Copeland 085-0160-00 Application Engineering Bulletin

Guidelines to using a three phase voltage monitor
Hide thumbs Also See for 085-0160-00:

Advertisement

Quick Links

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 085-0160-00 and is the answer not in the manual?

Questions and answers

Summary of Contents for Copeland 085-0160-00

  • Page 1: Table Of Contents

    Parameters Installation Din Rail Mounting Instructions Wiring Diagrams Setting the Parameters Terminating the Resistor Button Functions Parameters Fault Conditions Troubleshooting 085-0160-00 MODBUS Data Mapping Discrete Inputs (Read Only) Input Registers (Read Only) Holding registers (Read/Write) Terminal Installation Instructions Parameter Settings...
  • Page 2: Safety

    Additionally, a compressor’s refrigerant lines keep refrigerant and oil under pressure. When removing or recharging refrigerant from this component during service, this can pose a pressurized fluid hazard. © 2024 Copeland LP www.copeland.com...
  • Page 3: Flammable Refrigerant Hazards

    - IMMEDIATELY GET AWAY if you hear unusual sounds in the compressor. They can indicate that terminal pin ejection may be imminent. This may sound like electrical arcing (sizzling, sputtering or popping). However, terminal venting may still occur even if you do not hear any unusual sounds. © 2024 Copeland LP www.copeland.com...
  • Page 4 POE lubricant. Handle POE oil with care. Refer to the Safety Data Sheet (SDS) for further details. • Before energizing the system: 1. Securely fasten the protective terminal cover or molded plug to the compressor, and 2. Check that the compressor is properly grounded per the applicable system and compressor requirements. © 2024 Copeland LP www.copeland.com...
  • Page 5: Signal Word Definitions

    WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. © 2024 Copeland LP www.copeland.com...
  • Page 6: Introduction

    BULLETIN AE10-1313 R3 SEPTEMBER 2024 Introduction Figure 1 Voltage Wiring for Three Phase Line Monitors A phase monitor can be used with any three phase motor. A monitor such as the Copeland 085-0160-00 is recommended monitoring remote locations environments with...
  • Page 7: Figure 2 Part Winding Start (Pws) For 3-Phase Monitors

    BULLETIN AE10-1313 R3 SEPTEMBER 2024 Figure 2 Part Winding Start (PWS) For 3-Phase Monitors © 2024 Copeland LP www.copeland.com...
  • Page 8: Installation, Operation & Application Guide

    Set Date and Time: Provides real time clock for date and • Terminations: 1/4" quick connects time stamp • Weight: 12 ounces (341 grams) Language: Set to English or Spanish language for display ModBus: • RS485 Connections © 2024 Copeland LP www.copeland.com...
  • Page 9: Installation

    Note 2: Use of female quick connect terminals suitable for field wiring required. Female quick-connect terminals suitable for 1. Using (2) #8 screws, mount the 085-0160-00 in a cool, factory-wiring only are not permitted. dry, easily accessible location in the control panel.
  • Page 10: Wiring Diagrams

    Setup LED will automatically turn OFF. Terminating the Resistor The 085-0160-00 is equipped with an internal terminator resistor which can be enabled or disabled in the set up. Button Functions Press arrows to scroll through and select user parameter settings in Setup mode.
  • Page 11: Parameters

    1. Re-energize the contactor are present 2. If the fault reappears after the load energizes: a. Turn all power OFF b. Check all load side connections c. Check the contacts of the contactor for debris or excess carbon © 2024 Copeland LP www.copeland.com...
  • Page 12: Troubleshooting

    1. Check system for under-voltage cause. minimum percentage 2. Increase the percent under-voltage setting if necessary. 3. Increase the fault interrogation time if necessary *Only swap phases during initial setup, not after the 085-0160-00 has been in operation without errors. Troubleshooting Problem LCD Readout...
  • Page 13: 085-0160-00 Modbus Data Mapping

    ^ to lengthen the delay Scrambled characters Unreadable Irrelevant Processor or memory damaged. Replace control. or black boxes on LCD screen 085-0160-00 MODBUS Data Mapping Discrete Inputs (Read Only) Address Field Comments 10000 Relay State 0 = off, 1 = on...
  • Page 14 Fault 3 30025 Fault 4 30026 Fault 5 30027 Fault 6 30028 Fault 7 30029 Fault 8 30030 Fault 9 30031 Fault 10 30032 Fault 11 30033 Fault 12 30034 Fault 13 30035 Fault 14 © 2024 Copeland LP www.copeland.com...
  • Page 15: Holding Registers (Read/Write)

    0 = English, 1 = Spanish 40010 New date 5 bits day | 4 bits month | 7 bits years since 2020 40011 New time Minutes since midnight RS485 Termination 40012 0 = no, 1 = yes Resistor © 2024 Copeland LP www.copeland.com...
  • Page 16: Terminal Installation Instructions

    It is adjustable from 0 to 10 Terminals 6, 7 and 8 used for ModBus communication on minutes. Recommended: 4 mins 085-0160-00. Use of female quick connect terminals suitable for field wiring are required. Female quick-connect Delay on Fault terminals suitable for factory-wiring only are not permitted.
  • Page 17 **Non-critical faults are faults such as high/low voltage and phase unbalance. Critical faults, such as phase loss and phase reversal, have a fault interrogation and typical response time of under 4 seconds and it is not user adjustable. © 2024 Copeland LP www.copeland.com...
  • Page 18 BULLETIN AE10-1313 R3 SEPTEMBER 2024 Revision Tracking R3 The document format has been updated to the new Copeland format All occurrences of "Emerson" have been removed A note regarding A3 and R290 venting has been updated © 2024 Copeland LP...

Table of Contents