Trane TVR Connect Series Engineering Data
Trane TVR Connect Series Engineering Data

Trane TVR Connect Series Engineering Data

Commercial air conditioners

Advertisement

Quick Links

Engineering Data
TVR Connect Series
4TVH0086KE000AA
4TVH0096KE000AA
4TVH0115KE000AA
4TVH0140KE000AA
4TVH0155KE000AA
4TVH0170KE000AA
4TVH0192KE000AA
4TVH0210KE000AA
4TVH0229KE000AA
Commercial Air Conditioners
4TVH0249KE000AA
4TVH0268KE000AA
4TVH0290KE000AA
4TVH0307KE000AA
4TVH0324KE000AA
4TVH0344KE000AA
4TVH0362KE000AA
4TVH0382KE000AA
R410A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TVR Connect Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Trane TVR Connect Series

  • Page 1 R410A Commercial Air Conditioners Engineering Data TVR Connect Series 4TVH0249KE000AA 4TVH0086KE000AA 4TVH0096KE000AA 4TVH0268KE000AA 4TVH0115KE000AA 4TVH0290KE000AA 4TVH0140KE000AA 4TVH0307KE000AA 4TVH0155KE000AA 4TVH0324KE000AA 4TVH0170KE000AA 4TVH0344KE000AA 4TVH0192KE000AA 4TVH0362KE000AA 4TVH0210KE000AA 4TVH0229KE000AA 4TVH0382KE000AA...
  • Page 2 TVR CONNECT 380V 50/60Hz CONTENTS Part 1 General Information ................ 3 Part 2 Outdoor Unit Engineering Date ............ 21 Part 3 System Design and Installation ..........232...
  • Page 3 TVR CONNECT 380V 50/60Hz...
  • Page 4: Table Of Contents

    TVR Connect 380V 50/60Hz Part 1 General Information 1 Indoor and Outdoor Unit Capacities ............4 2 External Appearance .................. 7 3 Outdoor Unit Combinations ............... 9 4 Nomenclature ..........Erro! Indicador não definido. 5 Combination Ratio ................... 11 6 Selection Procedure ................. 13...
  • Page 5: Indoor And Outdoor Unit Capacities

    TVR Connect 380V 50/60Hz 1 Indoor and Outdoor Unit Capacities 1.1 Indoor Units 1.1.1 Standard indoor units Table 1-1.1: Standard indoor unit abbreviation codes Abbreviation Abbreviation Type Type code code One-way Cassette High Static Pressure Duct Two-way Cassette Wall-mounted Compact Four-way Cassette Ceiling &...
  • Page 6: Outdoor Units

    TVR Connect 380V 50/60Hz Airflow rate 200m 300m 400m 500m 800m 1000m 1500m 2000m 1.3 Outdoor Units Table 1-1.5: Outdoor unit capacity range Capacity Model Name Combination Type 4TVH0086KE000AA 10HP 4TVH0096KE000AA 12HP 4TVH0115KE000AA 14HP 4TVH0140KE000AA 16HP 4TVH0155KE000AA 18HP 4TVH0170KE000AA 20HP 4TVH0192KE000AA 22HP 4TVH0210KE000AA...
  • Page 7 TVR Connect 380V 50/60Hz Table 1-1.5: Outdoor unit capacity range (continued) Model Name Capacity Combination Type 100HP 4TVH0956KE000AA 28HP+36HP+36HP 102HP 4TVH0974KE000AA 22HP+40HP+40HP 104HP 4TVH0995KE000AA 32HP+36HP+36HP 106HP 4TVH1012KE000AA 34HP+36HP+36HP 108HP 4TVH1032KE000AA 36HP+36HP+36HP 110HP 4TVH1050KE000AA 36HP+36HP+38HP 112HP 4TVH1070KE000AA 36HP+36HP+40HP 114HP 4TVH1088KE000AA 36HP+38HP+40HP 116HP 4TVH1108KE000AA 36HP+40HP+40HP...
  • Page 8: External Appearance

    TVR Connect 380V 50/60Hz 2 External Appearance 2.1 Indoor Units 2.1.1 Standard indoor units Table 1-2.1: Standard indoor unit appearance One-way Cassette Two-way Cassette Compact Four-way Cassette Four-way Cassette Arc Duct Medium Static Pressure Duct High Static Pressure Duct Floor Standing Wall-mounted Ceiling &...
  • Page 9 TVR Connect 380V 50/60Hz 2.3 Outdoor Units 2.3.1 Single units Table 1-2.4: Single outdoor unit appearance 8/10/12/14/16/18HP 20/22/24HP 26/28/30/32/34/36/38/40HP (with single fan) (with dual fans) (with dual fans) 2.3.2 Combinations of units Table 1-2.5: Combination outdoor unit appearance 42HP 44/46/48HP 50/52HP 54HP 56HP...
  • Page 10: Outdoor Unit Combinations

    TVR Connect 380V 50/60Hz 3 Outdoor Unit Combinations Table 1-3.1: Outdoor unit combinations System Outdoor Modules No. of capacity branch units joint kit 25.2 ● 28.0 ● 33.5 ● 40.0 ● 45.0 ● 50.0 ● 56.0 ● 61.5 ● 67.0 ●...
  • Page 11 TVR Connect 380V 50/60Hz Table continued on next page … Table 1-3.1: Outdoor unit combinations (continued) System Outdoor No. of Modules capacity branch units joint kit 314.0 ●● ● 319.0 ● ● ● TODK03CN 325.0 ● ●● 330.0 ● ●● 336.0 ●●●...
  • Page 12: Combination Ratio

    TVR Connect 380V 50/60Hz 4 Combination Ratio Sum of capacity indexes of the indoor units Combination ratio = Capacity index of the outdoor units Table 1-5.1: Indoor and outdoor unit combination ratio limitations Maximum combination ratio Minimum Type Fresh air processing Fresh air processing units and combination ratio Standard indoor units only...
  • Page 13 TVR Connect 380V 50/60Hz Table 1-5.2: Combinations of indoor and outdoor units Outdoor unit capacity Sum of capacity indexes of Sum of capacity indexes of connected indoor Maximum number of Capacity connected indoor units (standard units (fresh air processing units and standard connected indoor index indoor units only)
  • Page 14: Selection Procedure

    TVR Connect 380V 50/60Hz 5 Selection Procedure 5.1 Procedure Step 1: Establish design conditions Design temperature and humidity (indoor and outdoor) Required heat load of each room System peak load Piping length, level differences Indoor unit specifications (type and quantity) Step 2: Select indoor units Decide indoor unit safety factor Select indoor unit models ensuring that:...
  • Page 15 TVR Connect 380V 50/60Hz 5.2 Example The following is a selection example based on total heat load for cooling. Figure 1-6.1: Room plan Room H Room G Room A Room F Room B Room E Room C Room D Step 1: Establish design conditions ▪...
  • Page 16 TVR Connect 380V 50/60Hz Table 1-6.2: Extract from medium static pressure duct (T2) cooling capacity table Indoor air temperature Capacity 14°C WB 16°C WB 18°C WB 19°C WB 20°C WB 22°C WB 24°C WB Model index 20°C DB 23°C DB 26°C DB 27°C DB 28°C DB...
  • Page 17 TVR Connect 380V 50/60Hz Table 1-6.5: Extract from Table 1-5.2 Combinations of Indoor and outdoor units Outdoor unit capacity Sum of capacity indexes of Maximum number of Capacity connected indoor units (standard connected indoor index indoor units only) units 50.0 250 to 650 56.0 280 to 728...
  • Page 18 TVR Connect 380V 50/60Hz Find the correction factor for piping length and level difference (“K1”) Figure 1-6.3: TVR CONNECT rate of change in cooling capacity K1=0.943 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 -100 -110 Notes:...
  • Page 19 TVR Connect 380V 50/60Hz Part 2 Outdoor Unit Engineering Data 1 Specifications ................... 22 2 Dimensions ....................36 3 Installation Space Requirements .............. 43 4 Piping Diagrams ..................44 5 Wiring Diagrams ..................49 6 Electrical Characteristics ................51 7 Functional Components and Safety Devices ..........53 8 Capacity Tables ..................
  • Page 20: Specifications

