E-48

PROCESS CONTROLLER

USER MANUAL
48
E-48 series universal process controllers are advanced new generation
microcontroller based industrial instruments designed for On/Off and PID
control forms, dimensions of 48x48 mm compatible with IEC/TR 60668
standarts. Universal inputs and outputs of controller can be programmed
easily by the user.
E-48 process controllers are equipment having high reading sensivity and
capability, with no moving parts, having infinite life and very low calibration
drift with time and environment conditions. Indicating method is 2x4 digit LED
display. E-48 indicating range is from -1999 to 9999 and is able to connect
mV, mA, thermocouple, resistance thermometer and other sensors and
transmitters. Controllers have high input empedance and protecting and
warning the system against the breakage sensors.
E-48 process controllers can be used in every field of the industry for the
measurement and control of temperature, pressure, level, speed, current,
voltage, resistance and other physical units; as well asin the industry
branches of iron&steel, cement, plastic, chemistry, metallurgy, petrochemical
refineries, ceramic, glass and others.
E-48 controller is designed for panel mounting and
should be used in an industrial environment.
The package of E-48 controller contains;
Controller and mounting bracket
User manual
Guarantee certificate
After opening the package, please check the contents with the
above list. If the delivered product is wrong type, any item is
missing or there are visible defects, contact the vendor from which
you purchased the product.
Before installing and operating the controller, please read the user
manual thoroughly.
The installation and configuration of the controller must only be
performed by a person qualified in instrumentation.
Keep the unit away from flamable gases, that could cause
explotions.
Do not use alcohol or other solvents to clean the controller.
Use a clean cloth soaked in water tightly squeezed to gently
wipe the outer surface of the controller.
The product life of this instrument is 10 years.
This controller complies with the European Low Voltage Directive
2006/95/EC, by the application of safety standard TS EN 61010-1.
(Pollution degree 2)
This controller complies with the EMC Directive 2004/108/EC
by the application of EMC standard TS EN 61326.

TECHNICAL SPECIFICATION

Thermocouple ( TC ) : B, E, J, K, L, N, R, S, T, U
Resistance Thermometer ( RT ) : Pt-100
Input Types
Current : 0-20 mA, 4-20 mA (Linear)
Voltage : 0-50 mV, 0-1 V, 0.2-1 V (Linear)
Relay : SPST-NO 250V AC, 3A
Control Output
Current : 0-20 mA, 4-20 mA, 20-0 mA, 20-4 mA (Isolated)
Pulse : 24V DC, 25 mA (for SSR) (Not Isolated)
Alarm Outputs
Relay : SPST-NO 250V AC, 3A
Display Type
2 x 4 digit 7 mm 7 segment led display
Thermocouple : (±0.5% of the reading value or ±1 C)
±1 digit max.
Accuracy
Pt-100 : (±0.5% of the reading value or ±1 C)
±1 digit max.
Analog Input: ±0.5% FS ±1 digit max.
Analog Digital Converter
16 bit
Digital Analog Converter
12 bit
Control Type
On/Off, PID
85-265 V AC / 85-375 V DC
Operating Voltage
20-60 V AC / 20-85 V DC
Power Consumption
4W (7 VA)
IP 66 Front Panel (NEMA 4X)
Protection Class
IP 20 Rear Case
o
o
o
-10 C, +55 C (+14 F, +131 F)
Operating Temperature
(with no condensation or icing)
o
o
o
-25 C, +65 C (-13 F, +149 F)
Storage Temperature
( with no condensation or icing )
10.000.000 operations
(The relay life differs according to the usage
Relay Mechanical Life
configuration. When the relays are old, their contacts
could melt or burn
out.)
Relay Electrical Life
>1.000.000 operations (under 1/10 of load)
Memory
EEPROM (100.000 max. write-erase)
Weight
155 g
TYPE CODING
0:No Output
1:
1 Analog Output (If Y=0)
E-48-W-X-Y-Z
0:85-265 V AC/85-375 V DC
1:
20-60 V AC/20-85 V DC
0:No Relay
1:
1 Relay
2:
2 Relays
0:None
3:
1 Pulse for SSR
1:
RS 485 (If X=0)
4:
1 Relay,1 Pulse for SSR

