Download Print this page
Bosch rexroth XI110204 Installation
Bosch rexroth XI110204 Installation

Bosch rexroth XI110204 Installation

Advertisement

Quick Links

ctrlX I/O
Digital Input Module XI110204
4-channel, DC 24 V, 3 ms Input Filter, 2-wire
DOK-XIO***-XI110204*DI-DA02-EN-P
1
Functional description
The digital input module XI110204 is used to detect binary 24
V control signals in a ctrlX I/O station. The module has four
channels in a 2-wire technique. The signal state is shown at
the channel LED on the removable peripheral connector.
The logic and peripheral voltage supply as well as the
EtherCAT-based module communication are routed through
the module.
Fig. 1: Module XI110204
For an application manual of the ctrlX I/O modules, refer to
the media directory ⮫ www.boschrexroth.com/mediadirectory
and enter the search term ⮫ "R911423458".
Ensure that the current documentation is consulted. For
the current documentations, go to ⮫ www.boschrexroth.com/
mediadirectory and enter the module type as search term.
For the integration into the parent system, the respective
ESI files are available. For the ESI files, go to ⮫ http://
www.boschrexroth.com/electrics, search term "⮫ ESI-Files".
2
Ordering data
Type
Part number
XI110204
R911417202
For more ordering data (accessories), go to the product cat-
alog under ⮫ www.boschrexroth.com/electrics.
3
Technical data
3.1
General technical data
XI110204
Number of inputs
4
Connection type
Push-in
Description
Digital input module, 4-channel,
DC 24 V, 3 ms input filter, 2-
wire
XI110204
Connection tech-
2-wire technique
nique
Specification
EN 61131-2, type 1/3
Input filter
3 ms
Signal voltage "0"
-3 V ... 5 V
Signal voltage "1"
11 V ... 30 V
Input current
Typically 2.4 mA
Reverse polarity pro-
Reverse voltage-protected up to 30 V
tection of the inputs
Max. output current
1 A
per clamping point
U
24 V
OUT
Max. sum current
2 A
U
24 V
OUT
Nominal voltage (U
/
DC 24 V (19.2 V to 30 V, including tol-
L
U
)
erance and residual ripple) PELV/SELV
P
(safety extra-low voltage)
Current consumption
26 mA
U
L
Current consumption
13 mA + load U
U
P
Max. power con-
1.26 W
sumption of the
module
Bit width in the
4 bits
process image
Configuration
No address or configuration setting
required
Dimensions
12 mm × 105 mm × 99 mm (width ×
height × depth)
Weight
90 g (module including connector)
Electrical isolation
DC 1200 V U
FE, tested for 60 s each
(not evaluated by UL)
EMC resistance
Acc. to EN 61000-6-2 and EN 61000-6-4
Mounting position
Vertical, on a horizontal mounting rail
Labeling, approvals
CE, UKCA, UL
3.2
Internal schematic diagram
System bus
µC
U
L
U
P
Fig. 2: Internal schematic diagram
3.3
Ambient conditions
Ambient temperature
≤ 2,000 m
2,000 m to 3,000 m
3,000 m to 4,000 m
4,000 m to 5,000 m
Maximum operating altitude
Acc. to DIN 60204
Ambient temperature
(storage and transport)
R911421693
Edition 02
O
to U
, DC 707 V U
/U
P
L
P
DI_1
.
.
.
.
Type 1/3
DI_4
Fuse
1
U
24 V
2
OUT
3
4
 
-25 to +55 °C
-25 to +50 °C
-25 to +45 °C
-25 to +40 °C
5,000 m
-40 to +70 °C
R911421693, Edition 02, 1 / 5
to
L

Advertisement

loading
Need help?

Need help?

Do you have a question about the rexroth XI110204 and is the answer not in the manual?

Questions and answers

Summary of Contents for Bosch rexroth XI110204

  • Page 1 ctrlX I/O Digital Input Module XI110204 4-channel, DC 24 V, 3 ms Input Filter, 2-wire R911421693 DOK-XIO***-XI110204*DI-DA02-EN-P Edition 02 Functional description XI110204 Connection tech- 2-wire technique The digital input module XI110204 is used to detect binary 24 nique V control signals in a ctrlX I/O station. The module has four Specification EN 61131-2, type 1/3 channels in a 2-wire technique.
  • Page 2 Electrical safety Permitted air humidity   according to DIN EN 61131-2    NOTICE (Operation, storage, trans- Loss of electric safety port) 10 to 95 % Unintended handling can affect the device safety! Observe Degree of protection IP20 the notes in the present data sheet during installation, com- Acc.
  • Page 3 Installation NOTICE Device destruction due to electrostatic discharge Clamping point assignment The device contains components that can be damaged or destroyed by electrostatic discharge. Comply with the Clamping point Assignment Color required safety measures against electrostatic discharge 1 - DI CH.1 Grey (ESD) acc.
  • Page 4 7.3.1 Mounting the ctrlX I/O module NOTICE Damage of the device by plug mounting under voltage! Disconnect the module and all connected module compo- nents from voltage before mounting or dismounting. NOTICE Damage of the device by short circuit of patch connectors There is an endcover on the right upon delivery of the bus coupler.
  • Page 5 Press the pusher with a suitable slotted screwdriver. – Remove line. – Release the pusher. *R911421693-02* Bosch Rexroth AG Bgm.-Dr.-Nebel-Str. 2 97816 Lohr a.Main © Bosch Rexroth AG 2024 Germany Tel. +49 9352 18 0 Fax +49 9352 18 8400 DC-AE/PWG-HW (AnBe/MaKo/MePe) www.boschrexroth.com/electrics...

This manual is also suitable for:

R911417202