    TVR Connect 380V 50/60Hz 1 Specifications 8-14HP Table 2-1.1: 8-14HP specifications Model name 4TVH0086KE000AA 4TVH0096KE000AA 4TVH0115KE000AA 4TVH0140KE000AA Power supply V/N/Hz 380-415/3/50(60) 25.2 28.0 33.5 40.0 Capacity kBtu/h 85.9 95.5 114.2 136.4 Cooling Power input 5.26 4.88 4.80 4.63 27.0 31.5 37.5 45.0 Capacity...
  • Page 21 TVR Connect 380V 50/60Hz Table 2-1.2: 16-22HP specifications Model name 4TVH0155KE000AA 4TVH0170KE000AA 4TVH0192KE000AA 4TVH0210KE000AA Power supply V/N/Hz 380-415/3/50(60) 45.0 50.0 56.0 61.5 Capacity kBtu/h 153.5 170.5 191.0 209.7 Cooling Power input 10.0 11.6 13.5 15.0 4.50 4.30 4.14 4.10 50.0 56.0 63.0 69.0...
  • Page 22 TVR Connect 380V 50/60Hz 24-30HP Table 2-1.3: 24-30HP specifications Model name 4TVH0229KE000AA 4TVH0249KE000AA 4TVH0268KE000AA 4TVH0290KE000AA Power supply V/N/Hz 380-415/3/50(60) 67.0 73.0 78.5 85.0 Capacity kBtu/h 228.5 248.9 267.7 289.9 Cooling Power input 16.6 19.0 23.0 25.1 4.04 3.84 3.42 3.38 75.0 81.5 87.5...
  • Page 23 TVR Connect 380V 50/60Hz 32-40HP Table 2-1.4: 32-40HP specifications 4TVH0307KE0 4TVH0324KE0 4TVH0344KE0 4TVH0362KE0 4TVH0382KE0 Model name 00AA 00AA 00AA 00AA 00AA Power supply V/N/Hz 380-415/3/50(60) 90.0 95.2 101.0 106.0 112.0 Capacity kBtu/h 306.9 324.6 344.4 361.5 381.9 Cooling Power input 27.9 30.2 33.1...
  • Page 24 TVR Connect 380V 50/60Hz 42-48HP Table 2-1.5: 42-48HP specifications Model name (Combination unit) 4TVH0399KE000AA 4TVH0420KE000AA 4TVH0439KE000AA 4TVH0458KE000AA Combination type 18HP+24HP 22HP+22HP 22HP+24HP 24HP+24HP Power supply V/N/Hz 380-415/3/50(60) 117.0 123.0 128.5 134.0 Capacity kBtu/h 399.0 419.4 438.2 456.9 Cooling Power input 28.2 30.0 31.6...
  • Page 25 TVR Connect 380V 50/60Hz 50-56HP Table 2-1.6: 50-56HP specifications Model name (Combination unit) 4TVH0484KE000AA 4TVH0499KE000AA 4TVH0517KE000AA 4TVH0537KE000AA Combination type 14HP+36HP 16HP+36HP 22HP+32HP 16HP+40HP Power supply V/N/Hz 380-415/3/50(60) 141.0 146.0 151.5 157.0 Capacity kBtu/h 480.8 497.9 516.6 535.4 Cooling Power input 41.8 43.1 42.9...
  • Page 26 TVR Connect 380V 50/60Hz 58-64HP Table 2-1.7: 58-64HP specifications Model name (Combination unit) 4TVH0554KE000AA 4TVH0573KE000AA 4TVH0592KE000AA 4TVH0611KE000AA Combination type 22HP+36HP 24HP+36HP 22HP+40HP 24HP+40HP Power supply V/N/Hz 380-415/3/50(60) 162.5 168.0 173.5 179.0 Capacity kBtu/h 554.1 572.9 591.6 610.4 Cooling Power input 48.1 49.7 54.2...
  • Page 27 TVR Connect 380V 50/60Hz 66-72HP Table 2-1.8: 66-72HP specifications Model name (Combination unit) 4TVH0631KE000AA 4TVH0651KE000AA 4TVH0668KE000AA 4TVH0688KE000AA Combination type 32HP+34HP 32HP+36HP 34HP+36HP 36HP+36HP Power supply V/N/Hz 380-415/3/50(60) 185.2 191.0 196.2 202.0 Capacity kBtu/h 631.5 651.3 669.0 688.8 Cooling Power input 58.1 61.0 63.3...
  • Page 28 TVR Connect 380V 50/60Hz 74-80HP Table 2-1.9: 74-80HP specifications Model name (Combination unit) 4TVH0706KE000AA 4TVH0726KE000AA 4TVH0744KE000AA 4TVH0764KE000AA Combination type 36HP+38HP 36HP+40HP 38HP+40HP 40HP+40HP Power supply V/N/Hz 380-415/3/50(60) 207.0 213.0 218.0 224.0 Capacity kBtu/h 705.9 726.3 743.4 763.8 Cooling Power input 68.9 72.3 75.0...
  • Page 29 TVR Connect 380V 50/60Hz 82-88HP Table 2-1.10: 82-88HP specifications Model name (Combination unit) 4TVH0783KE000AA 4TVH0802KE000AA 4TVH0821KE000AA 4TVH0840KE000AA Combination type 22HP+24HP+36HP 24HP+24HP+36HP 22HP+24HP+40HP 24HP+24HP+40HP Power supply V/N/Hz 380-415/3/50(60) 229.5 235.0 240.5 246.0 Capacity kBtu/h 782.6 801.4 820.1 838.9 Cooling Power input 64.7 66.3 70.7...
  • Page 30 TVR Connect 380V 50/60Hz 90-96HP Table 2-1.11: 90-96HP specifications Model name (Combination unit) 4TVH0858KE000AA 4TVH0880KE000AA 4TVH0898KE000AA 4TVH0917KE000AA Combination type 18HP+36HP+36HP 20HP+36HP+36HP 22HP+36HP+36HP 24HP+36HP+36HP Power supply V/N/Hz 380-415/3/50(60) 252.0 258.0 263.5 269.0 Capacity kBtu/h 859.3 879.8 898.5 917.3 Cooling Power input 77.9 79.8 81.2...
  • Page 31 TVR Connect 380V 50/60Hz Table 2-1.12: 98-104HP specifications Model name (Combination unit) 4TVH0936KE000AA 4TVH0956KE000AA 4TVH0974KE000AA 4TVH0995KE000AA Combination type 22HP+36HP+40HP 28HP+36HP+36HP 22HP+40HP+40HP 32HP+36HP+36HP Power supply V/N/Hz 380-415/3/50(60) 274.5 280.5 285.5 292.0 Capacity kBtu/h 936.0 956.5 973.6 995.7 Cooling Power input 87.3 89.2 91.8 94.1...
  • Page 32 TVR Connect 380V 50/60Hz 106-112HP Table 2-1.13: 106-112HP specifications Model name (Combination unit) 4TVH1012KE000AA 4TVH1032KE000AA 4TVH1050KE000AA 4TVH1070KE000AA Combination type 34HP+36HP+36HP 36HP+36HP+36HP 36HP+36HP+38HP 36HP+36HP+40HP Power supply V/N/Hz 380-415/3/50(60) 297.2 303.0 308.0 314.0 Capacity kBtu/h 1013.5 1033.2 1050.3 1070.7 Cooling Power input 96.5 99.3 102.0...
  • Page 33 TVR Connect 380V 50/60Hz 114-120HP Table 2-1.14: 114-120HP specifications Model name (Combination unit) 4TVH1088KE000AA 4TVH1108KE000AA 4TVH1126KE000AA 4TVH1146KE000AA Combination type 36HP+38HP+40HP 36HP+40HP+40HP 38HP+40HP+40HP 40HP+40HP+40HP Power supply V/N/Hz 380-415/3/50(60) 319.0 325.0 330.0 336.0 Capacity kBtu/h 1087.8 1108.3 1125.3 1145.8 Cooling Power input 108.1 111.4 114.1...
  • Page 34: Dimensions

    TVR Connect 380V 50/60Hz 2 Dimensions 2.1 Single Units 8/10/12/14/16/18HP Figure 2-2.1: 8/10/12/14/16/18HP dimensions (unit: mm) 70×40 220×70 20/22/24HP Figure 2-2.2: 20/22/24HP dimensions (unit: mm) 1340 220×70 70×40...
  • Page 35 TVR Connect 380V 50/60Hz 26/28/30/32/34/36/38/40HP Figure 2-2.3: 26/28/30/32/34/36/38/40HP dimensions (unit: mm) 1880 220×70 70×40 Detail R Table 2-2.1: Connection piping diameter (unit: mm) Figure 2-2.4: Detail R (unit: mm) Size ΦA ΦB Φ12.7 Φ25.4 Check port (used to measure Gas side system pressure, charge 10HP Φ12.7...
  • Page 36 TVR Connect 380V 50/60Hz 2.2 Combinations of Units 42HP Figure 2-2.5: 42HP dimensions (unit: mm) Outdoor unit 1 Outdoor unit 2 100-500 1340 44/46/48HP Figure 2-2.6: 44/46/48HP dimensions (unit: mm) Outdoor unit 1 Outdoor unit 2 100-500 1340 1340...
  • Page 37 TVR Connect 380V 50/60Hz 50/52/56HP Figure 2-2.7: 50/52/56HP dimensions (unit: mm) Outdoor unit 1 Outdoor unit 2 100-500 1880 54/58/60/62/64HP Figure 2-2.8: 54/58/60/62/64HP dimensions (unit: mm) Outdoor unit 1 Outdoor unit 2 100-500 1880 1340...
  • Page 38 TVR Connect 380V 50/60Hz 66/68/70/72/74/76/78/80HP Figure 2-2.9: 66/68/70/72/74/76/78/80HP dimensions (unit: mm) Outdoor unit 2 Outdoor unit 1 100-500 1880 1880 82/84/86/88HP Figure 2-2.10: 82/84/86/88HP dimensions (unit: mm) Outdoor unit 3 Outdoor unit 1 Outdoor unit 2 100-500 100-500 1880 1340 1340...
  • Page 39 TVR Connect 380V 50/60Hz 90HP Figure 2-2.11: 90HP dimensions (unit: mm) Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 100-500 100-500 1880 1880 92/94/96/98/102HP Figure 2-2.12: 92/94/96/98/102HP dimensions (unit: mm) Outdoor unit 3 Outdoor unit 1 Outdoor unit 2 100-500 100-500 1880...
  • Page 40 TVR Connect 380V 50/60Hz 100/104/106/108/110/112/114/116/118/120HP Figure 2-2.13: 100/104/106/108/110/112/114/116/118/120HP dimensions (unit: mm) Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 100-500 100-500 1880 1880 1880...
  • Page 41: Installation Space Requirements

    TVR Connect 380V 50/60Hz 3 Installation Space Requirements For single unit installation For single row installation Figure 2-3.1: Single unit installation (unit: mm) Figure 2-3.2: Single row installation (unit: mm) >1000 >1000 100-500 >1000 >1000 >1000 >1000 Front 100-500 Front >1000 >1000 For multi-row installation...
  • Page 42: Piping Diagrams

    TVR Connect 380V 50/60Hz 4 Piping Diagrams 8-18HP Figure 2-4.1: 8-18HP piping diagram Legend Parts name Parts name Compressor Charge port Oil separator Low pressure sensor High pressure switch Gas-liquid separator Check value Muffler Four-way valve Heat exchanger High pressure sensor Sensor Code Description Heat exchanger deicer temperature sensor...
  • Page 43 TVR Connect 380V 50/60Hz 20-24HP Figure 2-4.2: 20-24HP piping diagram Legend Parts name Parts name Compressor Charge port Oil separator Low pressure sensor High pressure switch Gas-liquid separator Check value Muffler Four-way valve Heat exchanger High pressure sensor Sensor Code Description Heat exchanger deicer temperature sensor Microchannel heat exchanger...
  • Page 44 TVR Connect 380V 50/60Hz 26-36HP Figure 2-4.3: 26-36HP piping diagram Legend Parts name Parts name Compressor Low pressure sensor Oil separator Gas-liquid separator High pressure switch Muffler Check value Heat exchanger Four-way valve Refrigerant bypass solenoid valve (SV6) High pressure sensor Sensor Code Description Heat exchanger deicer temperature sensor...
  • Page 45 TVR Connect 380V 50/60Hz 38-40HP Figure 2-4.3: 38-40HP piping diagram Legend Parts name Parts name Compressor Charge port Oil separator Low pressure sensor High pressure switch Gas-liquid separator Check value Muffler Four-way valve Heat exchanger High pressure sensor Sensor Code Description Heat exchanger deicer temperature sensor Microchannel heat exchanger...
  • Page 46: Oil Separator

    TVR Connect 380V 50/60Hz Key components: 1. Oil separator: Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation efficiency is up to 99%. 2. Gas-liquid separator: Separates liquid refrigerant from gas refrigerant, stores liquid refrigerant and oil to protect compressor from liquid hammering.
  • Page 47: Wiring Diagrams

    TVR Connect 380V 50/60Hz 5 Wiring Diagrams...
  • Page 48 TVR Connect 380V 50/60Hz Legend Code Name Code Name COMP A/ COMP B Compressor Heat exchanger temperature sensor EEVA/ EEVB/ EEVC Electronic expansion valve Outdoor ambient temperature sensor FAN A/ FAN B DC Fan Liquid pipe temperature sensor HEAT A/ HEAT B Compressor heater Microchannel heat exchanger inlet pipe temperature sensor RA/ RB...
  • Page 49: Electrical Characteristics

    TVR Connect 380V 50/60Hz 6 Electrical Characteristics Table 2-6.1: Outdoor unit electrical characteristics Model Power Supply Compressor Min. Max. Capacity Modules Volts TOCA volts volts 50/60 380~415 342 17.0 20.7 12.0 0.56 10HP 50/60 380~415 342 18.8 22.5 14.0 0.56 12HP 50/60 380~415 342 23.0...
  • Page 50 TVR Connect 380V 50/60Hz Table 2-6.1: Outdoor unit electrical characteristics (continued) Model Power Supply Compressor Capacit Min. Max. TOCA Modules Volts volts volts 74HP 38HP 36HP 50/60 380~415 342 138.6 154.2 100+80 33.0+33.7+22.0+33.0 0.92×2+0.92×2 2.9×2+2.9×2 76HP 40HP 36HP 50/60 380~415 342 139.0 154.8 100+80 34.1+34.8+22.0+33.0...
  • Page 51: Functional Components And Safety Devices

    TVR Connect 380V 50/60Hz 7 Functional Components and Safety Devices Table 2-7.1: 8/10/12/14/16/18HP functional components and safety devices Item 10HP 12HP 14HP 16HP 18HP Compressor top and discharge pipe 115°C = 5kΩ ± 3% Compressor temperature sensors Crankcase heater Inverter module Inverter module temperature sensor 90°C = 5kΩ...
  • Page 52: Capacity Tables

