Page 4
Selecting the default setting 9.3.2 Automatic arming / disarming 9.3.3 Custom point type duress alarm 9.3.4 Areas with blocking time 9.3.5 Access Levels 9.3.6 Tamper surveillance Alarm reporting History log 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Security advisories, that is a list of identified vulnerabilities and proposed solutions: https://www.boschsecurity.com/xc/en/support/product-security/security- advisories.html Bosch assumes no liability whatsoever for any damage caused by operating its products with outdated software components. Decommissioning When the system is at the end of service life, remove the connected products from the system and disassemble the system.
– Only authorized service personnel is allowed to install this MAP5000 system. – Use only the installation material recommended by BOSCH Security Systems to ensure error-free operation. – Follow anti-static procedures when handling system components. Ensure that you are properly grounded to discharge any static charge before you work with system components.
When determining the number of power supplies, it is also necessary to take into account the inrush current of loads (refer to Planning the system with power supply, page 8). This assembly is only required if the IPP-MAP0005-2 MAP power supply 150W is installed. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
A power supply segment is a power supply with all loads supplied by the power supply. Power supply segment 4-wire cables are used for load connection within the power supply segment. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Page 10
Short-time current limitation to 3.2 A per output A / B Current limitation to 1.6 A between internal and external BDB Remote operation with ICP-MAP0120 MAP expansion enclosure Figure 2.4: 2 LSN modules with up to 4 touch keypads 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Page 11
- - - 1.0 mm 0.785 mm 50 m 125 m 125 m - - - 1.0 mm 0.785 mm 50 m 50 m 50 m 50 m Table 2.1: Cable lengths Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Splitting the external BDB with a BDB/CAN splitter, page 53 System overview This chapter shows an overview of the system as it is installed in the ICP-MAP0111 MAP panel enclosure. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 17
Mounting location for ICP-MAP0065 MAP terminal block Grounding studs Flange for IPP-MAP0005-2 MAP power supply 150W Shielding connection points Knockout for AC wires (use when AC wires come in from the back of the enclosure) Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Unhinge and remove the enclosure door and set it aside. Remove the enclosure knockouts in the order shown in the figure below. Enclosure knockouts on ICP-MAP0111 MAP panel enclosure or ICP-MAP0120 MAP expansion enclosure Callout Description 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Mount the tamper switch rail to the inner right side of the enclosure as shown in the figure below. Secure the tamper switch rail with the two supplied screws. Do not mount the tamper switch at this time. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 20
ICP-MAP0050 MAP panel/power enclosure tamper switch Use the same way as shown above to mount the tamper switch rail for ICP-MAP0055 MAP expansion enclosure tamper switch in the ICP-MAP0120 MAP expansion enclosure. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
If a wall tamper is required, insert the plug for the tamper switch into the back of the enclosure (required in accordance with VdS and EN50131 grade 3) as shown in the figure. Secure the plug to the wall using a suitable screw (not supplied). Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 22
Mount the enclosure to the intended surface using suitable screws and anchors (not supplied). Use the mounting holes as shown in the figure. Ensure that all screws are tight and that the enclosure is securely fastened to the mounting surface. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Connect the ICP-MAP0115 MAP power enclosure to the ICP-MAP0111 MAP panel enclosure to provide additional power when high power capacity is required. ICP-MAP0115 MAP power enclosure with thermistor Callout Description Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Damage to the power supply due to debris during the installation is possible. Notice! To prevent damage to the power supply during installation, ensure that the supplied protective dust cover label is on top of the power supply before installing it. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 26
Secure the power supply to the enclosure back wall with the supplied hardware in the following order: external tooth washer, washer, hex nut Refer to Technical Specifications, page 73 for power specifications. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Plug the thermistor cable into the power supply to the terminal marked Mount the thermistor on the inside rear of the enclosure right on the top of the two batteries. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
If the TAE box is not mounted on the wall behind the enclosure, mount the TAE box to the enclosure back wall either horizontally or vertically as desired. Installing the TAE box Callout Description TAE box 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Use the corresponding ratings for the fuses SI 1 ... SI 5. (minimum 250 mA, maximum 1 A depending on the connected loads). The overall current of all SIV outputs must not exceed the available maximum current of the voltage output used. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Notice! To ensure proper system grounding, you must insert the grounding screw through the AT x000 and the accessory mounting plate. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Page 33
The analog AT x000 requires 12 V. Use the ribbon cable connector labeled AT x000 Uext. The analog AT x000 also requires a separate 12 V power source, such as the ICP-MAP0017 MAP 12V-28V power converter. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 34
ICP-MAP0007-2 MAP DE interface module Notice! The two trouble inputs are automatically configured to "Communicator Trouble" and "Negative Acknowledgment" when "Communicator" is selected in the Remote Programming Software for MAP (RPS for MAP). 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Mounting the modules onto the hinged mounting plate Hinged mounting plate overview The following graphic shows an overview of the hinged mounting plate and the designated mounting locations of the modules. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Page 37
Sliding the module onto the hinged mounting plate Slide the module onto the hinged mounting plate. Ensure that the locking clips snap into a pair of rectangular openings on the bottom rail. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 38