CONNECTION DIAGRAM

01
13
14
06
+24V
RL1
RL2
02
07
03
GND
08
04
09
A RS-485
B
05
11
12
10
20-60 VAC ; 50 - 60Hz
/ 20-85 VDC
85-265 VAC ; 50 - 60Hz / 85-375 VDC
The labels on the sides of the controller identify the ordering code
(Type), serial number and wiring connections.
The controller options are also indicated on the wiring diagram.
The terminals 01 to 05 are electrically live. While the
instrument is powered, never touch to these terminals.
Before operating the controller, ensure that the
controller is correctly configured. Incorrect
configuration could result in damage to the
process being controlled.
10 mm
E-48 controller should be installed inside a suitable
grounded metal enclosure (panel). This must
prevent the live parts being accessibleto human
hands and metal tools.
E-48 controller does not include a power switch.
Therefore, the power supply to the controller and power outputs
must be wired through the proper fuse or circuit breaker.
To minimize the pick-up of electrical noise, the wiring of low
voltage lines, particularly the sensor input should be routed away
from the high-current power cables. Where it is not possible, use
shielded cables with the shield grounded at both ends.
The cables used for powering the controller and the power
outputs must conform to the standarts IEC 60245 and IEC 60227.
+0.2
45 x 45 mm
-0.0
10 mm min.
Panel Cutout and Minimum Spacing
Cut a hole in the panel. (See the figure for overall dimensions.)
Remove the mounting bracket and slide the controller into the cutout
from the front of the panel.
Fit the mounting bracket and slide it until the controller is fastened.
o
R1 Led
o
R2 Led
PR Led
SF Led
o
o
R1 Led
When lit, it indicates that RL1 output is active.
R2 Led
When lit, it indicates that RL2 output is active.
PR Led
When lit, it indicates that the controller is in the
configuration mode.
SF Led
- When lit, it indicates that the controller is in manual mode.
- SF led will also flash when the auto-tuning is in progress.
Upper
- While in normal operation, it displays the process value or
error message.
Display
- While in configuration pages, it displays the name of the
parameters.
Lower
- While in normal operation, it displays the control set point
(Automatic mode) or manual output (Manual mode).
Display
- While in configuration pages, it displays the parameter
value.
 Star
- When pressed together with  button, password is asked
for entering the configuration page.
Button
- While in configuration pages, pressing this button reverts
to normal operation.
- While in normal operation, pressing this button for duration
Tx
3 seconds, toggles between automatic and manual mode.
This operation is disabled if the MPL parameter in page
PRTC is set to DSB or if the CNTL parameter in OCNF page is
Tx
set other than PID.
- While in normal operation, pressing this button
acknowledges the latched alarms if configured (AXLT = ON).
 Enter
- When pressed together with  button, password is asked
Button
for entering the configuration page.
mA
RT
- While in configuration pages, pressing this button selects
the next parameter.
TC
mV
- While in configuration pages, pressing this button for
duration 2 seconds, returns to the top of the page.
- While in normal operation, pressing this button selects the
next parameter in operator page.
E-48
Up/Down
- While in normal operation, these buttons can be used to
Buttons
edit the control set point (Automatic mode) or manual output
- While in configuration, these buttons can be used to select
the configuration pages and to edit the parameters.

DIMENSIONS

48 mm
44 mm
100 mm

PANEL MOUNTING

35 mm min.

FRONT PANEL

Upper
Display
Lower
Display
Up/Down
Enter
Star
Buttons
Button
Button
ALARM TYPES
A1tp
EXPLANATIONS
or
A1SP or a2sp > 0
A1SP or a2sp < 0
A2tp
Alarm State
1
LO
0
PV
PV
0
ASP
ASP
Alarm State
1
HI
0
PV
0
ASP
ASP
Alarm State
Alarm State
1
1
LOD
0
0
0
SP
SP+ASP
PV
0
SP+ASP
Alarm State
AlarmState
1
1
HID
0
0
0
SP
SP+ASP
PV
0
SP+ASP
Alarm State
Alarm State
1
1
LOB
0
0
0
SP-ASP SP SP+ASP
PV
0
Alarm State
Alarm State
1
1
HIB
0
0
0 SP-ASP
SP
SP+ASP
PV
0
OFF
Alarm function is cancelled when A1tp or A2TP parameters are off.
Alarm State
Shaded areas
1
show the
hysteresis.
0
AXHY
PV
0
ERROR MESSAGES
Message
Meaning
The connection of the sensor
Check the sensor and
Open
is broken.
the sensor connection.
The process value is below
Ufl
the sensor type-temperature
Check the sensor and
interval.
the input type specified
The process value is above
by the INPT parameter.
Ofl
the sensor type-temperature
interval.
The process value is
Nnnn
Check the analog value
above the value that can
on the input terminal
be displayed.
and the scalar specified
The process value is
by the Dp, Zero and span
Vvvv
below the value that can
parameters.
be displayed.