    TVR Connect 380V 50/60Hz 8 Capacity Tables 8.1 Cooling Capacity Tables Table2-8.1:8HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 20.12 2.03 22.99 2.18 28.73 2.56 31.50 2.61 33.94 2.68 39.57 2.97 42.55...
  • Page 53 TVR Connect 380V 50/60Hz Notes: Shaded cells indicate rating condition. Table continued on next page … Table2-8.1:8HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 17.68 1.98 20.23 2.13 25.20 2.49 27.74 2.55...
  • Page 54 TVR Connect 380V 50/60Hz Table2-8.1:8HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 14.70 1.68 16.80 1.81 21.00 2.12 23.10 2.17 25.20 2.25 29.40 2.50 32.93 2.93 14.70 1.83 16.80 1.97 21.00 2.30...
  • Page 55 TVR Connect 380V 50/60Hz Table2-8.1:8HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 11.38 1.19 13.04 1.28 16.36 1.51 17.91 1.53 19.57 1.60 22.89 1.78 26.08 2.12 11.38 1.29 13.04 1.39 16.36 1.64...
  • Page 56 TVR Connect 380V 50/60Hz Table2-8.1:8HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 8.17 0.83 9.28 0.89 11.61 1.04 12.83 1.07 14.03 1.12 16.36 1.24 18.69 1.34 8.17 0.91 9.28 0.97 11.61 1.14...
  • Page 57 TVR Connect 380V 50/60Hz Table2-8.2:10HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 22.42 2.54 25.16 2.68 31.53 3.15 34.66 3.22 37.79 3.35 42.69 3.60 44.06 4.15 22.42 2.76 25.16 2.92 31.53 3.43...
  • Page 58 TVR Connect 380V 50/60Hz Table2-8.2:10HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 19.68 2.42 22.42 2.60 27.61 3.00 30.35 3.07 33.09 3.19 38.67 3.54 41.61 4.25 19.68 2.63 22.42 2.82 27.61 3.26...
  • Page 59 TVR Connect 380V 50/60Hz...
  • Page 60 TVR Connect 380V 50/60Hz Table2-8.2:10HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 16.35 2.03 18.70 2.19 23.01 2.52 25.26 2.58 27.51 2.68 32.21 2.98 36.52 3.77 16.35 2.21 18.70 2.38 23.01 2.74...
  • Page 61 TVR Connect 380V 50/60Hz Table2-8.2:10HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 12.73 1.45 14.49 1.56 18.21 1.84 19.98 1.87 21.83 1.95 24.97 2.12 28.39 2.69 12.73 1.58 14.49 1.69 18.21 2.00...
  • Page 62 TVR Connect 380V 50/60Hz Table2-8.2:10HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 9.10 1.09 10.38 1.17 13.02 1.38 14.29 1.41 15.56 1.46 18.21 1.63 20.75 1.76 9.10 1.19 10.38 1.28 13.02 1.50...
  • Page 63 TVR Connect 380V 50/60Hz Table2-8.3:12HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 26.82 3.25 30.69 3.50 37.73 4.03 41.46 4.12 45.57 4.32 51.78 4.67 52.71 5.32 26.82 3.52 30.69 3.79 37.73 4.37...
  • Page 64 TVR Connect 380V 50/60Hz Table2-8.3:12HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 23.55 3.04 26.82 3.26 33.62 3.83 36.32 3.85 39.60 4.01 46.27 4.45 49.78 5.36 23.55 3.29 26.82 3.53 33.62 4.15...
  • Page 65 TVR Connect 380V 50/60Hz...
  • Page 66 TVR Connect 380V 50/60Hz Table2-8.3:12HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 19.57 2.54 22.37 2.73 28.00 3.20 30.69 3.27 33.50 3.40 38.54 3.72 43.69 4.72 19.57 2.75 22.37 2.96 28.00 3.47...
  • Page 67 TVR Connect 380V 50/60Hz Table2-8.3:12HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 15.23 1.82 17.34 1.95 21.79 2.30 23.89 2.35 26.12 2.45 30.46 2.71 33.98 3.39 15.23 1.97 17.34 2.12 21.79 2.49...
  • Page 68 TVR Connect 380V 50/60Hz Table2-8.3:12HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 10.89 1.38 12.41 1.49 15.58 1.75 17.10 1.79 18.62 1.85 21.79 2.06 24.84 2.23 10.89 1.50 12.41 1.61 15.58 1.89...
  • Page 69 TVR Connect 380V 50/60Hz Table2-8.4:14HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 32.02 3.27 36.64 3.53 45.08 4.07 49.48 4.16 53.99 4.32 60.69 4.62 61.97 5.11 32.02 3.65 36.64 3.94 45.08 4.54...
  • Page 70 TVR Connect 380V 50/60Hz Table2-8.4:14HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 28.10 3.14 32.13 3.38 40.12 3.96 43.36 3.98 47.51 4.16 55.15 4.59 58.97 5.31 28.10 3.50 32.13 3.77 40.12 4.41...
  • Page 71 TVR Connect 380V 50/60Hz...
  • Page 72 TVR Connect 380V 50/60Hz Table2-8.4:14HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 23.36 2.65 26.71 2.85 33.41 3.34 36.77 3.42 40.00 3.55 45.90 3.87 52.84 4.83 23.36 2.95 26.71 3.18 33.41 3.73...
  • Page 73 TVR Connect 380V 50/60Hz Table2-8.4:14HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 18.15 1.89 20.81 2.04 26.02 2.39 28.56 2.44 31.10 2.54 36.30 2.81 40.81 3.42 18.15 2.11 20.81 2.28 26.02 2.67...
  • Page 74 TVR Connect 380V 50/60Hz Table2-8.4:14HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 12.95 1.37 14.80 1.48 18.49 1.73 20.35 1.77 22.20 1.85 26.02 2.06 29.71 2.22 12.95 1.53 14.80 1.65 18.49 1.93...
  • Page 75 TVR Connect 380V 50/60Hz Table2-8.5:16HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 36.02 3.58 41.20 3.85 50.52 4.43 55.82 4.55 60.65 4.72 65.72 4.86 67.21 5.53 36.02 4.04 41.20 4.35 50.52 5.00...
  • Page 76 TVR Connect 380V 50/60Hz Table2-8.5:16HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 31.53 3.40 36.14 3.68 44.31 4.22 48.80 4.33 53.17 4.50 62.03 4.99 63.87 5.71 31.53 3.85 36.14 4.15 44.31 4.77...
  • Page 77 TVR Connect 380V 50/60Hz...
  • Page 78 TVR Connect 380V 50/60Hz Table2-8.5:16HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 26.24 2.87 30.04 3.10 37.52 3.62 40.97 3.68 44.31 3.80 51.56 4.20 57.89 5.25 26.24 3.24 30.04 3.50 37.52 4.09...
  • Page 79 TVR Connect 380V 50/60Hz Table2-8.5:16HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 20.49 2.07 23.36 2.22 29.23 2.60 32.11 2.66 35.10 2.78 40.51 3.04 44.88 3.75 20.49 2.34 23.36 2.51 29.23 2.94...
  • Page 80 TVR Connect 380V 50/60Hz Table2-8.5:16HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 14.62 1.56 16.69 1.67 20.83 1.96 22.90 2.00 25.09 2.09 29.23 2.32 33.38 2.51 14.62 1.76 16.69 1.89 20.83 2.21...
  • Page 81 TVR Connect 380V 50/60Hz Table2-8.6:18HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 40.11 4.47 45.82 4.82 56.67 5.58 61.79 5.66 67.50 5.90 72.50 6.02 74.05 6.40 40.11 5.00 45.82 5.38 56.67 6.24...
  • Page 82 TVR Connect 380V 50/60Hz Table2-8.6:18HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 35.12 4.21 40.11 4.53 49.29 5.21 54.17 5.33 59.28 5.56 68.93 6.15 70.70 6.57 35.12 4.70 40.11 5.06 49.29 5.83...
  • Page 83 TVR Connect 380V 50/60Hz...
  • Page 84 TVR Connect 380V 50/60Hz Table2-8.6:18HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 29.17 3.53 33.33 3.80 41.79 4.46 45.36 4.51 49.17 4.66 57.38 5.17 65.59 6.15 29.17 3.94 33.33 4.25 41.79 4.99...
  • Page 85 TVR Connect 380V 50/60Hz Table2-8.6:18HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 22.74 2.56 25.95 2.75 32.50 3.23 35.71 3.30 38.93 3.43 45.24 3.79 50.95 4.44 22.74 2.86 25.95 3.07 32.50 3.61...
  • Page 86 TVR Connect 380V 50/60Hz Table2-8.6:18HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 16.19 1.82 18.57 1.96 23.21 2.30 25.48 2.35 27.85 2.45 32.50 2.71 37.14 2.94 16.19 2.03 18.57 2.19 23.21 2.57...
  • Page 87 TVR Connect 380V 50/60Hz Table2-8.7:20HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 44.91 4.22 50.51 4.47 63.14 5.24 70.06 5.41 74.23 5.46 78.29 5.48 79.61 5.88 44.91 4.86 50.51 5.15 63.14 6.03...
  • Page 88 TVR Connect 380V 50/60Hz Table2-8.7:20HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 39.31 4.13 44.91 4.44 55.34 5.13 60.61 5.23 66.21 5.45 74.34 5.81 76.21 6.30 39.31 4.76 44.91 5.12 55.34 5.91...
  • Page 89 TVR Connect 380V 50/60Hz...
  • Page 90 TVR Connect 380V 50/60Hz Table2-8.7:20HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 32.73 3.51 37.44 3.79 46.78 4.43 50.73 4.47 55.34 4.65 64.68 5.17 71.15 6.01 32.73 4.05 37.44 4.36 46.78 5.11...
  • Page 91 TVR Connect 380V 50/60Hz Table2-8.7:20HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 25.48 2.49 29.10 2.68 36.34 3.13 39.96 3.21 43.59 3.34 49.96 3.63 57.65 4.43 25.48 2.87 29.10 3.09 36.34 3.61...
  • Page 92 TVR Connect 380V 50/60Hz Table2-8.7:20HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 18.23 1.75 20.75 1.87 26.02 2.20 28.55 2.25 31.19 2.34 36.34 2.59 41.50 2.81 18.23 2.01 20.75 2.16 26.02 2.54...
  • Page 93 TVR Connect 380V 50/60Hz Table2-8.8:22HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 49.33 5.15 55.47 5.46 69.35 6.39 76.94 6.60 81.52 6.67 85.98 6.68 87.43 7.69 49.33 5.86 55.47 6.20 69.35 7.27...
  • Page 94 TVR Connect 380V 50/60Hz Table2-8.8:22HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 43.18 4.93 49.33 5.31 60.78 6.12 66.57 6.24 72.72 6.50 81.64 6.94 83.69 8.05 43.18 5.61 49.33 6.03 60.78 6.96...
  • Page 95 TVR Connect 380V 50/60Hz...
  • Page 96 TVR Connect 380V 50/60Hz Table2-8.8:22HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 35.93 4.15 41.13 4.48 51.37 5.24 55.72 5.29 60.78 5.50 71.03 6.11 78.15 7.61 35.93 4.72 41.13 5.09 51.37 5.96...
  • Page 97 TVR Connect 380V 50/60Hz Table2-8.8:22HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 27.98 2.96 31.96 3.18 39.92 3.72 43.90 3.81 47.87 3.96 54.87 4.31 63.31 5.64 27.98 3.36 31.96 3.62 39.92 4.23...
  • Page 98 TVR Connect 380V 50/60Hz Table2-8.8:22HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 20.02 2.24 22.79 2.40 28.59 2.82 31.36 2.88 34.25 3.00 39.92 3.32 45.59 3.59 20.02 2.54 22.79 2.73 28.59 3.21...
  • Page 99 TVR Connect 380V 50/60Hz Table2-8.9:24HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 53.67 5.97 60.22 6.32 75.42 7.41 83.02 7.59 88.87 7.75 93.54 7.75 94.60 8.52 53.67 6.74 60.22 7.13 75.42 8.36...
  • Page 100 TVR Connect 380V 50/60Hz Table2-8.9:24HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 47.01 5.68 53.67 6.11 65.96 7.04 72.96 7.25 79.05 7.49 89.11 8.02 90.15 8.82 47.01 6.41 53.67 6.90 65.96 7.94...
  • Page 101 TVR Connect 380V 50/60Hz...
  • Page 102 TVR Connect 380V 50/60Hz Table2-8.9:24HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 39.05 4.77 44.67 5.15 54.96 5.93 60.34 6.06 65.83 6.30 76.82 6.99 84.67 8.38 39.05 5.39 44.67 5.81 54.96 6.69...
  • Page 103 TVR Connect 380V 50/60Hz Table2-8.9:24HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 30.41 3.42 34.73 3.68 43.38 4.30 47.83 4.42 52.15 4.59 59.76 5.00 68.87 6.26 30.41 3.86 34.73 4.15 43.38 4.86...
