Three Phase (3W/4W) Three Phase Touch Screen Digital Multi-function Meter Installation & Operating Instructions Section Contents Introduction Measurement Reading Screens Programming 3.1 Password Protection 3.1.1 Change Password 3.2 Menu selection 3.2.1 System Parameter selection screen 3.2.1.1 System type 3.2.1.2 Potential transformer Primary value 3.2.1.3 Potential transformer secondary value 3.2.1.4 Current transformer Primary value 3.2.1.5 Current transformer Secondary value...
Page 4
3.2.4.1.2.4 Hysteresis selection 3.2.4.1.2.5 Energizing delay time 3.2.4.1.2.6 De-energizing delay time 3.2.4.2 Relay 2 output selection menu 3.2.4.3 Parameter setting for Analog Output-1 3.2.4.4 Parameter setting for Analog Output-2 3.2.5 Brightness & Contrast Touch screen calibration. Phase Rotation Error screen. Run - Hour.
1. Introduction This instrument is a panel mounted 96 x 96mm DIN Quadratic Digital metering system for the measurement of important electrical parameters like AC voltage, AC Current, Frequency, Power, Energy(Active / Reactive / Apparent) . The instrument integrates accurate measurement of technology (All Voltage &...
Page 6
TABLE 1: Units of Measured Parameters Measurement Volts System Voltage Amps System Current Volts Voltage VL1-N(4wire only) Volts Voltage VL2-N(4wire only) Volts Voltage VL3-N(4wire only) Volts Voltage VL1-L2 Volts Voltage VL2-L3 Volts Voltage VL3-L1 Amps Current L1 Amps Current L2 Amps Current L3 Neutral Current ( 4 wire only )
Units of Measured Parameters Measurement Current Demand Amps KVA Demand KW Import Demand KW Export Demand Amps Max Current Demand Max kVA Demand Max KW Import Demand Max KW Export Demand Hours Run Hour On Hour Hours Counts Number of Interruptions Phase Reversal Indication ( 4 wire only ) V1 THD* V2 THD*...
Measurement Reading Screens In normal operation the user is presented with one of the measurement reading screens out of several screens. These screens from particular submenu may be scrolled through one at a time in incremental order by touching the “ key”...
Page 9
Screen 7 : Screen 8 : Screen 9 : System Frequency System Power Factor System Interruptions SYSTEM INTERRUPTIONS SYSTEM FREQUENCY SYSTEM POWER FACTOR LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE 0.000 0.000 0.000...
Page 10
Screen 15 : Line Voltage THD Screen 14 : Screen 15 : Phase Voltage THD Line-Line Voltage (In case of 4 wire) (In case of 3 wire) PHASE VOLTAGE % THD LINE-LINE VOLTAGE LINE VOLTAGE THD LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE 0.000 415.1...
Page 11
Screen 22 : L2 Phase Power Screen 23 : L3 Phase Power Screen 24 : Phase Angle Reactive/Apparent/Active Reactive/Apparent/Active (Phase L1/L2/L3) (for 4W only) (For 4 wire only) (For 4 wire only) L2 PHASE POWER L3 PHASE POWER PHASE ANGLE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE...
Page 12
Screen 31 : Pictorial representation Screen 32 : Pictorial representation SUBMENU 5 : ENERGY L2 Phase Waveform (For 4 wire only) L3 Phase Waveform (For 4 wire only) Screen 33 : Active Energy Import (only accessed through power submenu list) (only accessed through power submenu list) L3 PHASE WAVEFORM ACTIVE ENERGY IMPORT LINE-NEUTRAL VOLTAGE...
Page 13
Parameter Screens MAIN MENU RESET CHANGE COMMUNICATION POWER ENERGY SYSTEM VOLTAGE CURRENT OPTIONS PASSWORD PARAMETERS (Sec 3.1) (Sec 3.2.4) L1 PHASE SYSTEM Line to Neutral * ACTIVE ENERGY SYSTEM TYPE Line Current POWER * IMPORT (Sec 3.2.1.1) PARAMETERS VOLTAGE L2 PHASE ACTIVE ENERGY Max.
