Deka HRC Series Installation And Operating Instructions Manual

Stationary battery

Advertisement

Quick Links

STATIONARY BATTERY INSTALLATION
AND OPERATING INSTRUCTIONS
IN REFERENCE TO THIS MANUAL:
– "Battery" is defined as an individual 12-volt unit.
– "Battery string" is defined as a series connected elec-
trical system comprised of batteries
(individual 12-volt units).
SAFETY PRECAUTIONS
Although all valve regulated batteries have the
electrolyte immobilized within the battery, the
electrical hazard associated with batteries still exists.
Work performed on these batteries should be
done with the tools and the protective equipment
listed below. VRLA battery installations should be
supervised by personnel familiar with batteries and
battery safety precautions.
WARNING: Risk of fire, explosion or burns. Do not
disassemble, heat above 65°C, or incinerate .
Protective Equipment
Although VRLA batteries can vent or leak small
amounts of electrolyte, electrical safety is the principle
but not the only concern for safe handling. Per IEEE
1188 recommendations, the following minimum set
of equipment for safe handling of the battery and
protection of personnel shall be available:
1. Safety glasses with side shields, or goggles, or face
shields as appropriate. (Consult application specific
requirements)
2. Electrically insulated gloves, appropriate for
the installation.
3. Protective aprons and safety shoes.
4. Portable or stationary water facilities in the battery
vicinity for rinsing eyes and skin in case of contact
with acid electrolyte.
5. Class C fire extinguisher.
6. Acid neutralizing agent.
1
For Energy Storage
applications following
UL 1973 requirements
Appendix A must
be reviewed.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HRC Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Deka HRC Series

  • Page 1 STATIONARY BATTERY INSTALLATION AND OPERATING INSTRUCTIONS For Energy Storage applications following UL 1973 requirements Appendix A must be reviewed. IN REFERENCE TO THIS MANUAL: Protective Equipment Although VRLA batteries can vent or leak small – “Battery” is defined as an individual 12-volt unit. amounts of electrolyte, electrical safety is the principle –...
  • Page 2: Receiving And Storage

    RECEIVING & STORAGE Protective Equipment cont. 7. Adequately insulated tools (as defined by ASTM F1505 Receiving Inspection “Standard Specification for Insulated and Insulating Hand Tools”). Upon receipt, and at the time of actual unloading, 8. Lifting devices of adequate capacity, when required. each package should be visually inspected for any possible damage or electrolyte leakage.
  • Page 3: Installation

    See rack assembly instructions. for damage or injury as a result of mishandling or misuse of the product. DEKA HRC BATTERIES ARE TESTED AND APPROVED TO BE INSTALLED AND OPERATED IN THEIR UPRIGHT POSITION. FRONT TERMINAL BATTERY TOP TERMINAL BATTERY Terminals –...
  • Page 4: Battery Assembly

    Venting SYSTEM OPERATIONS Under normal operation, VRLA batteries emit hydro- Charger Voltage gen gas, which is combustible at certain concentra- tions. Proper ventilation should be provided per IEEE These batteries are designed for continuous 1187 and/or local codes. Some batteries are designed float applications.
  • Page 5: Record Keeping

    RECORD KEEPING Battery Operation Battery operating temperature will affect battery string Voltages, Temperatures & Ohmic capacity and operating life. Temperatures greater than 77°F (25°C) will reduce READINGS the operating life of the battery. For every 13°F (7°C) Record keeping is an important part of stationary increase in operating temperature above 77°F (25°C), battery maintenance and warranty coverage.
  • Page 6: Maintenance

    MAINTENANCE Battery Cleaning Do not use any chemical compounds to clean Always wear eye protection when working on or near batteries. Batteries, cabinets, and racks, shall batteries. Keep sparks and open flames away from only be cleaned with: clear water, a mixture of batteries at all times.
  • Page 7 10. Minimum & maximum allowable operating range is -40°C (-40°F) to 40°C (104°F). 11. Minimum & maximum allowable discharge current to an end voltage of 10.50V (1.75 vpc) is listed below: Deka HRC – Minimum & Maximum Discharge Currents Minimum Discharge...
  • Page 8 APPENDIX B...
  • Page 9 APPENDIX C VOLTAGE COMPENSATION CHART °C Float Equalize °F >35 13.38 14.28 >95 13.39 14.29 93.2 13.40 14.30 91.4 13.42 14.32 89.6 13.43 14.33 87.8 13.44 14.34 86.0 13.45 14.35 84.2 13.46 14.36 82.4 13.48 14.38 80.6 13.49 14.39 78.8 13.50 14.40 77.0...
  • Page 10 APPENDIX D DEKA HRC CHARGE CURRENT LIMITS Battery Max. Charge Min. Charge Type Current (A) Current (A)** HRC600 13.3 HRC700 16.1 HRC800 17.2 HRC950 24.4 ** = Using minimum charge current will extend recharge time and increase risk of battery...
  • Page 11 APPENDIX E BATTERY MAINTENANCE REPORT Inspection Date _____________________________________________________________________ No. of Units/String __________________ Company ___________________________________________________________________________ Type _______________________________ Address ____________________________________________________________________________ Date New __________________________ Battery location and/or number ______________________________________________________ Date Installed _______________________ Individual Charger Output _____________________ Amp Air Temperature ______________________°F Battery Readings Total Battery String Voltage ________________ Panel Meter Volts ______________________ Unit Ohms or...
  • Page 12 APPENDIX F ACCEPTANCE & PERFORMANCE TESTING Each cell must be at 100% State of Charge prior to performing an acceptance or If a DC load bank is used, be sure to disconnect the battery string from the performance test on the battery system. To ensure the cells are fully charged, the UPS charger/load circuit.
  • Page 13 K t Factor (Discharges ≥ 1 hr.) K c Factor (Discharges ≤ 1 hr.) Temperature Temperature Temperature Temperature K t Factor K t Factor K c Factor K c Factor ºC ºF ºC ºF ºC ºF ºC ºF 35.0 0.962 22.2 1.019 35.0...
  • Page 14 e-mail: reservepowersales@dekabatteries.com www.dekabatteries.com East Penn Manufacturing Co. Lyon Station, PA 19536-0147 Phone: 610-682-3263 Fax: 610-682-4781 All data subject to change without notice. No part of this document may be copied or E.P.M. Form No. 2531 Revised 11/24 © 2024 by EPM Printed in U.S.A. reproduced, electronically or mechanically, without written permission from the company.