  • Page 104 TVR Connect 380V 50/60Hz Table2-8.9:24HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 21.76 2.51 24.78 2.69 30.99 3.15 34.14 3.23 37.19 3.36 43.38 3.72 49.70 4.04 21.76 2.83 24.78 3.04 30.99 3.56...
  • Page 105 TVR Connect 380V 50/60Hz Table2-8.10:26HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 59.95 7.40 68.37 7.96 85.33 9.30 94.08 9.54 97.76 9.46 101.87 9.37 104.29 10.05 59.95 8.28 68.37 8.90 85.33 10.40...
  • Page 106 TVR Connect 380V 50/60Hz Table2-8.10:26HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 52.46 7.01 59.95 7.55 74.90 8.84 82.28 9.03 89.76 9.40 97.54 9.71 99.55 10.38 52.46 7.84 59.95 8.44 74.90 9.88...
  • Page 107 TVR Connect 380V 50/60Hz...
  • Page 108 TVR Connect 380V 50/60Hz Table2-8.10:26HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 44.36 6.00 49.94 6.36 62.25 7.43 68.58 7.62 74.69 7.91 87.22 8.78 93.02 9.81 44.36 6.71 49.94 7.11 62.25 8.31...
  • Page 109 TVR Connect 380V 50/60Hz Table2-8.10:26HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 34.55 4.33 39.40 4.65 48.46 5.35 53.30 5.48 58.14 5.70 67.94 6.33 77.01 7.52 34.55 4.84 39.40 5.20 48.46 5.99...
  • Page 110 TVR Connect 380V 50/60Hz Table2-8.10:26HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 24.65 3.08 28.13 3.31 35.18 3.88 38.77 3.98 42.24 4.13 48.46 4.51 54.99 4.84 24.65 3.44 28.13 3.70 35.18 4.34...
  • Page 111 TVR Connect 380V 50/60Hz Table2-8.11:28HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 62.92 7.80 71.94 8.40 88.22 9.66 97.02 9.88 106.03 10.30 113.89 10.51 117.86 10.78 62.92 8.90 71.94 9.59 88.22 11.01 97.02...
  • Page 112 TVR Connect 380V 50/60Hz Table2-8.11:28HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 55.06 7.44 62.92 8.01 77.56 9.25 85.07 9.44 93.03 9.84 108.03 10.86 111.43 11.10 55.06 8.48 62.92 9.13 77.56 10.55...
  • Page 113 TVR Connect 380V 50/60Hz...
  • Page 114 TVR Connect 380V 50/60Hz Table2-8.11:28HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 45.81 6.27 52.38 6.75 65.50 7.91 71.35 8.02 77.45 8.30 89.98 9.17 102.99 10.39 45.81 7.15 52.38 7.71 65.50 9.03...
  • Page 115 TVR Connect 380V 50/60Hz Table2-8.11:28HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 35.62 4.49 40.77 4.85 50.97 5.68 56.00 5.80 61.16 6.04 71.00 6.67 80.03 7.45 35.62 5.13 40.77 5.53 50.97 6.48...
  • Page 116 TVR Connect 380V 50/60Hz Table2-8.11:28HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 25.42 3.01 29.06 3.24 36.44 3.80 40.07 3.89 43.70 4.05 50.97 4.49 58.23 4.86 25.42 3.43 29.06 3.69 36.44 4.34...
  • Page 117 TVR Connect 380V 50/60Hz Table2-8.12:30HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 68.12 7.75 77.85 8.35 95.55 9.60 105.17 9.83 115.13 10.26 120.52 10.21 123.80 10.76 68.12 9.04 77.85 9.73 95.55 11.19 105.17...
  • Page 118 TVR Connect 380V 50/60Hz Table2-8.12:30HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 59.68 7.37 68.23 7.94 83.83 9.14 92.15 9.35 100.59 9.74 115.13 10.59 117.83 11.12 59.68 8.60 68.23 9.26 83.83 10.66 92.15...
  • Page 119 TVR Connect 380V 50/60Hz...
  • Page 120 TVR Connect 380V 50/60Hz Table2-8.12:30HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 49.59 6.20 56.75 6.69 70.93 7.83 77.61 7.97 84.06 8.24 97.55 9.08 110.21 10.53 49.59 7.23 56.75 7.80 70.93 9.13...
  • Page 121 TVR Connect 380V 50/60Hz Table2-8.12:30HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 38.58 4.46 44.09 4.80 55.10 5.62 60.73 5.76 66.24 5.99 77.14 6.63 86.76 7.65 38.58 5.20 44.09 5.59 55.10 6.55...
  • Page 122 TVR Connect 380V 50/60Hz Table2-8.12:30HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 27.55 3.10 31.54 3.34 39.40 3.91 43.38 4.01 47.25 4.16 55.10 4.61 63.08 5.00 27.55 3.61 31.54 3.89 39.40 4.56...
  • Page 123 TVR Connect 380V 50/60Hz Table2-8.13:32HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 72.20 9.44 82.51 10.16 101.17 11.68 111.24 11.95 121.31 12.42 128.19 12.48 131.25 13.11 72.20 10.80 82.51 11.63 101.17 13.36 111.24...
  • Page 124 TVR Connect 380V 50/60Hz Table2-8.13:32HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 63.24 8.94 72.20 9.61 88.64 11.06 97.48 11.32 106.82 11.83 122.41 12.88 124.87 13.49 63.24 10.23 72.20 11.00 88.64 12.66 97.48...
  • Page 125 TVR Connect 380V 50/60Hz...
  • Page 126 TVR Connect 380V 50/60Hz Table2-8.13:32HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 52.56 7.52 60.04 8.10 75.14 9.49 82.64 9.72 88.52 9.93 103.62 11.04 117.38 12.84 52.56 8.61 60.04 9.27 75.14 10.86...
  • Page 127 TVR Connect 380V 50/60Hz Table2-8.13:32HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 40.89 5.44 46.78 5.86 58.44 6.86 64.21 7.02 70.11 7.31 81.77 8.10 91.84 9.34 40.89 6.23 46.78 6.71 58.44 7.85...
  • Page 128 TVR Connect 380V 50/60Hz Table2-8.13:32HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 29.23 3.83 33.40 4.12 41.74 4.82 45.92 4.94 50.09 5.13 58.44 5.69 66.79 6.16 29.23 4.38 33.40 4.71 41.74 5.52...
  • Page 129 TVR Connect 380V 50/60Hz Table2-8.14:34HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 76.26 9.09 85.80 9.63 107.06 11.26 117.69 11.52 128.45 11.99 136.27 12.09 135.49 12.24 76.26 10.68 85.80 11.32 107.06 13.23 117.69...
  • Page 130 TVR Connect 380V 50/60Hz Table2-8.14:34HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 66.85 8.59 76.38 9.25 93.86 10.65 103.40 10.92 112.43 11.32 127.47 12.20 130.01 12.66 66.85 10.09 76.38 10.87 93.86 12.51 103.40...
  • Page 131 TVR Connect 380V 50/60Hz...
  • Page 132 TVR Connect 380V 50/60Hz Table2-8.14:34HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 55.61 7.23 63.56 7.79 79.44 9.12 85.92 9.18 94.35 9.61 109.14 10.57 120.86 11.92 55.61 8.50 63.56 9.15 79.44 10.72...
  • Page 133 TVR Connect 380V 50/60Hz Table2-8.14:34HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 43.26 5.24 49.37 5.64 61.71 6.60 67.95 6.76 74.06 7.03 85.06 7.67 96.71 8.88 43.26 6.16 49.37 6.62 61.71 7.76...
  • Page 134 TVR Connect 380V 50/60Hz Table2-8.14:34HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 30.86 3.66 35.25 3.94 44.03 4.61 48.42 4.72 52.81 4.90 61.58 5.43 70.49 5.89 30.86 4.30 35.25 4.63 44.03 5.41...
  • Page 135 TVR Connect 380V 50/60Hz Table2-8.15:36HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 80.50 10.80 91.00 11.50 113.72 13.46 124.95 13.77 136.07 14.30 143.97 14.38 146.81 14.86 80.50 12.45 91.00 13.26 113.72 15.53 124.95...
  • Page 136 TVR Connect 380V 50/60Hz Table2-8.15:36HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 70.87 10.24 80.63 10.98 99.64 12.71 109.77 13.03 119.77 13.56 137.55 14.80 140.63 15.33 70.87 11.81 80.63 12.66 99.64 14.66 109.77...
  • Page 137 TVR Connect 380V 50/60Hz...
  • Page 138 TVR Connect 380V 50/60Hz Table2-8.15:36HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 59.02 8.64 67.42 9.30 82.85 10.71 91.25 10.97 99.89 11.45 116.31 12.68 131.74 14.55 59.02 9.97 67.42 10.73 82.85 12.35...
  • Page 139 TVR Connect 380V 50/60Hz Table2-8.15:36HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 45.93 6.29 52.48 6.77 65.56 7.92 72.11 8.11 78.65 8.43 90.38 9.21 103.22 10.66 45.93 7.25 52.48 7.80 65.56 9.13...
  • Page 140 TVR Connect 380V 50/60Hz Table2-8.15:36HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 32.72 4.38 37.41 4.72 46.80 5.53 51.49 5.67 56.18 5.90 65.56 6.54 74.95 7.08 32.72 5.06 37.41 5.45 46.80 6.38...
  • Page 141 TVR Connect 380V 50/60Hz Table2-8.16:38HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 84.49 11.83 95.50 12.60 119.35 14.75 131.14 15.08 142.81 15.66 151.10 15.75 161.61 13.65 84.49 13.61 95.50 14.50 119.35 16.97 131.14...
  • Page 142 TVR Connect 380V 50/60Hz Table2-8.16:38HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 74.38 11.20 84.62 12.01 104.57 13.90 115.20 14.25 125.70 14.83 144.36 16.19 154.80 14.06 74.38 12.89 84.62 13.82 104.57 16.00 115.20...
  • Page 143 TVR Connect 380V 50/60Hz...
  • Page 144 TVR Connect 380V 50/60Hz Table2-8.16:38HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 61.49 9.35 70.24 10.07 86.31 11.59 95.07 11.88 104.07 12.40 121.17 13.72 143.96 13.21 61.49 10.76 70.24 11.58 86.31 13.34...
  • Page 145 TVR Connect 380V 50/60Hz Table2-8.16:38HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 47.85 6.76 54.67 7.28 68.30 8.52 75.13 8.72 81.94 9.07 94.16 9.91 112.79 9.61 47.85 7.78 54.67 8.38 68.30 9.80...
  • Page 146 TVR Connect 380V 50/60Hz Table2-8.16:38HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 35.75 3.92 40.88 4.22 51.14 4.95 56.26 5.07 61.39 5.27 71.64 5.85 81.90 6.33 35.75 4.51 40.88 4.86 51.14 5.69...
  • Page 147 TVR Connect 380V 50/60Hz Table2-8.17:40HP cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 89.27 12.70 100.91 13.53 126.11 15.83 138.56 16.19 150.89 16.81 159.65 16.91 162.80 13.82 89.27 14.68 100.91 15.64 126.11 18.31 138.56...
  • Page 148 TVR Connect 380V 50/60Hz Table2-8.17:40HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 78.59 12.00 89.41 12.86 110.49 14.89 121.73 15.27 132.81 15.89 152.53 17.34 155.95 14.21 78.59 13.87 89.41 14.87 110.49 17.22 121.73...
  • Page 149 TVR Connect 380V 50/60Hz...
  • Page 150 TVR Connect 380V 50/60Hz Table2-8.17:40HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 65.45 10.09 74.76 10.86 91.87 12.50 101.19 12.81 110.77 13.38 128.98 14.80 146.09 13.43 65.45 11.66 74.76 12.55 91.87 14.45 101.19...
  • Page 151 TVR Connect 380V 50/60Hz Table2-8.17:40HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 50.93 7.31 58.20 7.86 72.70 9.20 79.96 9.42 87.22 9.80 100.22 10.70 114.46 9.79 50.93 8.45 58.20 9.09 72.70 10.64...
  • Page 152 TVR Connect 380V 50/60Hz Table2-8.17:40HP cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 36.28 4.00 41.48 4.31 51.90 5.05 57.10 5.17 62.30 5.38 72.70 5.97 83.11 6.46 36.28 4.63 41.48 4.98 51.90 5.84...
  • Page 153: Heating Capacity Tables