3. Programming The following sections comprise step by step procedures for configuring the instrument for individual user requirements. To access the set-up screens touch on the “ SETUP ” icon in Main Menu. This will take the User into the Password Protection Entry Stage(Section 3.1). 3.1.
Page 16
After entering the complete password user needs to confirm password SETUP by touching “ key”. 1234 ENTER ENTER BACK Password confirmed. SETUP If Entered password is correct then “Password Accepted” is displayed PASSWORD ACCEPTED on screen & user will enter into setup menu. ENTER BACK Password Incorrect.
3.1.1 Change Password Change Password Option is the second last option in list of “SETUP” submenu, so can be accessed by a simple touch anywhere in “ Change PASSWORD ENTER CURRENT PASSWORD Password” row. In this screen user first needs to enter the current password. ENTER BACK After input of correct password, “PASSWORD ACCEPTED”...
3.2.3 RESET PARAMETERS 3.2.4 OUTPUT OPTIONS 3.2.5 BRIGHTNESS & CONTRAST Touching on SYSTEM PARAMETER will open the system parameters list screen.Then these screens from particular parameter may be scrolled through one at a time in incremental order by touching the “ key”...
3.2.1.2 Potential Transformer Primary Value The nominal full scale voltage will be displayed as Line to Line Voltages for all system types. This screen can be accessed only from system parameters list menu. Here again 0 to 9 digit input keypad is provided to set value of PT LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE...
Valid range of PT secondary setting value is from 241.0 to 480.0. for 415 VL-L. Please refer the table bellow for different ranges. LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE PT SECONDARY INVALID VALUE If value outside the range is entered, It will display “INVALID VALUE” followed by correct range of parameter.
Valid range of CT primary setting value is from 1 to 9999. If value outside the range is entered, It will display “INVALID VALUE” LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE CT PRIMARY followed by correct range of parameter. INVALID VALUE ENTER BACK 3.2.1.5 Current Transformer Secondary Value...
3.2.1.7 Auto Scrolling This screen allows user to enable screen scrolling. Seven options : ALL, SYSTEM, VOLTAGE, CURRENT AUTO - SCROLL LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE CT SECONDARY POWER, ENERGY & NONE are displayed on screen. Touching radio 1 AMPERE 0.000 0.000...
3.2.1.9 ENERGY ON RS485. This screen enable user to set energy in terms of Wh / kWh / MWh on Rs485 Output depending as per the user’s requirement .This setting is applicable for all types of energy. Three options: WATT, KILO-WATT & MEGA-WATT are displayed on screen.
3.2.2 Communication Parameter Selection : After entering in the “COMMUNICATION PARAMETERS” list of following parameters will be displayed 3.2.2.1 RS485 ADDRESS 3.2.2.2 Rs485 BAUD RATE 3.2.2.3 Rs485 PARITY 3.2.2.1 Rs485 Address Setting This screen applies to the RS 485 output only. This screen allows the user to set RS485 address parameter for the instrument.
3.2.2.3 RS 485 Parity & Stop bit Selection This screen allows the user to set Parity & number of stop bits. Four options: ODD PARITY WITH ONE STOP BIT, NO PARITY LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE RS485 PARITY &...
Touching on any parameter will display the confirmation dialog, now a touch on “ key” will confirm the resetting of that particular LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE RESET PARAMETERS RESET ALL Parameter. 0.000 0.000 0.000 RESET ALL ENERGIES RESET DEMAND PARAMETERS ARE YOU SURE YOU WANT TO RESET ALL Touching on “...
3.2.4.1.1.1 Assignment of Energy to pulse output (Relay 1) : This screen allows the user to assign energy to pulse output (for Relay 1) Following six options are displayed:- Apparent Energy Import Energy ( Active ) RELAY-1 ENERGY ASSIGNMENT LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE...
