Download Print this page

Danfoss VACON 134U3015 Operating Manual page 24

Hide thumbs Also See for VACON 134U3015:

Advertisement

Electrical Installation
Terminal
42
4
4
50
53
54
55
Table 4.1 Terminal Descriptions - Digital Inputs/Outputs,
Analog Inputs/Outputs
Terminal
Parameter
61
68 (+)
69 (-)
20
Default
Parameter
setting
Programmable
analog output. The
analog signal is 0–
Parameter 6-91
20 mA or 4–
[0] No
Terminal 42
20 mA at a
operation
Analog Output
maximum of
500 Ω. Can also
be configured as
digital outputs.
10 V DC analog
supply voltage.
15 mA maximum
+10 V DC
commonly used
for potentiometer
or thermistor.
Analog input. Only
Parameter
voltage mode is
group 6-1*
supported. It can
Analog input 53
also be used as
digital input.
Analog input.
Parameter
Selectable
group 6-2*
between voltage
Analog input 54
or current mode.
Common for
digital and analog
inputs.
Default
Description
setting
Serial communication
Integrated RC filter
for cable shield.
ONLY for
connecting the
shield when
experiencing EMC
problems.
Parameter
RS485 interface. A
group 8-3* FC
control card switch
port settings
is provided for
Parameter
termination
group 8-3* FC
resistance.
port settings
Relays
Danfoss A/S © 08/2018 All rights reserved.
®
VLT
Midi Drive FC 280
Description
Terminal
01, 02, 03
Table 4.2 Terminal Descriptions - Serial Communication
4.8.2 Wiring to Control Terminals
Control terminal connectors can be unplugged from the
frequency converter for ease of installation, as shown in
Illustration 4.9.
For details about STO wiring, refer to chapter 6 Safe Torque
Off (STO).
NOTICE
Keep control cables as short as possible and separate
them from high-power cables to minimize interference.
1.
2.
3.
4.
See chapter 9.5 Cable Specifications for control terminal
cable sizes and chapter 7 Application Examples for typical
control cable connections.
4.8.3 Enabling Motor Operation
(Terminal 27)
A jumper wire is required between terminal 12 (or 13) and
terminal 27 for the frequency converter to operate when
using factory default programming values.
Default
Parameter
setting
Parameter 5-40
[1] Control
Function Relay
Ready
Loosen the screws for the terminals.
Insert sleeved control cables into the slots.
Fasten the screws for the terminals.
Ensure that the contact is firmly established and
not loose. Loose control wiring can be the source
of equipment faults or less than optimal
operation.
Digital input terminal 27 is designed to receive
24 V DC external interlock command.
When no interlock device is used, wire a jumper
between control terminal 12 (recommended) or
13 to terminal 27. The jumper provides an
internal 24 V signal on terminal 27.
Description
Form C relay
output. These
relays are in
various locations
depending on the
frequency
converter configu-
ration and size.
Usable for AC or
DC voltage and
resistive or
inductive loads.
MG07A502