    TVR Connect 380V 50/60Hz 8.2 Heating Capacity Tables Table2-8.18:8HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 19.02 4.51 18.65 4.66 18.29 4.81 18.10 4.92 17.92 4.82 17.56 4.50...
  • Page 154 TVR Connect 380V 50/60Hz Table2-8.18:8HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 17.39 4.42 17.36 4.68 16.51 4.38 16.35 4.25 16.18 4.09 15.85 3.85 -25.0 -25.4 18.15 4.74...
  • Page 155 TVR Connect 380V 50/60Hz Table2-8.18:8HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 15.84 4.20 15.07 3.83 14.77 3.64 14.63 3.60 14.48 3.55 14.18 3.68 -25.0 -25.4 16.47 4.63...
  • Page 156 TVR Connect 380V 50/60Hz Table2-8.18:8HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 12.13 3.03 11.72 2.94 11.49 3.09 11.38 3.15 11.26 3.20 11.03 3.29 -25.0 -25.4 12.97 3.63...
  • Page 157 TVR Connect 380V 50/60Hz Table2-8.18:8HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 9.13 2.69 8.89 2.72 8.65 2.79 8.49 2.79 8.32 2.78 7.88 2.72 -25.0 -25.4 9.40 2.79...
  • Page 158 TVR Connect 380V 50/60Hz Table2-8.19:10HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 22.19 5.10 21.76 5.28 21.34 5.46 21.12 5.54 20.91 5.67 20.48 5.48 -25.0 -25.4 22.19 5.23...
  • Page 159 TVR Connect 380V 50/60Hz Table2-8.19:10HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 20.04 4.90 19.65 5.08 19.42 5.31 19.07 5.25 18.88 5.04 18.50 4.79 -25.0 -25.4 20.83 5.23...
  • Page 160 TVR Connect 380V 50/60Hz Table2-8.19:10HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 18.54 4.96 17.77 4.81 17.24 4.46 17.06 4.29 16.89 4.17 16.55 4.17 -25.0 -25.4 19.09 5.25...
  • Page 161 TVR Connect 380V 50/60Hz Table2-8.19:10HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 14.37 3.60 13.81 3.53 13.41 3.40 13.27 3.45 13.14 3.58 12.87 3.75 -25.0 -25.4 15.20 4.34...
  • Page 162 TVR Connect 380V 50/60Hz Table2-8.19:10HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 10.70 3.03 10.42 3.07 10.12 3.10 9.96 3.13 9.80 3.17 9.49 3.22 -25.0 -25.4 11.04 3.21...
  • Page 163 TVR Connect 380V 50/60Hz Table2-8.20:12HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 26.42 5.61 25.91 5.76 25.40 5.90 25.15 5.99 24.89 5.92 24.38 5.76 -25.0 -25.4 26.42 5.69...
  • Page 164 TVR Connect 380V 50/60Hz Table2-8.20:12HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 23.85 5.37 23.40 5.51 22.94 5.48 22.71 5.49 22.48 5.44 22.02 5.36 -25.0 -25.4 23.85 5.43...
  • Page 165 TVR Connect 380V 50/60Hz Table2-8.20:12HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 21.34 5.09 20.93 5.08 20.52 5.08 20.31 5.00 20.11 4.96 19.70 4.99 -25.0 -25.4 21.34 5.18...
  • Page 166 TVR Connect 380V 50/60Hz Table2-8.20:12HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 16.60 4.04 16.28 4.04 15.96 4.05 15.80 4.01 15.64 4.03 15.32 4.05 -25.0 -25.4 17.23 4.28...
  • Page 167 TVR Connect 380V 50/60Hz Table2-8.20:12HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 12.26 3.17 11.63 3.02 11.40 3.06 11.29 3.08 11.17 3.51 10.94 11.26 -25.0 -25.4 12.68 3.30...
  • Page 168 TVR Connect 380V 50/60Hz Table2-8.21:14HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 31.70 7.62 31.09 7.87 30.48 8.11 30.17 8.25 29.87 8.34 29.26 8.60 -25.0 -25.4 31.70 7.69...
  • Page 169 TVR Connect 380V 50/60Hz Table2-8.21:14HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 28.63 7.26 28.07 7.49 27.52 7.73 27.25 7.83 26.97 7.96 26.42 8.18 -25.0 -25.4 28.63 7.31...
  • Page 170 TVR Connect 380V 50/60Hz Table2-8.21:14HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 25.61 6.93 25.12 7.15 24.62 7.33 24.38 7.45 24.13 7.55 23.64 7.63 -25.0 -25.4 25.61 6.98...
  • Page 171 TVR Connect 380V 50/60Hz Table2-8.21:14HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 20.57 6.07 20.27 6.30 19.87 6.37 19.15 6.00 18.77 5.74 18.39 5.68 -25.0 -25.4 21.20 6.34...
  • Page 172 TVR Connect 380V 50/60Hz Table2-8.21:14HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 15.42 4.91 15.00 4.80 14.55 4.67 14.32 4.60 14.10 4.56 13.60 4.40 -25.0 -25.4 15.83 5.16...
  • Page 173 TVR Connect 380V 50/60Hz Table2-8.22:16HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 35.22 8.16 34.54 8.43 33.87 8.67 33.53 8.81 33.19 8.92 32.51 9.21 -25.0 -25.4 35.22 8.22...
  • Page 174 TVR Connect 380V 50/60Hz Table2-8.22:16HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 31.81 7.76 31.19 8.01 30.58 8.26 30.28 8.36 29.97 8.50 29.36 8.75 -25.0 -25.4 31.81 7.82...
  • Page 175 TVR Connect 380V 50/60Hz Table2-8.22:16HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 28.45 7.41 27.91 7.64 27.36 7.85 27.09 7.98 26.81 8.09 26.27 8.15 -25.0 -25.4 28.45 7.47...
  • Page 176 TVR Connect 380V 50/60Hz Table2-8.22:16HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 22.37 6.37 22.00 6.57 21.57 6.66 21.07 6.34 20.85 6.14 20.43 6.12 -25.0 -25.4 23.35 6.73...
  • Page 177 TVR Connect 380V 50/60Hz Table2-8.22:16HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 17.00 5.19 16.53 5.09 16.02 4.95 15.77 4.87 15.51 4.82 14.78 4.59 -25.0 -25.4 17.47 5.48...
  • Page 178 TVR Connect 380V 50/60Hz Table2-8.23:18HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 39.45 9.24 38.69 9.56 37.93 9.83 37.55 9.99 37.17 10.12 36.41 10.41 -25.0 -25.4 39.45 9.34...
  • Page 179 TVR Connect 380V 50/60Hz Table2-8.23:18HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 35.62 8.79 34.94 9.09 34.25 9.38 33.91 9.48 33.57 9.58 32.88 9.88 -25.0 -25.4 35.62 8.88...
  • Page 180 TVR Connect 380V 50/60Hz Table2-8.23:18HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 31.87 8.39 31.26 8.61 30.64 8.86 30.34 8.99 30.03 9.15 29.42 9.37 -25.0 -25.4 31.87 8.46...
  • Page 181 TVR Connect 380V 50/60Hz Table2-8.23:18HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 25.06 7.15 24.64 7.37 24.63 7.73 24.47 7.86 23.63 7.54 22.88 7.36 -25.0 -25.4 26.17 7.56...
  • Page 182 TVR Connect 380V 50/60Hz Table2-8.23:18HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 19.40 6.28 18.99 6.32 18.51 6.19 18.21 6.07 17.93 5.99 17.33 5.76 -25.0 -25.4 19.79 6.45...
  • Page 183 TVR Connect 380V 50/60Hz Table2-8.24:20HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 44.38 10.23 43.52 10.57 42.67 10.91 42.24 11.10 41.82 11.30 40.96 11.63 -25.0 -25.4 44.38 10.40...
  • Page 184 TVR Connect 380V 50/60Hz Table2-8.24:20HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 40.08 9.77 39.30 10.10 38.53 10.41 38.15 10.61 37.76 10.74 36.99 11.06 -25.0 -25.4 40.08 9.91...
  • Page 185 TVR Connect 380V 50/60Hz Table2-8.24:20HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 35.85 9.31 35.16 9.60 34.47 9.92 34.13 10.09 33.78 10.25 33.09 10.54 -25.0 -25.4 35.85 9.45...
  • Page 186 TVR Connect 380V 50/60Hz Table2-8.24:20HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 28.23 8.00 28.17 8.39 27.77 8.74 27.50 8.78 26.52 8.31 25.74 7.99 -25.0 -25.4 29.50 8.50...
  • Page 187 TVR Connect 380V 50/60Hz Table2-8.24:20HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 22.16 7.15 21.59 7.04 21.00 6.90 20.70 6.84 20.38 6.73 19.75 6.51 -25.0 -25.4 22.57 7.37...
  • Page 188 TVR Connect 380V 50/60Hz Table2-8.25:22HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 48.60 11.78 47.67 12.18 46.73 12.59 46.27 12.79 45.80 13.01 44.87 13.41 -25.0 -25.4 48.60 11.97...
  • Page 189 TVR Connect 380V 50/60Hz Table2-8.25:22HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 43.89 11.21 43.05 11.62 42.20 11.99 41.78 12.21 41.36 12.36 40.52 12.75 -25.0 -25.4 43.89 11.39...
  • Page 190 TVR Connect 380V 50/60Hz Table2-8.25:22HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 39.27 10.73 38.51 11.07 37.76 11.43 37.38 11.59 37.00 11.81 36.25 12.14 -25.0 -25.4 39.27 10.88...
  • Page 191 TVR Connect 380V 50/60Hz Table2-8.25:22HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 30.92 9.22 30.86 9.66 30.42 10.06 30.12 10.10 29.05 9.57 28.19 9.21 -25.0 -25.4 32.31 9.80...
  • Page 192 TVR Connect 380V 50/60Hz Table2-8.25:22HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 23.88 8.03 23.25 7.90 22.60 7.75 22.25 7.67 21.90 7.54 21.19 7.29 -25.0 -25.4 24.38 8.30...
  • Page 193 TVR Connect 380V 50/60Hz Table2-8.26:24HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 52.83 12.91 51.81 13.36 50.80 13.80 50.29 14.02 49.78 14.27 48.77 14.71 -25.0 -25.4 52.83 13.13...
  • Page 194 TVR Connect 380V 50/60Hz Table2-8.26:24HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 47.71 12.29 46.79 12.74 45.87 13.15 45.41 13.39 44.96 13.55 44.04 13.98 -25.0 -25.4 47.71 12.49...
  • Page 195 TVR Connect 380V 50/60Hz Table2-8.26:24HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 42.68 11.76 41.86 12.13 41.04 12.53 40.63 12.71 40.22 12.94 39.40 13.31 -25.0 -25.4 42.68 11.93...
  • Page 196 TVR Connect 380V 50/60Hz Table2-8.26:24HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 33.60 10.11 33.54 10.59 33.06 11.03 32.73 11.07 31.57 10.50 30.64 10.09 -25.0 -25.4 35.12 10.74...
  • Page 197 TVR Connect 380V 50/60Hz Table2-8.26:24HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 25.54 9.11 24.84 8.96 24.12 8.77 23.74 8.68 23.35 8.53 22.56 8.24 -25.0 -25.4 26.12 9.43...
  • Page 198 TVR Connect 380V 50/60Hz Table2-8.27:26HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 57.41 14.37 56.30 14.81 55.20 15.21 54.65 15.50 54.10 15.69 52.99 16.09 -25.0 -25.4 57.41 14.49...
  • Page 199 TVR Connect 380V 50/60Hz Table2-8.27:26HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 51.84 13.68 50.85 14.11 49.85 14.52 49.35 14.71 48.85 14.92 47.86 15.28 -25.0 -25.4 51.84 13.78...
  • Page 200 TVR Connect 380V 50/60Hz Table2-8.27:26HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 46.38 13.04 45.49 13.41 44.60 13.79 44.15 13.97 43.70 14.18 42.81 14.50 -25.0 -25.4 46.38 13.12...
  • Page 201 TVR Connect 380V 50/60Hz Table2-8.27:26HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 36.07 11.01 35.75 11.41 35.15 11.75 35.38 12.10 34.43 11.94 33.30 11.48 -25.0 -25.4 37.86 11.65...
  • Page 202 TVR Connect 380V 50/60Hz Table2-8.27:26HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 28.49 9.92 27.71 9.77 26.92 9.61 26.52 9.51 26.11 9.44 25.29 9.23 -25.0 -25.4 29.08 10.27...
  • Page 203 TVR Connect 380V 50/60Hz Table2-8.28:28HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 61.64 16.54 60.45 17.05 59.26 17.56 58.67 17.83 58.08 18.06 56.89 18.54 -25.0 -25.4 61.64 16.69...
  • Page 204 TVR Connect 380V 50/60Hz Table2-8.28:28HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 55.66 15.76 54.59 16.24 53.52 16.68 52.98 16.95 52.45 17.16 51.38 17.59 -25.0 -25.4 55.66 15.87...
  • Page 205 TVR Connect 380V 50/60Hz Table2-8.28:28HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 49.80 14.98 48.84 15.47 47.88 15.87 47.40 16.09 46.92 16.32 45.96 16.69 -25.0 -25.4 49.80 15.09...
  • Page 206 TVR Connect 380V 50/60Hz Table2-8.28:28HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 38.73 12.69 38.38 13.15 37.74 13.53 37.98 13.93 36.96 13.74 35.75 13.21 -25.0 -25.4 40.65 13.42...
  • Page 207 TVR Connect 380V 50/60Hz Table2-8.28:28HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 30.19 11.17 29.35 10.99 28.49 10.81 28.05 10.69 27.60 10.60 26.71 10.36 -25.0 -25.4 30.87 11.58...
  • Page 208 TVR Connect 380V 50/60Hz Table2-8.29:30HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 66.92 19.24 65.63 19.80 64.34 20.37 63.70 20.70 63.06 20.97 61.77 21.44 -25.0 -25.4 66.92 19.36...
  • Page 209 TVR Connect 380V 50/60Hz Table2-8.29:30HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 60.43 18.29 59.27 18.77 58.11 19.34 57.53 19.57 56.94 19.84 55.78 20.32 -25.0 -25.4 60.43 18.39...
  • Page 210 TVR Connect 380V 50/60Hz Table2-8.29:30HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 54.06 17.34 53.02 17.89 51.98 18.32 51.46 18.54 50.94 18.80 49.90 18.54 -25.0 -25.4 54.06 17.46...
  • Page 211 TVR Connect 380V 50/60Hz Table2-8.29:30HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 42.64 14.84 42.64 15.52 40.92 15.23 40.03 14.99 39.62 14.97 38.81 14.90 -25.0 -25.4 44.62 15.68...
  • Page 212 TVR Connect 380V 50/60Hz Table2-8.29:30HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 32.49 12.24 31.51 11.98 30.67 11.91 30.28 11.90 29.91 11.94 29.15 12.04 -25.0 -25.4 33.31 12.71...
  • Page 213 TVR Connect 380V 50/60Hz Table2-8.30:32HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 70.44 20.64 69.09 21.24 67.73 21.87 67.05 22.11 66.38 22.40 65.02 23.01 -25.0 -25.4 70.44 20.78...
  • Page 214 TVR Connect 380V 50/60Hz Table2-8.30:32HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 63.61 19.60 62.39 20.13 61.16 20.70 60.55 20.99 59.94 21.24 58.72 21.77 -25.0 -25.4 63.61 19.73...
  • Page 215 TVR Connect 380V 50/60Hz Table2-8.30:32HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 56.91 18.62 55.81 19.17 54.72 19.67 54.17 19.91 53.63 20.15 52.53 19.95 -25.0 -25.4 56.91 18.74...
  • Page 216 TVR Connect 380V 50/60Hz Table2-8.30:32HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 44.71 15.84 43.98 16.31 43.01 16.41 42.13 16.16 41.71 16.10 40.86 15.93 -25.0 -25.4 46.68 16.69...
  • Page 217 TVR Connect 380V 50/60Hz Table2-8.30:32HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 34.11 13.11 33.07 12.80 32.06 12.59 31.65 12.58 31.23 12.61 30.43 12.71 -25.0 -25.4 34.99 13.63...
  • Page 218 TVR Connect 380V 50/60Hz Table2-8.31:34HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 74.67 22.46 73.23 23.23 71.80 23.98 71.08 24.29 70.36 24.64 68.92 25.36 -25.0 -25.4 74.67 22.84...
  • Page 219 TVR Connect 380V 50/60Hz Table2-8.31:34HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 67.43 21.42 66.13 22.10 64.83 22.71 64.19 23.09 63.54 23.40 62.24 24.07 -25.0 -25.4 67.43 21.72...
  • Page 220 TVR Connect 380V 50/60Hz Table2-8.31:34HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 60.32 20.37 59.16 20.99 58.00 21.63 57.42 21.96 56.84 22.27 55.68 22.30 -25.0 -25.4 60.32 20.66...
  • Page 221 TVR Connect 380V 50/60Hz Table2-8.31:34HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 48.47 17.77 47.81 18.39 47.02 18.86 46.10 18.47 44.67 17.90 43.31 17.03 -25.0 -25.4 49.95 18.61...
  • Page 222 TVR Connect 380V 50/60Hz Table2-8.31:34HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 36.73 14.84 35.72 14.54 34.66 14.18 34.11 13.96 33.57 13.81 32.40 13.28 -25.0 -25.4 37.46 15.26...
  • Page 223 TVR Connect 380V 50/60Hz Table2-8.32:36HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 78.89 24.26 77.38 25.03 75.86 25.85 75.10 26.18 74.34 26.57 72.82 27.30 -25.0 -25.4 78.89 24.61...
  • Page 224 TVR Connect 380V 50/60Hz Table2-8.32:36HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 71.24 23.09 69.87 23.78 68.50 24.45 67.82 24.81 67.13 25.14 65.76 25.86 -25.0 -25.4 71.24 23.38...
  • Page 225 TVR Connect 380V 50/60Hz Table2-8.32:36HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 63.74 21.97 62.51 22.59 61.29 23.26 60.67 23.54 60.06 23.91 58.83 23.49 -25.0 -25.4 63.74 22.21...
  • Page 226 TVR Connect 380V 50/60Hz Table2-8.32:36HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 50.15 18.74 49.34 19.31 48.26 19.43 47.61 19.29 46.71 18.98 45.76 18.77 -25.0 -25.4 52.39 19.81...
  • Page 227 TVR Connect 380V 50/60Hz Table2-8.32:36HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 38.40 15.48 37.35 15.20 36.56 15.40 36.17 15.47 35.63 15.35 34.42 14.94 -25.0 -25.4 39.31 16.08...
  • Page 228 TVR Connect 380V 50/60Hz Table2-8.33:38HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 83.82 26.74 82.21 27.58 80.60 28.43 79.79 28.82 78.99 29.25 77.38 30.06 -25.0 -25.4 83.82 27.11...
  • Page 229 TVR Connect 380V 50/60Hz Table2-8.33:38HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 75.70 25.43 74.24 26.20 72.79 26.94 72.06 27.33 71.33 27.68 69.87 28.45 -25.0 -25.4 75.70 25.74...
  • Page 230 TVR Connect 380V 50/60Hz Table2-8.33:38HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 67.72 24.17 66.42 24.90 65.12 25.58 64.47 25.94 63.81 26.30 62.51 25.87 -25.0 -25.4 67.72 24.45...
  • Page 231 TVR Connect 380V 50/60Hz Table2-8.33:38HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 53.28 20.61 52.42 21.24 51.28 21.39 50.59 21.23 49.63 20.89 48.62 20.68 -25.0 -25.4 55.66 21.80...
  • Page 232 TVR Connect 380V 50/60Hz Table2-8.33:38HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 40.26 16.83 39.13 16.51 38.29 16.72 37.89 16.80 37.31 16.66 35.99 16.20 -25.0 -25.4 41.29 17.51...
  • Page 233 TVR Connect 380V 50/60Hz Table2-8.34:40HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 86.99 28.80 85.32 29.72 83.65 30.61 82.81 31.05 81.98 31.47 80.30 32.36 -25.0 -25.4 86.99 29.20...
  • Page 234 TVR Connect 380V 50/60Hz Table2-8.34:40HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 78.56 27.38 77.05 28.19 75.54 29.00 74.78 29.42 74.03 29.81 72.52 30.63 -25.0 -25.4 78.56 27.72...
  • Page 235 TVR Connect 380V 50/60Hz Table2-8.34:40HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 70.28 26.03 68.93 26.81 67.58 27.56 66.90 27.95 66.23 28.33 64.88 27.87 -25.0 -25.4 70.28 26.33...
  • Page 236 TVR Connect 380V 50/60Hz Table2-8.34:40HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 55.30 22.21 54.41 22.88 53.22 23.05 52.50 22.84 51.51 22.48 50.46 22.27 -25.0 -25.4 57.77 23.48...
  • Page 237 TVR Connect 380V 50/60Hz Table2-8.34:40HP heating capacity(continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -30.0 -30.5 41.37 17.65 40.19 17.31 39.32 17.53 38.91 17.61 38.30 17.46 36.48 16.76 -25.0 -25.4 42.49 18.40...
  • Page 238 TVR Connect 380V 50/60Hz 8.3 Capacity Correction Factors for Piping Length and Level Difference Figure 2-8.1: Rate of change in cooling capacity 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 -100 -110 Figure 2-8.2: Rate of change in heating capacity...
  • Page 239 TVR Connect 380V 50/60Hz 8.4 Capacity Correction Factors for Frost Accumulation The heating capacity tables do not take account of the reduction in capacity when frost has accumulated or while the defrosting operation is in progress. If snow has accumulated against the outside surface of the outdoor unit heat exchanger heating capacity is reduced.
  • Page 240: Operating Limits