3.2.4.1.2 Limit output This screen is for Limit output mode selection. It allows the user to set Limit output corresponding measured value. After entering in Limit Output first time(was disabled previously), only “PARAMETER:” is displayed on screen. Now a simple touch on “PARAMETER:” will open list of parameters, Refer Table 2 “Parameter for Analog &...
3.2.4.1.2.3 Trip point selection This screen applies to the Trip point selection. This screen allows the user to set Trip point for instrument in %. This screen can be accessed only from Limit Output settings list menu. LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE RELAY-1 TRIP POINT ENTER TRIP POINT IN %...
The allowable range is 0.5% to 50 % of Trip point . If value outside this range is entered, it will display “INVALID VALUE” LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE RELAY-1 HYSTERESIS INVALID VALUE followed by correct range of parameter. ENTER BACK 3.2.4.1.2.5 Energizing Delay time.
3.2.4.1.2.6 De-Energizing Delay time This screen allows the user to set De-Energizing Delay time for Relay 1 Limit Assigned Parameters . This screen can be accessed only from Limit Output settings list menu. RELAY-1 DE-ENERGIZING DELAY LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE Here a 0 to 9 digit input keypad is provided to set value of Delay, &...
3.2.4.4 Parameter setting for Analog Output 2 ( Optional ) This option allows the user to set analog output 2 to corresponding measured parameter. A simple touch on “ANALOG-2”row will open screen having list of parameters.( Refer table2 “ Parameter for Analog & Limit output ”) Touch on “...
Page 33
LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE CT SECONDARY LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE CT SECONDARY CT SECONDARY LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE...
5. Phase Rotation Error screen PHASE SEQUENCE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE Meter shows phase rotation error if the phase sequence 0.000 0.000 0.000 ERROR R-Y-B (L1-L2-L3) is not maintained This screen indicates that 0.000 0.000 0.000 NOTE : WRONG PHASE SEQUENCE. Phase sequence is incorrect.
. On Hour This Screen shows the total no. of hours the Axillary Supply is ON. Even if the Auxiliary supply is interrupted count of On hour will be SYSTEM ON HOUR LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE LINE-NEUTRAL VOLTAGE maintained in internal memory & displayed in the format “hours. min”. 0.000 0.000 0.000...
Page 36
These outputs can be individually assigned to represent any one of the measured and displayed Parameters. All settlings are user configurable via the user interface screen. See Analog o/p selection ( section 3.2.4.3 & section 3.2.4.4 ) for details . * Note : Refer diagrams 1 &...
Page 37
Diagram 2 : ( 0 - 1 mA ) 0 (0.5 mA) 270 (0.25 mA) 90 (0.75 mA) 181 (0 mA) 180 (1 mA) TABLE 2 : Parameter for Analog & Limit output Range Parameter Parameter 3P 4W 3P 3W Analog Output Limit Output ü...
Page 38
Range Parameter Parameter 3P 4W 3P 3W Analog Output Limit Output ű ü 0 - 120 % 10 - 120 % ACTIVE POWER L2 ű ü ACTIVE POWER L3 10 - 120 % 0 - 120 % ű ü 0 - 120 % APPARENT POWER L1 10 - 120 % ű...
Range Parameter Parameter 3P 4W 3P 3W Analog Output Limit Output ü ü VA DEMAND 0 - 120 % 10 - 120 % ü ü VA MAX DEMAND 0 - 120 % 10 - 120 % ü ü CURRENT DEMAND 0 - 100 % 10 - 120 % ü...
Page 40
TABLE 3 : Energy Pulse Rate Divisor 1.For Energy Output in Wh 2. For Energy Output in Kwh Pulse rate Pulse rate Divisor Pulse System Power* Divisor Pulse System Power* 1per Wh Up to 3600W 1 per kWh Up to 3600W 1per kWh Up to 3600kW Up to 3600kW...