INPUT TYPES and RANGES

TEMPERATURE SENSORS

Temperature Range
Sensor Type
Standart
o
( C)
60 , 1820
Type B
B
IEC 60584-1
Type E
-200 , 840
E
IEC 60584-1
Type J
J
-200 , 1120
IEC 60584-1
Type K
-200 , 1360
K
IEC 60584-1
Type L
-200 , 900
L
DIN 43710
N
Type N
-200 , 1300
IEC 60584-1
Type R
R
-40 , 1760
IEC 60584-1
Type S
-40 , 1760
S
IEC 60584-1
Type T
T
IEC 60584-1
-200 , 400
Type U
-200 , 600
U
DIN 43710
-200 , 840
Pt-100
Pt
IEC 60751
LINEAR INPUTS
Type
Current
0a20
Current
4a20
Voltage
0v50
Voltage
00v1
Voltage
02v1

AUTO-TUNE

Auto-tuning matches the characteristics of the controller to the
process being controlled in order to obtain good control. Tuning
involves calculating and setting the values of the PID parameters.
The Auto-tuner works by switching the output on and off to induce an
oscillation in the process value. From the amplitude and period of
oscillations PID parameters are calculated.
Auto-tune can be performed at any time, but normally it is performed
only once during the initial commissioning of the process. However,
if the process under control subsequently becomes unstable
(because its characteristics have changed), you can re-tune again
for the new conditions.
In order to start Auto-tune process:
1- Set the CNTL parameter in OCNF page as PID.
2- Set the control set point to the value at which you will normally
operate the process. Consider also the process value may exceed
the control set point while in Auto-tuning.
3- Set the HYS parameter in TUNE page as 0. 1 (if DP=1) or 1 (if DP=0).
4- Set the AT parameter in TUNE page as ON to commence
Auto-tuning process. Press  button to revert the normal operation.
The lower display and SF led will flash to indicate that tuning is in
progress.
After a few cycles of oscillation the tuning is completed and the
calculated PID parameters PB, IT and DT are stored.
While the Auto-tuning in progress if AT parameter is set the OFF or
operating power of the controller is interrupted Auto-tune progress is
stopped and old PID values are retained.
Alarm State
1
Low
Alarm
(Absolute)
0
0
Alarm State
1
High
Alarm
(Absolute)
0
0
Low
Deviation
(Relative)
SP
PV
High
Deviation
(Relative)
SP
PV
Band
Alarm
(In)
SP
PV
Band
Alarm
(Out)
SP
PV
When alarm state is
"1" the output (relay)
is active.
Remedy
o
( F)
,
140
3308
,
-328
1544
,
-328
1562
,
-328
2480
,
-328
1652
-328
,
2372
, 3200
104
,
104
3200
-328
,
752
,
-328
1112
,
-328
1544
Range
0-20 mA DC
4-20 mA DC
0-50 mV DC
0-1 V DC
0.2-1 V DC

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the E-48 and is the answer not in the manual?

Questions and answers

Summary of Contents for Elimko E-48

  • Page 1 Deviation drift with time and environment conditions. Indicating method is 2x4 digit LED (Relative) display. E-48 indicating range is from -1999 to 9999 and is able to connect SP+ASP SP+ASP mV, mA, thermocouple, resistance thermometer and other sensors and...
  • Page 2  and  buttons are used to select the configuration pages (3) The value of AR parameter defines the auto return time to normal Manufacturer / Technical Support: Elimko Co. Ltd. while PAGE message is displayed in the upper display.

Table of Contents