Advertisement
This manual provides installation instructions for PVC/CPVC common venting and is a supplement to the Installation and Operations Manual supplied with the Rinnai Tankless Water Heater. For Ubbink Polypropylene (PP) common venting, refer to installation instructions for Ubbink Polypropylene (PP) common venting.
Common venting must satisfy all the requirements of the Installation and Operations Manual, as well as the requirements in this manual.
For detailed information on the Rinnai Tankless Water Heater, including installation instructions, refer to the Tankless Water Heater Installation and Operation Manual or view an online version at rinnai.us.
Illustrations of tankless water heaters in this document represent one of the applicable Rinnai tankless water heaters. Your water heater may look different than the images in this document.
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Common venting allows multiple Rinnai Tankless Water Heaters to share the same vent system.
Rinnai Tankless Water Heaters can only be common vented with Schedule 40 PVC/CPVC or with a Rinnai certified common vent system.
Do Not
Must Do
PVC solvents (primer and glue) can be extremely flammable. Vapors may cause a flash fire or explosion resulting in property damage, personal injury or death.
When installing PVC/CPVC Common Vent, follow these guidelines:
DO NOT
ACCEPTABLE | ACCEPTABLE | NOT ACCEPTABLE |
90° Elbows, Long Sweep | 90° Elbows, Short Sweep | 90° Elbows, Close Turn |
![]() | ![]() | ![]() |
NOTE
Unless recovering a tank, Rinnai recommends electronically connecting with common venting and where water heaters are in a manifold system. Refer to the Rinnai Tankless Water Heater Installation and Operation Manual for additional details on electronically connecting multiple water heaters.
For the table below:
Common Vent Maximum Equivalent Vent Length / Rinnai Common Vent System or Schedule 40 PVC/CPVC
Direct Vent
Room Air
Direct Vent
Room Air
Direct Vent
Room Air
Various 3 in., 4 in., and 6 in. Schedule 40 PVC/CPVC Terminations:
Support Brackets Required
NOTE
Vent termination per ANSI Z223.1/NFPA 54. For clearances not specified in ANSI Z223.1/NFPA 54, clearances are in accordance with local installation codes and the requirements of the gas supplier.
Support Brackets Required
If the vent system is to be enclosed, it is suggested that the design of the enclosure shall permit inspection of the vent system. The design of such an enclosure shall be deemed acceptable by the installer or the local inspector.
Refer to the Rinnai Tankless Water Heater Installation and Operation Manual for minimum clearance requirements around the water heater.
There should be a minimum of 12 in. (305 mm) between exhaust and intake terminations.
Clearances of Brackets:
All supports, such as wall brackets or spacer blocks, must be installed with a maximum distance of 78 in. (2 m) between each support. Additional supports can be installed before and after an elbow if needed.
Freestanding Components:
Components which are installed freestanding for vertical termination with a length of over 59 in. (1.5 m), must be additionally secured to the building with guys or braces.
Pitched Roof Termination Clearances:
NOTE
Vent termination per ANSI Z223.1/NFPA 54. For clearances not specified in ANSI Z223.1/NFPA 54, clearances are in accordance with local installation codes and the requirements of the gas supplier.
This appliance, along with the Common Vent System, is certified with the 3 in., 4 in., 6 in. wall termination mounted in the orientation shown below.
Vent Size | Separation Distance |
3 in., 4 in., 6 in. | 12 in. Minimum |
The exhaust and combustion air terminations must follow these clearances:
There should be a minimum of 36 in. (91 cm) between exhaust terminations in multiple common vent installations. Refer to the Rinnai Tankless Water Heater Installation and Operation Manual for maximum vent lengths based on the vent diameter installed.
Common Vent Applications Utilizing Room Air
This rack system requires adequate combustion air for ventilation and dilution of flue gases. Failure to provide adequate combustion air can result in unit failure, fire, explosion, serious bodily injury or death. Use the following methods to ensure adequate combustion air is available for correct and safe operation of this rack system.
Combustion air must be free of corrosive chemicals. Do not provide combustion air from corrosive environments. System failure due to corrosive air is not covered by warranty.
Combustion air must be free of acid forming chemicals such as sulfur, fluorine and chlorine. These chemicals have been found to cause rapid damage and decay and can become toxic when used as combustion air in gas appliances. Such chemicals can be found in, but not limited to bleach, ammonia, cat litter, aerosol sprays, cleaning solvents, varnish, paint, and air fresheners. Do not store these products or similar products in the vicinity of the water heater system.
Unconfined Space:
An unconfined space is defined in National Fuel Gas Code, ANSI Z223.1/NFPA 54 as "a space whose volume is not less than 50 cubic feet per 1,000 Btu/hr (4.8 m3 per kW per hour) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space." If the "unconfined space" containing the system is in a building with tight construction, additional outside air may be required for proper operation. Outside air openings should be sized the same as for a confined space.
Confined Space:
(Small Room, Closet, Alcove, Utility Room, Etc.)
