Preparing the Site
Note
Statement 7001 ESD Mitigation
This equipment may be ESD sensitive. Always use an ESD ankle or wrist strap before handling equipment.
Connect the equipment end of the ESD strap to an unfinished surface of the equipment chassis or to the ESD
jack on the equipment if provided.
Warning
Statement 7003 Shielded Cable Requirements for Intrabuilding Lightning Surge
The intrabuilding port(s) of the equipment or subassembly must use shielded intrabuilding cabling/wiring that
is grounded at both ends.
The following port(s) are considered intrabuilding ports on this equipment:
RJ-45 Management Ethernet Port
Note
Statement 7004 Special Accessories Required to Comply with GR-1089 Emission and Immunity
Requirements
To comply with the emission and immunity requirements of GR-1089, shielded cables are required for the
following ports:
Copper RJ-45 Ethernet Management port
Warning
Statement 7005 Intrabuilding Lightning Surge and AC Power Fault
The intrabuilding port(s) of the equipment or subassembly is suitable for connection to intrabuilding or
unexposed wiring or cabling only. The intrabuilding port(s) of the equipment or subassembly MUST NOT
be metallically connected to interfaces that connect to the OSP or its wiring for more than 6 meters
(approximately 20 feet). These interfaces are designed for use as intrabuilding interfaces only (Type 2, 4, or
4a ports as described in GR-1089) and require isolation from the exposed OSP cabling. The addition of primary
protectors is not sufficient protection in order to connect these interfaces metallically to an OSP wiring system.
The following ports are considered intrabuilding ports on the equipment:
RJ-45 Management Ethernet Port
Warning
Statement 7012 Equipment Interfacing with AC Power Ports
Connect this equipment to AC mains that are provided with a surge protective device (SPD) at the service
equipment that complies with NFPA 70, the National Electrical Code (NEC).
Note
Statement 7013 Equipment Grounding Systems—Common Bonding Network (CBN)
This equipment is suitable for installations using the CBN.
Cautions and Regulatory Compliance Statements for NEBS
Cisco Nexus 9336C-FX2 ACI-Mode Switch Hardware Installation Guide
15
Need help?
Do you have a question about the Nexus 9336C-FX2 and is the answer not in the manual?