| Installation Modular Alarm Platform 5000 Connecting the grounding cable to the hinged mounting plate Connect the grounding cable from the enclosure back wall to the hinged mounting plate. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Attach the carrier plate of the ICP-COM-IF2 relay module in the holes provided in the hinged mounting plate or the mounting rails. Use the screw provided to secure the carrier plate to the bottom rail. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
R = red), in addition to existing wires where appropriate. Mount the small snap ferrite sleeve (contained in the accessory pack of the MAP5000 panel) on the black-red cable of the wireless modem close to the wireless modem. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Page 41
– Alarm – Non-cycling sleep – Cyclic sleep with no temporary wake-up event1 in progress 600 ms on, 600 ms off Limited network service due to one of the following: Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Max power: 10 W Radiator length: 100 mm Foot: 34 mm Magnetic antenna mast incl. bottom with 2.6 m cable. The FME female connector is preconfigured on the coaxial cable. Rod antenna 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Page 43
Area of use: inside, outside Rod antenna incl. 20 m cable. The mounting bracket is designed for mounting on vertical surfaces, the FME female connector is preconfigured 1) not for VdS Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Using a wrong cable type can lead to malfunction of the system. Notice! Use shielded cables only. Connecting the Bosch Data Bus To assist with cable connections, the terminal blocks on each system module are color- coded. Terminal block color codes...
Page 45
The order of system modules on the BDB shown in the figure is not mandatory. A symmetrical load distribution to the power supply outputs A and B must be ensured as far as possible. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Bosch Data Bus cable routing 4.1.1 Internal / external Bosch Data Bus The MAP5000 system contains two Bosch Data Buses (BDB), which are used to connect the system modules to the MAP5000 panel. Internal BDB The maximum length of the internal BDB is 3 m.
The following applies for VdS: Touch keypads for different areas must not be connected on the same BDB. 4.1.2 Topology of the external Bosch Data Bus Mount the external BDB as shown below. Notice! Any other bus topology does not conform to the specifications of the BDB.
Input for tamper switch, is activated by configuration for remote operation of the power supply on the external BDB. Output for voltage supply (switched), supervised, nominal voltage 24 VDC Bosch Data Bus - connection A Bosch Data Bus - connection B Output for AC fail and summary power supply trouble (optional) AC connection 4.2.2...
External BDB connector (1) Use this connection to connect additional system modules to the external BDB (refer to Connecting the Bosch Data Bus, page 44 and Modules on the BDB, page 46). Programmable output (2) Use these connections to control devices in certain system states (refer to Programmable output signals, page 66).
Looping the shield wire through the LSN elements Other connections of the additional shielding wire at other locations are not permitted. With loop wiring, the additional shielding wire must be connected at both loop ends. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
500 m cable length as well as a higher reliability can be achieved. For information on installing a BDB/CAN splitter, refer to the correspondent installation manual and datasheet. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Only assign one area (where applicable with overlapping dependent partition areas) to a touch keypad. Exception: Mutually independent areas may be assigned to the touch keypad of the MAP5000 panel area. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Secure the cover using one screw M3 x 20 mm (F.01U.172.636). The fed-in cable must be provided with strain relief. The adhesive seal must be attached after completion of all work. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Insert the lockset into the opening on the enclosure door. Secure the lockset with the nut. Once the enclosure lockset is installed, connect the long grounding cable to the enclosure door. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Make sure that the AC wires are connected to the MAP terminal block. Connect the battery wire leads to the batteries. Do not connect the batteries to the power supply at this time. Switch the AC breaker on. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
For operation of the management system, restrict the data transfer from MAP5000 to the management system. Ensure that this does not have any influence on the panel. VdS and EN50131 programming instruction Settings in RPS for MAP: Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 62
In the MAP5000 panel menu, select -> setup: Management system as a Monitoring Station. Notice! Data transfer between the MAP5000 and the connected PC system must always take place via a secure, authenticated and encrypted connection. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Connecting the batteries Danger! Battery Injuries due to electric shock, fire or explosion are possible if the battery is handled or connected incorrectly. Notice! Use only VdS-approved maintenance-free batteries for VdS applications. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Properties field on the parameter Default Property Values Set and select the standard that you want to program. Right-click on any parameter on the left side of the Properties window. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Stick the type label supplied in the MAP5000 panel accessory pack on the MAP5000 panel enclosure at a location that is easily visible from outside. Lock the enclosure door after completing all work. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Duress alarm Duress alarm External intrusion alarm Intrusion alarm from unoccupied protection area Internal intrusion alarm Intrusion alarm from disarmed area with – activated internal program – intrusion alarm 24h 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Page 67
Report failure panel alarm MAP5000 panel has received negative acknowledgment from communicator due to report failure panel alarm Internal tamper alarm Tamper alarm from disarmed area Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 68
Reporting of panel summary armed armed Reportable external fire alarm Reporting of duress alarm event, possibly also delayed if present/absent option is used Anti-mask intrusion trouble Covering of a motion detector 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Notice! Have maintenance and inspection work carried out regularly by trained expert personnel. Bosch Sicherheitssysteme GmbH recommends performing a functional and visual inspection at least once annually. Danger! Danger of electric shock if live parts are touched. For your safety, you should switch off the...
