat /Cool...
Page 19
Elimko 3.6. Output Conf gurat on Page ( OCNF Screen Definition M n. Max. Un t Access Control Output Lower L m t 0.0* CTYP ≠ NONE 0. 0 CTYP , the lower value that can be set s -100.0. Negat ve values nd cate cool ng.
Page 20
Elimko 3.6. Output Conf gurat on Page ( OCNF Screen M n. Max. Un t Definition Access RLxD Relay Funct ons (x = 1..4 Relasy Always CO-1 Parameters that determ ne the funct ons of the relays n the dev ce.
Elimko 3.7. PID Conf gurat on Page ( TUNE Screen M n. Max. Un t Definition Access PID Auto Tune CTYP ≠ NONE : Cancels the automat c tun ng n progress. : Starts automat c tun ng. All PID parameters can be calculated automat cally us ng the Auto PID Tun ng feature.
Page 22
Elimko 3.7. PID Conf gurat on Page ( TUNE Screen M n. Max. Un t Definition Access PID Parameter Type CTYP ≠ NONE : Standard PID parameters : Advanced PID parameters If selected as , d fferent values can be used for the ntegral t me and der vat ve t me, depend ng on the state and level of the process value w th respect to the control setpo nt.
Page 23
Elimko 3.7. PID Conf gurat on Page ( TUNE Screen M n. Max. Un t Definition Access PB-2 Proport onal Band - 999.9 CTYP 20. 0 Proport onal band for PID output n the negat ve (cool ng) d rect on.
Page 24
Elimko 3.8. Secur ty Conf gurat on Page ( PRTC Screen M n. Max. Un t Definition Access SCOD Security Code 9999 Always Th s s the secur ty code that s asked when access ng the conf gurat on pages.
Page 25
Elimko 3.8. Secur ty Conf gurat on Page ( PRTC Screen M n. Max. Un t Definition Access FCST Factory Sett ngs Always : It does not perform any operat on. LOAD : Loads the sett ngs prev ously backed up w th SAVE operat on.
Elimko 4. CONFIGURATION STEPS AND APPLICATIONS The recommended conf gurat on sequence s g ven below. It s not obl gatory to perform the conf gurat on n the order descr bed. Deta led descr pt ons of all parameters descr bed can be found on the relevant conf gurat on pages.
Page 27
Elimko 4. CONFIGURATION STEPS AND APPLICATIONS The device has 4 alarms that can be used for different purposes. For each alarm, A1TP A2TP A3TP A4TP the alarm type parameters ( , and ) can be configured A1SP A2SP A3SP according to the desired alarm type, and the relevant set point (...
Elimko Open-Loop Valve Control (Float ng Control) The control type should be selected as Close CO-2 CTYP . In th s control type, the valve s controlled us ng Open and Close s gnals w thout feedback. The 250 V AC...
Page 29
Elimko 5. MODBUS COMMUNICATION Dev ces w th commun cat on feature operate as Modbus RTU Slaves. The supported funct ons are l sted below. All data, except for the status b ts, s n s gned, word (2-byte) and b g-end an format.
Page 30
Elimko 5. MODBUS COMMUNICATION Reg ster Address Table Address Access Parameter Explanat on M n. Max. Status B ts 1 Status B ts 2 Process Value Progress ve Set Po nt Reserved Reserved Reserved Rema nn ng Step T me...
Page 31
Elimko 5. MODBUS COMMUNICATION Reg ster Address Table Address Access Parameter Explanat on M n. Max. Hysteres s 9999 SPSR Control Set Po nt Source Control Set Po nt Lower L m t -1999 9999 SPLL Control Set Po nt Upper L m t...
Page 32
Elimko 5. MODBUS COMMUNICATION Reg ster Address Table Address Access Parameter Explanat on M n. Max. RL2D Relay 2 Funct on RL3D Relay 3 Funct on Relay 4 Funct on RL4D Analog Output 1 Funct on AO1D AO2D Analog Output 2 Funct on...
Page 33
Elimko 5. MODBUS COMMUNICATION Reg ster Address Table Address Access Parameter Explanat on M n. Max. Reserved 3. Step Set Value -1999 9999 3. Step T me 9999 Reserved Reserved Co l Address Table 0 (Reset) 1 (Set) Adrress Access...