Divisors 100 CT secondary = 1A Max pulse rate 3600 pulses per 100Ah ** CT secondary = 5A Max pulse rate 720 pulses per 100Ah ** Divisors 1000 CT secondary = 1A Max pulse rate 3600 pulses per 1000Ah ** CT secondary = 5A Max pulse rate 720 pulses per 1000Ah ** Pulse duration 60 ms, 100 ms or 200 ms **No.
Page 42
Trip point: Trip point can be set in the range of 10% to 120 % of nominal value for Hi-Alarm & 10% to 100 % of nominal value for Lo-Alarm. Hysteresis: Hysteresis can be set in the range of 0.5% to 50 % of set trip point . If Hi-alarm Energized or Hi-alarm De-energized is selected then relay will get De-energized or Energized respectively, if set parameter value is less than Hysteresis Similarly if Lo-alarm Energized or Lo-alarm De-Energized.
11. RS 485 ( ModBus ) Output : This instrument supports MODBUS (RS485) RTU protocol( 2-wire ) . Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents, an Earth connection should be made at one point on the network.Loop (ring) topology does not require any termination load.
Page 44
The each byte in RTU mode has following format: 8-bit binary, hexadecimal 0-9, A-F 2 hexadecimal characters contained in each 8-bit field of the message 4 bytes (32 bits) per parameter. Format of Data Bytes Floating point format ( to IEEE 754) Most significant byte first (Alternative least significant byte first) 2 byte Cyclical Redundancy Check (CRC) Error Checking Bytes...
This function code is not supported by the instrument. Illegal function Attempt to access an invalid address or an attempt to read Illegal Data or write part of a floating point value Address Illegal Data Attempt to set a floating point variable to an invalid value Value Accessing 3 X register for reading measured values: Two consecutive 16 bit registers represent one parameter.
Page 46
Number of register Hi : Most significant 8 bits of Number of registers requested. Number of register Lo : Least significant 8 bits of Number of registers requested. (Note : Two consecutive 16 bit register represent one parameter.) Response: Volt3 (219.25V) 01 (Hex) 04 (Hex) 04 (Hex) 43 (Hex) 5B (Hex)
Page 47
Parameter Parameter Address Parameter Parameter Modbus Start Address Hex Modbus Start Address Hex 3P 4W 3P 3W 3P 4W 3P 3W High Byte High Byte High Byte (Register) Low Byte 30015 ű ü ű 30017 ü ű ü 30019 ű ü...
Page 48
Parameter Parameter Address Parameter Parameter Modbus Start Address Hex Modbus Start Address Hex 3P 4W 3P 3W 3P 4W 3P 3W High Byte High Byte High Byte (Register) Low Byte 30065 PF Sum ű ü 30067 Phase Angle Ave ü ü...
Page 50
Query : 01 (Hex) Device Address 03 (Hex) Function Code Start Address High 00 (Hex) 0A (Hex) Start Address Low Number of Registers Hi 00 (Hex) Number of Registers Lo 02 (Hex) E4 (Hex) CRC Low CRC High 09 (Hex) Start Address High : Most significant 8 bits of starting address of the parameter requested.
Page 51
Data Register2 High Byte 00 (Hex) Data Register2 Low Byte 00(Hex) EE (Hex) CRC Low CRC High 27 (Hex) Byte Count : Total number of data bytes received. Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested. Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Page 52
Byte Count 04 (Hex) Data Register-1High Byte 40 (Hex) Data Register-1 Low Byte 00(Hex) Data Register-2 High Byte 00(Hex) Data Register-2 Low Byte 00(Hex) 66 (Hex) CRC Low CRC High 10 (Hex) Byte Count : Total number of data bytes received. Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Page 53
Start Address High : Most significant 8 bits of starting address of the parameter requested. Start Address low :Least significant 8 bits of starting address of the parameter requested. Number of register Hi : Most significant 8 bits of Number of registers requested. Number of register Lo : Least significant 8 bits of Number of registers requested.