    TVR Connect 380V 50/60Hz 9 Operating Limits Figure 2-9.1: Cooling operating limits Figure 2-9.2: Heating operating limits 10 15 20 25 30 35 10 15 20 25 30 35 Indoor temperature ( C DB) Indoor temperature ( C DB) Notes: These figures assume the following operating conditions: ▪...
  • Page 241: Sound Levels

    TVR Connect 380V 50/60Hz 10 Sound Levels 10.1 Overall Table 2-10.1: Sound pressure level Model dB(A) Model dB(A) Model dB(A) 46HP 84HP 10HP 48HP 86HP 12HP 50HP 88HP 14HP 52HP 90HP 16HP 54HP 92HP 18HP 56HP 94HP 20HP 58HP 96HP 22HP 60HP 98HP...
  • Page 242 TVR Connect 380V 50/60Hz 10.2 Octave Band Levels Figure 2-10.2: 8HP octave band level Figure 2-10.3: 10HP octave band level NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 NC-20 NC-20 Octave band center frequency (Hz) Octave band center frequency (Hz) Figure 2-10.4: 12HP octave band level Figure 2-10.5: 14HP octave band level NC-70...
  • Page 243 TVR Connect 380V 50/60Hz Figure 2-10.8: 20HP octave band level Figure 2-10.9: 22HP octave band level NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 NC-20 NC-20 Octave band center frequency (Hz) Octave band center frequency (Hz) Figure 2-10.10: 24HP octave band level Figure 2-10.11: 26HP octave band level NC-70 NC-70...
  • Page 244 TVR Connect 380V 50/60Hz Figure 2-10.14: 32HP octave band level Figure 2-10.15: 34HP octave band level NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 Octave band center frequency (Hz) Octave band center frequency (Hz) Figure 2-10.14: 36HP octave band level Figure 2-10.15: 38HP octave band level NC-70 NC-70 NC-60...
  • Page 245: Standard Accessories

