Page 2
SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during installation and maintenance of the MBP and UPS. The Hotswap MBP models that are covered in this manual are intended for installation in an environment within 0 to 40°C, free of conductive contaminant. This equipment has been tested and found to comply with Class A UPS,pursuant to Part 15 of the FCC Rules.
Page 3
The admissible storage temperature range is -15ºC to +60ºC. Special precautions p The Hotswap MBP is designed to work with approved EATON UPS (contact your Eaton reseller for more information) p All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
Before installing your HotSwap MBP with your UPS, please read first the safety instructions. Then follow the indications in this manual, which completes the UPS Installation and User Manual. To discover the entire range of EATON products, we invite you to visit our web site at www.eaton.com/ powerquality or contact your EATON representative.
2. Presentation The Eaton® HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads (HotSwap function). You can safely eliminate the effects of UPS maintenance and guard the integrity of your equipment.
Page 7
2. Presentation MBP11K208 Tower installation Rack installation Wall mounting Description Weight Dimensions (inch/mm) (lb/kg) D x W x H MBP6K208 5.5 / 2.5 4.3 x 7.0 x 5.1 / 110 x 177 x 130 MBP11K208 13.7 / 6.2 8.7 x 13.2 x 5.1 / 220 x 336 x 130...
MBP status, and the indication on UPS display panel of both following status: p MBP connection to UPS p Bypass switch position Check the UPS user manual to check the compatibility of this feature, or contact Eaton reseller for more information MBP6K208...
3. Connect the MBP detection cable from the I/O cord Set (1) to the specific UPS connector (MBP detect, refer to UPS User Manual). Only with compatible EATON UPS, contact your Eaton reseller for more information. 4. Slide the MBP I/O cover (2) after removing the 4 screws, to access to MBP terminal blocks.
13. Connect the MBP detection cable (6) to the specific UPS connector (MBP detect, refer to the UPS User Manual). Only with compatible EATON UPS, contact your Eaton reseller for more information. 14. Put back and secure the I/O terminal blocks cover of the UPS - refer to the UPS user manual.
Page 13
4. Power cables connection 16. Punch the knockouts of MBP I/O cover (1) and insert cable glands of UPS (or conduit fittings) inside. 17. Insert the Normal AC source cable through the cable gland (or a conduit through the conduit fitting). 18.
5. Operations 5.1 UPS start-up with HotSwap MBP Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm. 1. Check that the UPS is correctly connected to the HotSwap MBP (see previous chapter 4) If the UPS if equipped with outlets, those outlets can no longer be used (loads can only be connected to the MBP outlets or the MBP Output terminal blocks).
5. Operations 5.2 UPS replacement with HotSwap MBP UPS Removing (please follow the MANDATORY step below): MBP6K208: 1. Put the UPS in “internal Bypass mode” (refer to the UPS user manual) 2. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user manual) BYPASS 3.
Page 16
5. Operations MBP11K208: 1. Put the UPS in “internal Bypass mode” (refer to the UPS user manual) BYPASS 2. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user manual) 3. Set the MBP manual Bypass switch to "Bypass" position. The "Bypass mode" red light of the MBP goes On, indicating that the load is supplied directly by AC source 4.
Connect the I/O cord Set (1) connector to the MBP , and secure it by fixing the 2 locking screws MBP11K208: p First check that the Normal AC source switch (3) of the MBP is still locked to the "0" position...
6. Specifications MBP6K208 MBP11K208 Input Terminal blocks Output 2 L6-30R + Terminal blocks 3 L6-30R + Terminal blocks Overall dimensions D x W x H (inch / mm) 5.6 x 7.0 x 5.1 / 10.2 x 13.2 x 5.1 /...