A confined space is defined in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 as "a space whose volume is less than 50 cubic feet per 1,000 Btu/hr (4.8 m3 per kW per hour) of the aggregate input rating of the combined appliances installed in that space." A confined space must have two combustion air openings. Size the combustion air openings based on the BTU input for all gas utilization equipment in the space and the method by which combustion air is supplied.
Louvers and Grills
When sizing the permanent opening, consideration must be taken for the design of the louvers or grills to maintain the free area required for all gas utilizing equipment in the space. If the free area of the louver or grill design is not available, assume wood louvers will have 25% free area and metal louvers or grills will have 75% free area. Under no circumstance should the louver, grill or screen have openings smaller than 1/4 in.
Example:
Wood: 10 in x 12 in x 0.25 = 30 in2
Metal: 10 in x 12 in x 0.75 = 90 in2
Location
To maintain proper circulation of combustion air, two permanent openings (one upper, one lower) must be positioned in confined spaces. The upper shall be within 12 in. (305 mm) of the top of the confined space and the lower opening shall be within 12 in. (305 mm) of the bottom of the confined space. Openings must be positioned as to never be obstructed.
Using Outdoor Air For Combustion
Outdoor air can be provided to a confined space through two permanent openings, one commencing within 12 in. (305 mm) of the top and one commencing within 12 in. (305 mm) of the bottom of the confined space. The openings shall communicate to the outside by one of two ways.
(Be sure to maintain 12 in. (305 mm) above grade or anticipated snow level)
Vent termination per ANSI Z223.1/NFPA 54. For clearances not specified in ANSI Z223.1/NFPA 54, clearances are in accordance with local installation codes and the requirements of the gas supplier.
(Be sure to maintain 12 in. (305 mm) above grade or anticipated snow level)
NOTE
Combustion air provided to the system should not be taken from any area of the structure that may produce a negative pressure (such as exhaust fans or powered ventilation fans).
Using Indoor Air For Combustion
When using air from other room(s) in the building, the total volume of the room(s) must be of adequate volume (greater than 50 cubic feet per 1,000 Btu/hr). Each combustion air opening must have at least one square inch of free area for each 1,000 Btu/hr, but not less than 100 square inches each.
When communicating directly with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in 2 /2,000 Btu/hr (1,100 mm 2 /kW) of total input rating of all appliances in the confined space.
Note: If ducts are used, the cross sectional area of the duct must be greater than or equal to the required free area of the openings to which they are connected.
When communicating indirectly with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in 2 /4,000 Btu/hr (550 mm of total input rating of all appliances in the confined space. Combustion air to the appliance can be provided from a well ventilated attic or crawl space.
TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION, COMMON VENTING WITH OTHER MANUFACTURER'S INDUCED DRAFT APPLIANCES IS NOT ALLOWED.
The information below applies to Concentric and Twin Pipe:
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
If locally adopted installation codes specify clearances different than those illustrated, then the most stringent clearance shall prevail.
Clearance to opposite wall is 24 in. (60 cm). | |
[1] A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. [2] Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. | *Clearances are in accordance with local installation codes and the requirements of the gas supplier. |
Other than direct vent, when using room air for combustion, you must install terminations to expel exhaust.
Room Air and External Termination Clearances
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
If locally adopted installation codes specify clearances different than those illustrated, then the most stringent clearance shall prevail.
Clearance to opposite wall is 24 in (60 cm). | |
[1] A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. [2] Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. | *Clearances are in accordance with local installation codes and the requirements of the gas supplier. |
Check on whether local codes supersede the clearances below.
The vent for this appliance shall not terminate
Important considerations for locating vent termination under a soffit (ventilated or unventilated or eave vent; or to a deck or porch)
Represents the exhaust vent of the common venting.
Represents the combustion air vent of the common venting.
Install the Condensate Trap and Drain Pipe
Condensate must be drained to prevent malfunction, diagnostic code failures, or property damage. Condensate should be disposed according to local codes. Refer to the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1 condensate disposal.
A condensate pump must be used if the condensate outlet is lower than the public sewage system.
Rinnai recommends installing a condensate neutralizer which allows condensate to flow through neutralizing media to raise the pH of the condensate to a level that will help prevent corrosion of the drain and public sewer system.
Ensure that the condensate drain does not freeze.
READ ALL INSTRUCTIONS BEFORE INSTALLATION
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
This manual contains the following important safety symbols. Always read and obey all safety messages.
Safety alert symbol. Alerts you to potential hazards that can kill or hurt you and others.
Indicates an imminently hazardous situation which, if not avoided, will result in personal injury or death.
Indicates a potentially hazardous situation which, if not avoided, could result in personal injury or death.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It may also be used to alert against unsafe practices.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Rinnai RU199i, RU180i, RU160i, RU130i, CU199i Manual
Advertisement
Need help?
Do you have a question about the RU199i and is the answer not in the manual?
Questions and answers