Page 54
Parameter Modbus Start Address Hex Address Parameter Read / Write (Register) High Byte High Byte High Byte Low Byte 40037 System Power R/Wp 40039 Energy digit reset count 40041 Register Order/Word Order R/Wp CT Secondary 40043 R/Wp 40045 R/Wp PT Secondary 40047 Relay1 output select R/Wp...
Page 55
Explanation for 4 X register : Address Parameter Description 40001 Demand Reset Demand Reset is used to reset the Demand parameter. A value of zero must be Written to this register to reset the Demand period. Writing any other value will return an error. 40003 Demand Period Demand period represents demand time in minutes.
Page 56
Address Parameter Description 40017 Run/On Hour & This address is used to reset the Run/On hour & number Interruption of Interruption . Write zero value to this register to reset reset the Run/On hour & number of Interruption. Writing any other value will return an error. 40019 Rs485 Set-up This address is used to set the baud rate, Parity, Number of...
Page 57
Address Parameter Description 40031 Analog Out 2- This address is used to set the parameter for Analog Output 2.. Para Set Write one of the parameter no. As per the options given in Table 2 for Analog & Limit Output Parameters. Writing any other value will return an error.
Page 58
Address Parameter Description This address is used to read and write the CT secondary value CT secondary 40043 write one of the following values to this address. 1=1A CT secondary 5=5A CT secondary writing any other value will return an error. PT secondary This address is used to read and write the PT secondary value.
Page 59
Address Parameter Description 40059 Relay 2 This address is used to select the Relay 2 operation as output select pulse or Limit. write one of the following values to this address. 0 = Pulse output on Relay 2 128 (decimal) = Limit output on Relay 2 writing any other value will return an error.
Page 60
Address Parameter Description 3) If password lock is present & to disable this lock first send valid password to this location then write “0000” to this location 4) If password lock is present & to modify 4X parameter first send valid password to this location so that 4X parameter will be accessible for modification.
Page 61
Decimal value Parity Baud Rate Stop Bit 19200 9600 NONE 9600 NONE EVEN 9600 9600 4800 NONE 4800 NONE 4800 EVEN 4800 2400 NONE 2400 NONE 2400 EVEN 2400 NOTE : Codes not listed in the table above may give rise to unpredictable results including loss of communication.
Page 64
Address Parameter Modbus Start Address (Hex) Mapping Register High Byte Low Byte (Register) Number. 40521 Mapped Add for register #0x0210 40522 Mapped Add for register #0x0212 40523 Mapped Add for register #0x0214 40524 Mapped Add for register #0x0216 40525 Mapped Add for register #0x0218 40526 Mapped Add for register #0x021A Mapped Add for register #0x021C...
Page 65
Byte Count 04 (Hex) Voltage 2 * Data Register-1High Byte 00 (Hex) (3X Address 0x0002) Data Register-1 Low Byte 02 (Hex) Power Factor 1 * Data Register-2 High Byte 00 (Hex) (3X Address 0x001E) Data Register-2 Low Byte 1E (Hex) CB (Hex) CRC lOW CRC High...
Page 66
Query: 01 (Hex) Device Address 04 (Hex) Function Code Start Address High 02 (Hex) 00 (Hex) Start Address Low Number of Registers Hi 00 (Hex) Number of Registers Lo 04 (Hex) ** F0 (Hex) CRC Low CRC High 71 (Hex) Start Address High : Most significant 8 bits of starting address of User assignable register.
Page 67
Data Register-3 High Byte 3F (Hex) Data Register-3 Low Byte 80 (Hex) Power Factor 1Data Data Register-4 High Byte 00 (Hex) Data Register-4 Low Byte 00 (Hex) 79 (Hex) CRC Low CRC High 3F (Hex) User Assignable mapping Registers User Assignable Data Registers (Starting (Starting ( 4X Registers Table10 )
To get the data through User assignable Register use following steps: 1) Assign starting addresses(Table3) of parameters of interest to a “User assignable mapping registers” in a sequence in which they are to be accessed (see section “Assigning parameter to user assignable registers”) 2) Once the parameters are mapped data can be acquired by using “User assignable data register “...