    TVR Connect 380V 50/60Hz 11 Accessories 11.1 Standard Accessories Table 2-11.1: Standard accessories Name Shape Quantity Function Installation and owner's manual L-shaped connection pipe Connecting gas and liquid pipes Matched resistor Enhances communication stability Wrench Removing side plate L-shaped pipe Figure 2-11.1: L-shaped pipe size (unit: mm) Table 2-11.2: L-shaped pipe size (unit: mm) 8-12HP...
  • Page 246: Installation

    TVR CONNECT 380V 50/60Hz Part 3 System Design and Installation 1 Preface to Part 3 ..................233 2 Unit Placement and Installation ............. 234 3 Outdoor Unit Ducting and Shielding ............238 4 Refrigerant Piping Design ............... 242 5 Refrigerant Piping Installation ..............253 6 Drain Piping ...................
  • Page 247: Preface To Part 3

    1.1 Notes for Installers Boxes The information contained in this Engineering Data Book may primarily be of use during the system design stage of a Trane TVR CONNECT Series project. Additional important information which may primarily be of use during field installation has been placed in boxes, such as the example below, titled “Notes for installers”.
  • Page 248: Unit Placement And Installation

    TVR CONNECT 380V 50/60Hz 2 Unit Placement and Installation 2.1 Outdoor Units 2.1.1 Placement considerations Placement of outdoor units should take account of the following considerations: ▪ Air conditioners should not be exposed to direct radiation from a high-temperature heat source. ▪...
  • Page 249 TVR CONNECT 380V 50/60Hz 2.1.3 Master and slave unit positioning In systems with multiple outdoor units, the units should be placed in order from largest capacity unit to smallest capacity unit. The largest capacity unit must be placed on the first branch, and be set as the master unit, while the others should be set as slave units.
  • Page 250 TVR CONNECT 380V 50/60Hz Figure 3-2.5: Outdoor unit typical concrete base structure design (unit: mm) Minimum Φ8 Expansion bolt width 100mm Drain size 100mmx20mm Depends on the positioning size of the unit Figure 3-2.6: Expansion bolt positioning Table 3-2.1: Expansion bolt spacings (unit: mm) Dimension 8-18HP 20-24HP...
  • Page 251: Indoor Units

    TVR CONNECT 380V 50/60Hz Figure 3-2.7: Hoisting Figure 3-2.8: 8-18HP Center of gravity Sling belt REAR FRONT CENTER OF GRAVITY Figure 3-2.9: 20-40HP Center of gravity REAR CENTER OF FRONT GRAVITY Dimension 8-18HP 20-24HP 26-40HP 1340 1880 2.2 Indoor Units 2.2.1 Placement considerations Placement of indoor units should take account of the following considerations: ▪...
  • Page 252: Outdoor Unit Ducting And Shielding

    TVR CONNECT 380V 50/60Hz 3 Outdoor Unit Ducting and Shielding 3.1 Ducting Requirements Depending on the height of adjacent walls relative to the height of the units, ducting may be required to ensure proper air discharge. In the situation depicted in Figure 3-3.1, when the space over the unit is less than 1500mm, ducting is required to ensure proper air discharge.
  • Page 253 TVR CONNECT 380V 50/60Hz 3.3 Transverse Ducting Figure 3-3.2: Transverse ducting (unit: mm) Table 3-3.1: Duct dimensions (unit: mm) Table 3-3.2: External static pressure 8-18HP 20-24HP 26-40HP ESP (Pa) Remarks 1290 1680 Factory default 770≤B≤800 770≤B≤800 770≤B≤800 0 – 20 Remove steel mesh and connect to duct <...
  • Page 254: Fan Performance

    TVR CONNECT 380V 50/60Hz 3.5 Fan Performance The default external static pressure of outdoor units’ air outlets is zero. With the steel mesh cover removed the external static pressure is 20Pa. Static pressure exceeds 20Pa needs to be customized. Figure 3-3.9: 8-12HP units fan performance Figure 3-3.10: 14-18HP units fan performance 120Pa 100Pa...
  • Page 255 TVR CONNECT 380V 50/60Hz Figure 3-3.11: 38-40HP units fan performance 120Pa 100Pa 80Pa 60Pa 40Pa 20Pa 22000(rated) 21400 21600 21800 22000 22200 22400 Air flow (m3/h)  Notes for installers ▪ Before installing outdoor unit ducting, be sure to remove the unit’s steel mesh cover, otherwise airflow will be adversely affected.
  • Page 256: Refrigerant Piping Design

    TVR CONNECT 380V 50/60Hz 3.6 Snow Shielding In areas of high snowfall, snow shields should be installed on air inlets and outlets to prevent snow from entering the units. Additionally, the foundation or base height of ODU is required to be the expected maximum snowfall thickness h0 + 300mm, preventing the snow from exceeding the bottom of the unit.
  • Page 257 TVR CONNECT 380V 50/60Hz 4.3 Permitted Piping Lengths and Level Differences The piping length and level difference requirements that apply are summarized in Table 3-4.3 and are fully described as follows (refer to Figure 3-4.2): 1. Requirement 1: The total length of piping in one refrigerant system should not exceed 1100m. When calculating the total length of piping, the actual length of the indoor main pipes (the piping between the first indoor branch joint and all other indoor branch joints, L to L...
  • Page 258 TVR CONNECT 380V 50/60Hz Figure 3-4.2: Permitted refrigerant piping lengths and level differences Legend Main pipe to L Indoor main pipes a to k Indoor auxiliary pipes Figures in parentheses A to J Indoor branch joints indicate indoor unit capacity indexes. L, M Outdoor branch joints g1 to g3, G...
  • Page 259 TVR CONNECT 380V 50/60Hz 4.4 Selecting Piping Diameters Tables 3-4.5 to 3-4.9, below, specify the required pipe diameters for the indoor and outdoor piping. The main pipe (L ) and first indoor branch joint (A) should be sized according to 3-4.5. Figure 3-4.3: Selecting piping diameters Legend Main pipe...
  • Page 260 TVR CONNECT 380V 50/60Hz Table 3-4.6: Indoor main pipes (L to L ) and indoor branch joint kits Total capacity indexes of indoor units Gas pipe (mm) Liquid pipe (mm) Branch joint kit Capacity indexes < 168 Φ15.9 Φ9.52 TRDK056HP 168 ≤...
  • Page 261 TVR CONNECT 380V 50/60Hz Table 3-4.0: Outdoor branch joint kits (L to M) Table 3-4.10: Indoor auxiliary pipes (a to k) No. of Outdoor unit Capacity of indoor Branch joint kit Gas pipe (mm) Liquid pipe (mm) outdoor units capacity unit (kW) <...
  • Page 262 TVR CONNECT 380V 50/60Hz ▪ The indoor units (N1 to N5) downstream of indoor branch B have total capacity of 16 x 5=80kW. Refer to Table 3-4.6. Indoor main pipe L2 is Φ31.8/Φ19.1 Indoor branch joint B is TRDK225HP. ▪ The indoor units (N10 and N11) downstream of indoor branch J have total capacity of 5.6+2.8= 8.4 kW. Refer to Table 3-4.6.
  • Page 263 TVR CONNECT 380V 50/60Hz Table 3-4.9: Indoor branch joint dimensions (unit: mm) Model Gas side joints Liquid side joints TRDK056HP TRDK112HP TRDK225HP TRDK314HP TRDK768HP TRDK840HP Table continued on next page …...
  • Page 264 TVR CONNECT 380V 50/60Hz Table 3-4.9: Indoor branch joint dimensions (unit: mm) (continued) Model Gas side joints Liquid side joints TRDK918HP Table 3-4.10: Outdoor branch joint dimensions for 2 unit’s combination (unit: mm) Model Gas side joints Liquid side joints TODK02CNHPA TODK02CNHPB...
  • Page 265 TVR CONNECT 380V 50/60Hz Table 3-4.11: Outdoor branch joint dimensions for 3 unit’s combination (unit: mm) Model Gas side joints Liquid side joints TODK03CNHPA TODK03CNHPB...
  • Page 266 TVR CONNECT 380V 50/60Hz 4.7 Refrigerant Leakage Precautions R410A refrigerant is not flammable in air at temperatures up to 100°C at atmospheric pressure and is generally considered a safe substance to use in air conditioning systems. Nevertheless, precautions should be taken to avoid danger to life in the unlikely event of a major refrigerant leakage.
  • Page 267: Refrigerant Piping Installation