Page 72
Programming, the MAP5000 panel firmware and history are deleted and network settings are reset (DHCP, 0.0.0.0) when executing this option. Carry out steps 1 - 6 of the above, then carry out steps 2 - 7. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Dimension in cm (H x W x D) 43.6 x 44.3 x 11.2 Weight in kg 8.31 System parameters Number of addresses 1500 Number of areas Event log capacity 5000 Users Number of users 1000 Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 74
MAP power supplies 150W MAP BDB/CAN splitters Ethernet interface 1, RJ 45 connection, 100Mbps maximum Management system connection Via MAP OPC server from Bosch - in VdS systems, only feedback-free connection as information system via exclusive transmission path Number of inputs...
Page 75
Maximum storage temperature in °C Minimum relative humidity in % Maximum relative humidity in % Protection class IP30 Security level IK06 Environmental class EN50130-5, EN50131-1, VdS 2110, VdS 2252 Usage Indoor Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
AE 3 Access for installers via touch keypad Open MAP panel enclosure. Switch to installer mode (refer to Installer button, page 71). Enter installer passcode. AE 3 Access for installers via RPS for MAP 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Page 77
May turn chime on/off May change schedule May edit blocking time User category permissions May add user May delete user May change user passcode Event category permissions May clear internal alarm Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 78
May view MAP5000 panel version Maintenance category permissions May adjust touch keypad volume/brightness May change output state May set date time May test bell May test motion detectors May walk test automatic points 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Using the wizard, select the type Static or Dynamic, the user and function of the key switch Arm / Disarm Area. Now select the area that is to be armed / disarmed. For exit delay, select No Delay. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Only relevant for option MAP5000 Panel > Armed State At Exit Delay Start Exit Door point that must be mandatorily tripped once upon leaving the area. The option MAP5000 Panel > Unvacated Premises must be activated 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
The touch keypad is located in the secured area. Include a new area if not yet present. Include a touch keypad if not yet present. Include the area in the scope of the touch keypad: Local Area. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Internal warning device when control panel enclosure is opened An internal warning device must be provided that trips a time-limited audible alarm when the control panel enclosure is opened in unarmed state. Assign device siren to free output. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 84
May clear external alarm May clear tamper May clear trouble May clear battery trouble May silence Remote service category permissions May authorize manufacturer user May authorize RPS for MAP user Arm category permissions 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Point type technical, fire for alarm inputs Inputs that are assigned the device Point can be programmed to the point type technical or fire (refer to Point types and point evaluation, page 66). Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Program the duration of the acoustic warning signal before arming in the area: Area Manager > Area > Exit Delay > Normal Delay Time. Deactivate the option Arm Only If Area Is Ready To Arm. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
AE 3 Access for installers via touch keypad or via RPS for MAP – AE 4 Access for manufacturers via RPS for MAP Level 2A is a subset of level 2B. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Page 88
Further subdivisions are possible within the access levels if the owner wishes to grant the users different permissions: User Manager > Permission Sets General permissions Access Level May silence buzzer on touch keypad May change own user passcode 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
Page 89
May disarm area * Can disarm only if in alarm May bypass detectors May bypass detectors in area May unbypass detector May switch internal program on/off Status category permissions May view area status Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
Realize the location supervision by security-relevant persons who guarantee that actions that pose a risk to security are detected at all times at the time of the required location supervision. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...
1 supervision for Ethernet and wireless path. ICP-MAP5000-COM | ICP-MAP5000-COM/3 and ICP-MAP5000-SC | ICP-MAP5000-SC/3 supervise the link to Ethernet and poll the wireless network on checking for connection, signal strength and sign in status. Bosch Sicherheitssysteme GmbH 2025-04 | V28 | F.01U.168.332 Installation manual...
For both history logs there is no duration defined. This means, that events are stored for an unlimited amount of time and are not affected in case of power loss at the MAP5000 panel. 2025-04 | V28 | F.01U.168.332 Bosch Sicherheitssysteme GmbH Installation manual...