Sign of Sign of Sign of Inductive / Connections Quadrant Active Reactive Power Capacitive Power ( P ) Power ( Q ) Factor ( PF ) Import Import Export Export Inductive means Current lags Voltage Capacitive means Current leads Voltage When the instrument displays Active power ( P )with “...
As the front of the enclosure conforms to IP54 it is protected from water spray from all directions, additional protection to the panel may be obtained by the use of an optional panel gasket. The terminals at the rear of the product should be protected from liquids. The instrument should be mounted in a reasonably stable ambient temperature and where the operating temperature is within the range -10 to 55 C .
3. To protect the product against permanent damage, surge transients must be limited to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source. The unit has been designed to automatically recover in the event of a high level of transients.
13.4 Auxiliary Supply instrument should ideally be powered from a dedicated supply, however it may be powered from the signal source, provided the source remains within the limits of the chosen auxiliary voltage. 13.5 Fusing It is recommended that all voltage lines are fitted with 1 amp HRC fuses. 13.6 Earth/Ground Connections For safety reasons, CT secondary connections should be grounded in accordance with local regulations.
Page 73
Inputs Nominal input voltage (AC RMS) Phase-Neutral 230 V (Three wire and Four wire) Line-Line 400 V Max continuous input voltage 120% of Rated Value Max short duration input voltage 2 x Rated Value (1s application repeated 10 times at 10s intervals) Nominal input voltage burden 0.2VA approx.
Page 74
Operating Measuring Ranges Voltage 5 .. 120 % of Rated Value Current 5 .. 120 % of Rated Value Frequency 40 .. 70 Hz 0.5 Lag ... 1 ... 0.8 Lead Power Factor Accuracy Voltage ± 0.5 % of range ±...
10... 100% of Nominal Value. Current Range 20... 100% of Nominal Value for THD. cosØ / sinØ = 1 Power For Active / Reactive Power & Energy 10... 100% of Nominal Current & 50... 100% of Nominal Voltage. Power Factor / Phase Angle 40...
Page 76
Standards EMC Immunity IEC 61326 10V/m min-Level 3 industrial low level electromagnetic radiation environment IEC 61000-4-3. IEC 61010-1 , Year 2001 Safety IP for water & dust IEC 60529 Isolation Dielectric voltage withstand 2.2 kV RMS 50 Hz for 1 minute test between circuits and between all electrical circuits accessible surfaces...
Page 77
Pulse output Option ( 1 or 2 Relay ) : Relay 1NO + 1NC Switching Voltage & Current Switching Voltage & Current 240VDC , 5Amp. Default Pulse rate Divisor 1 per Wh (up to 3600W), 1 per kWh (up to 3600kW), 1 per MWh (above 3600 kW) Programmable on site Pulse rate Divisors...
16. Connection for Optional Pulse Output / RS 485 / Analog Output ( rear view of the instrument ) : 1. One Pulse Output (One Limit Output) N/O N/C COM Relay 1 2. Two Pulse Output ( Two Limit Output) N/O N/C COM N/O N/C COM Relay 2...
Page 79
4. Two Analog Output A1 A2 Gnd 4 -20 mA 5. One Pulse (One Limit) + RS 485 Output N/O N/C COM RS 485 Relay 2 6. One Pulse (One Limit) + Two Analog Output N/O N/C COM A1 A2 Gnd Relay 2 0 - 1mA...
Page 80
7. RS 485 + Two Analog Output A1 A2 Gnd RS 485 4 -20 mA 8. RS 485 Output + One Pulse (One Limit) + Two Analog Output N/O N/C COM A1 A2 Gnd RS 485 Relay 2 0 - 1mA 9.
Page 81
The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the correct method of installation for this product. It is the user's responsibility to determine the suitability of the installation method in the user’s field conditions.
Need help?
Do you have a question about the ND22 and is the answer not in the manual?
Questions and answers