    TVR CONNECT 380V 50/60Hz 5 Refrigerant Piping Installation 5.1 Procedure and Principles 5.1.1 Installation procedure  Notes for installers Installation of the refrigerant piping system should proceed in the following order: Pipe Pipe brazing Pipe Gastightness Joint Vacuum drying insulation and installation flushing test...
  • Page 268 TVR CONNECT 380V 50/60Hz 5.2 Storing Copper Piping 5.2.1 Pipe delivery, storage and sealing  Notes for installers ▪ Ensure that piping does not get bent or deformed during delivery or whilst stored. ▪ On construction sites store piping in a designated location. ▪...
  • Page 269 TVR CONNECT 380V 50/60Hz 5.3.3 Expanding copper piping ends  Notes for installers ▪ Ends of copper piping can be expanded so that another length of piping can be inserted and the joint brazed. ▪ Insert the expanding head of the pipe expander into the pipe. After completing pipe expansion, rotate the copper pipe a few degrees to rectify the straight line mark left by the expanding head.
  • Page 270 TVR CONNECT 380V 50/60Hz 5.3.5 Bending piping Bending copper piping reduces the number of brazed joints required and can improve quality and save material.  Notes for installers Piping bending methods ▪ Hand bending is suitable for thin copper piping (Ф6. 35mm - Ф12. 7mm). ▪...
  • Page 271 TVR CONNECT 380V 50/60Hz 5.5 Brazing Care must be taken to prevent oxide forming on the inside of copper piping during brazing. The presence of oxide in a refrigerant system adversely affects the operation of valves and compressors, potentially leading to low efficiency or even compressor failure.
  • Page 272 TVR CONNECT 380V 50/60Hz … box continued from previous page Piping orientation during brazing Brazing should be conducted downwards or horizontally to avoid filler leakage. Figure 3-5.6: Piping orientation during brazing Piping overlap during brazing Table 3-5.3 specifies the minimum permissible piping overlap and the range of permissible gap sizes for brazed joints on piping of different diameters.
  • Page 273 TVR CONNECT 380V 50/60Hz 5.6 Branch Joints  Notes for installers ▪ Use U-shaped branch joints as specified on the Figure 3-5.8: Branch joint orientation construction drawings – do not replace U-shaped branch joints with tee joints. ▪ To avoid accumulation of oil in the outdoor units, outdoor branch joints should be installed horizontally and must not be higher than the outdoor unit refrigerant outlets.
  • Page 274 TVR CONNECT 380V 50/60Hz 5.7 Piping Connections between Outdoor Units The piping connecting the outdoor units should be horizontal and must not be higher than the refrigerant outlets. If necessary, to avoid obstacles the piping may be vertically offset below the outlets. When inserting a vertical offset to avoid an obstacle, the whole outdoor piping should be offset, rather than just the section adjacent to the obstacle.
  • Page 275 TVR CONNECT 380V 50/60Hz 5.8.2 Procedure  Notes for installers Warning Only use nitrogen for flushing. Using carbon dioxide risks leaving condensation in the piping. Oxygen, air, refrigerant, flammable gases and toxic gases must not be used for flushing. Use of such gases may result in fire or explosion. Procedure The liquid and gas sides can be flushed simultaneously;...
  • Page 276: Gastightness Test

    TVR CONNECT 380V 50/60Hz 5.9 Gastightness Test 5.9.1 Purpose To prevent faults caused by refrigerant leakage, a gastightness test should be performed before system commissioning. 5.9.2 Procedure  Notes for installers Warning Only dry nitrogen should be used for gastightness testing. Oxygen, air, flammable gases and toxic gases must not be used for gastightness testing.
  • Page 277: Vacuum Drying

    TVR CONNECT 380V 50/60Hz 5.9.3 Leak detection  Notes for installers The general methods for identifying the source of a leak are as follows: 1. Audio detection: relatively large leaks are audible. 2. Touch detection: place your hand at joints to feel for escaping gas. 3.
  • Page 278 TVR CONNECT 380V 50/60Hz 5.10.2 Procedure  Notes for installers During vacuum drying, a vacuum pump is used to lower the pressure in the piping to the extent that any moisture present evaporates. At 5mmHg (755mmHg below typical atmospheric pressure) the boiling point of water is 0°C. Therefore a vacuum pump capable of maintaining a pressure of -756mmHg or lower should be used.
  • Page 279: Drain Piping

    TVR CONNECT 380V 50/60Hz 6 Drain Piping 6.1 Design Considerations Drain piping design should take account of the following considerations: ▪ Indoor unit condensate drain piping needs to be of sufficient diameter to carry the volume of condensate produced at the indoor units and installed at a slope sufficient to allow drainage.
  • Page 280 TVR CONNECT 380V 50/60Hz Figure 3-6.5: Drain piping air vents Vent ▪ Air conditioner drain piping should be installed separately from waste, rainwater and other drain piping and should not come into direct contact with the ground. ▪ Drain piping diameter should be not less than the indoor units’ drain piping connection. ▪...
  • Page 281 TVR CONNECT 380V 50/60Hz Table 3-6.2: Vertical drain piping diameters Nominal PVC piping Capacity (L/h) Remarks diameter (mm) PVC25 Branch piping only PVC32 PVC40 PVC50 1440 PVC63 2760 Branch or main piping PVC75 5710 PVC90 8280 6.4 Drain Piping for Units with Lift Pumps Drain piping for units with lift pumps should take account of the following additional considerations: ▪...
  • Page 282: Insulation

    TVR CONNECT 380V 50/60Hz  Notes for installers Installation of the drain piping should proceed in the following order: Drain piping Watertightness Indoor unit installation Drain piping insulation installation test Caution ▪ Ensure that all joints are firm and once the drain piping is all connected conduct a watertightness test and water flow test.
  • Page 283 TVR CONNECT 380V 50/60Hz of insulation should be increased over and above the specifications in Table 3-7.1. Table 3-7.1: Refrigerant piping insulation thickness Pipe outer diameter Minimum insulation thickness (mm) Minimum insulation thickness (mm) (mm) Humidity < 80%RH Humidity ≥ 80%RH Ф6.35 Ф9.53 Ф12.7...
  • Page 284 TVR CONNECT 380V 50/60Hz 7.1.4 Installation of piping insulation With the exception of joint insulation, insulation should be applied to piping before fixing the piping in place. Insulation at joints in refrigerant piping should be applied after the gastightness test has been completed. ...
  • Page 285: Charging Refrigerant

    TVR CONNECT 380V 50/60Hz 8 Charging Refrigerant 8.1 Calculating Additional Refrigerant Charge The additional refrigerant charge required depends on the lengths and diameters of the outdoor and indoor liquid pipes. Table 3-8.1 shows the additional refrigerant charge required per meter of equivalent pipe length for different diameters of pipe.
  • Page 286: Adding Refrigerant

    TVR CONNECT 380V 50/60Hz 8.2 Adding Refrigerant  Notes for installers Caution ▪ Only charge refrigerant after performing a gastightness test and vacuum drying. ▪ Never charge more refrigerant than required as doing so can lead to liquid hammering. ▪ Only use refrigerant R410A - charging with an unsuitable substance may cause explosions or accidents. ▪...
  • Page 287: Electrical Wiring

    TVR CONNECT 380V 50/60Hz 9 Electrical Wiring 9.1 General  Notes for installers Caution ▪ All installation and wiring must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation. ▪ Electrical systems should be grounded in accordance with all applicable legislation. ▪...
  • Page 288: Power Supply Wiring

    TVR CONNECT 380V 50/60Hz 9.2 Power Supply Wiring Power supply wiring design and installation should adhere to the following requirements: ▪ Separate power supplies should be provided for the indoor units and outdoor units. ▪ Where five or more outdoor units are installed, additional residual current protection (leakage protection) should be installed as shown in Figure 3-9.1.
  • Page 289: Communication Wiring

    TVR CONNECT 380V 50/60Hz  Notes for installers The 3-phase, 380-415V, 50 or 60Hz power supply should be connected to the outdoor unit power supply terminals as shown in Figure 3-9.4. Figure 3-9.4: Outdoor unit 3-phase power supply terminals 9.3 Communication Wiring Communication wiring design and installation should adhere to the following requirements: ▪...
  • Page 290 TVR CONNECT 380V 50/60Hz Figure 3-9.5: Communication wiring M1 M2 9.3.1 Outdoor units’ H1 H2 communication The outdoor unit’s combined system, and the communication lines between the ODUs must be connected in series. ▪ The H1 H2 communication wires should be connected one unit after another in a daisy chain from the master outdoor unit to the final slave outdoor unit.
  • Page 291 TVR CONNECT 380V 50/60Hz 9.3.3 Outdoor unit and indoor units’ P Q communication Communication wiring design and installation should adhere to the following requirements: ▪ 0.75mm2 two-core shielded cable should be used for communication wiring. Using other types of cable can lead to interference and malfunction.
  • Page 292 TVR CONNECT 380V 50/60Hz Communication wiring design and installation should adhere to the following requirements when IDUs separate power supplied. ▪ 1.5mm two-core cable should be used for communication wiring when the is indoor unit separate power supplied. ▪ All indoor units in the system are TVR CONNECT indoor units. ▪...
  • Page 293 TVR CONNECT 380V 50/60Hz  Notes for installers The communication wires should be connected to the master outdoor unit terminals indicated in Figure 3-9.11 and Table 3-9.2. Caution ▪ Communication wiring has polarity. Care should be taken to connect the poles correctly. Figure 3-9.11: Master outdoor unit communication terminals Table 3-9.2: Communication connections Terminals...
  • Page 294: Installation In Areas Of High Salinity

    TVR CONNECT 380V 50/60Hz 10 Installation in Areas of High Salinity 10.1 Caution Do not install outdoor units where they could be directly exposed to sea air. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. Outdoor units installed in seaside locations should be placed such as to avoid direct exposure to the sea air and additional anticorrosion treatment options should be selected, otherwise the service life of the outdoor units will be seriously affected.
  • Page 295: Commissioning

    0. If all IDUs in the system are TVR CONNECT series, and the RS-485 (P Q) communication function is required to be enabled, set the 4 digit of the master ODU digital display to 0.
  • Page 296: Pre-Commissioning Checks

    TVR CONNECT 380V 50/60Hz 11.3 Pre-commissioning Checks Before turning on the power to the indoor and outdoor units, ensure the following: 1. All indoor and outdoor refrigeration piping and communication wiring has been connected to the correct refrigeration system and the system to which each indoor and outdoor unit belongs is clearly marked on each unit or recorded in some other suitable place.
  • Page 297 Once all the pre-commissioning checks in Part 3, 11.3 “Pre-commissioning Checks” have been completed, a test run should be performed as described below and a TVR CONNECT Series System Commissioning Report (see Part 3, 12 “Appendix to Part 3 – System Commissioning Report”) should be completed as a record of the operating status of the system during commissioning.
  • Page 298: Appendix To Part 3 - System Commissioning Report

    TVR CONNECT 380V 50/60Hz 12 Appendix to Part 3 – System Commissioning Report A total of up to 11 report sheets should be completed for each system: ▪ One Sheet A, one Sheet B and one Sheet C per system. ▪...
  • Page 299 TVR CONNECT 380V 50/60Hz TVR CONNECT Series System Commissioning Report – Sheet A SYSTEM INFORMATION Project name and location Customer company System name Installation company Commissioning date Agent company Commissioning Outdoor ambient temp. engineer L1-L2 L2-L3 L3-L1 Power supply (V)
  • Page 300 TVR CONNECT 380V 50/60Hz...
  • Page 301 TVR CONNECT 380V 50/60Hz TVR CONNECT Series System Commissioning Report – Sheet B Project name and location System name OUTDOOR UNITS Master unit Slave unit 1 Slave unit 2 Compressor suction pipe temperature System pressure at check port Phase currents (A)
  • Page 302 TVR CONNECT 380V 50/60Hz TVR CONNECT Series System Commissioning Report – Sheet C Project name and location System name RECORD OF ISSUES SEEN DURING COMMISSIONING Serial no. of Description of observed issue Suspected cause Troubleshooting undertaken relevant unit OUTDOOR UNIT FINAL CHECKLIST...
  • Page 303 TVR CONNECT 380V 50/60Hz TVR CONNECT Series System Commissioning Report – Sheet D Project name and location System name Observed values DSP1 Cooling Heating Parameters displayed on DSP2 Remarks content mode mode --.-- "Standby (ODU address+ IDU number)/frequency/special status" Master unit: 0; slave units: 1, 2 0.--...
  • Page 304 TVR CONNECT 380V 50/60Hz Table continued on next page … TVR CONNECT Series System Commissioning Report – Sheet E Project name and location System name … table continued from previous page Observed values DSP1 Cooling Heating Parameters displayed on DSP2...

Table of Contents