— About this manual — Document information File name 4NWD005624_OPM_ABB_PVA31TX_5-10kVA_EN_REV-A UPS model PowerValue 31TX 5-10 kVA Date of issue 15.12.2021 Issued by Product Marketing Checked by R&D Article number Document number : 4NWD005624 Revision — Safety symbols and warnings The following symbols are used in this manual, the list below explains each symbol.
A B B U P S P R O D U C T S A N D S O L U T I O N S — Contents Important safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 1 .1 Operator precautions .
Page 5
4.5.7 Information Screen ......... . .36 4.5.7.1 Information - Identification Screen .
DISPLAY A WARNING LABEL ON ALL PRIMARY POWER ISOLATORS INSTALLED performed only by service personnel qualified AWAY FROM THE UPS AREA TO WARN and authorized by ABB, refer to service ELECTRICAL MAINTENANCE PERSONNEL manual(separate document). THAT THE CIRCUIT FEEDS A UPS.
POTENTIAL NEGATIVE EFFECTS ON HUMAN HEALTH AND THE ENVIRONMENT, WHICH COULD OTHERWISE ARISE FROM INAPPROPRIATE WASTE HANDLING. — 1 .3 Declaration of safety conformity and CE marking The PowerValue 31TX 5-10 kVA is designed, These products also meet the following manufactured and commercialized in accordance product standards: with the EN ISO 9001 standard relating to quality —...
1 .4 Inquiries Inquiries regarding the UPS should be the serial number of the equipment before addressed to the local ABB office or agent contacting ABB or authorized agent. The authorized by ABB. Note the type code and serial number is shown on the nameplate of the product.
— 2 General characteristics UPS cabinet Article number Dimensions WxHxD (mm) Weight with batteries (kg) PowerValue 31TX 5 kVA 4NWP100250R0001 520 x 1200 x 746 PowerValue 31TX 6 kVA 4NWP100251R0001 520 x 1200 x 746 PowerValue 31TX 8 kVA 4NWP100252R0001...
A B B U P S P R O D U C T S A N D S O L U T I O N S — 2 .2 UPS panel open view Figure 2.2-1 shows the front panel open view, figure 2.2-2 shows the rear panel open view of the UPS. —...
2 M A I N T E N A N C E — 3 Installation — 3 .1 Delivery, transportation and storage — 3 .1 .1 Visual inspection 3 .1 .2 Unpacking list 3.1.1-1 When receiving the goods, make sure that they After examining the package, open the box TILTMARKER indicator correspond to the material indicated in the...
3 I N S TA L L AT I O N — 3 .1 .5 Moving the Cabinet 3 .1 .6 Storage of UPS 3.1.5-1: Before storing, charge the UPS 5 hours. Store the moving the cabinet THE UPS IS FIXED ON THE PALLET WITH 2 UPS covered and upright in a cool, dry location.
A B B U P S P R O D U C T S A N D S O L U T I O N S — 3 .2 Site planning and positioning 3 .2 .1 Positioning of UPS — 3.2.2-1: Insert the battery module...
“ Warning! Line Input N Error” (figure 3.3.2-1). Subsequently, the UPS will transfer to battery mode if battery pack is connected, or transfer to standby mode without output if no battery pack is connected. SYSTEM ON ABB 31TX Bat Mode 10KVA Warning...
A B B U P S P R O D U C T S A N D S O L U T I O N S 3 .3 .3 Recommended cable sections and fuse ratings — 3.3.3-1: When selecting the cable cross-sections and the protective devices, follow the recommendations in Wiring diagram below table or follow local standards.
• Operate additional SNMP adapters and their software — 4 .1 Control Panel The user-friendly control — SYSTEM ON ABB 31 TX Line M ode 4.1-1: 1 0KVA panel has three parts: Control panel • Selection keys...
4.1.2-1: The LCD screen is divided into five parts. The default LCD (1) UPS Mode: Current operation mode. SYSTEM ON ABB 31 TX (2) UPS Flow Chart: Current flow chart and (1 ) 1 0KVA Standby M ode measurement data.
The following table describes the UPS status information: — Table 6: Symbols in operating mode Status LCD Screen Description SYSTEM ON ABB 31 TX Line M ode 1 0KVA When the input voltage is within acceptable range, UPS will provide LOAD BYPASS L3:0% L3:230.0V...
A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .3 UPS start-up and shutdown — 4.3.1-1: SWITCH OFF THE CONNECTED LOADS BYPASS MODE IS ENABLED BY DEFAULT Open key BEFORE TURNING ON THE UPS.
A B B U P S P R O D U C T S A N D S O L U T I O N S — — 4.4.1-1: Parallel system 4 .4 Parallel Operation installation — 4.4.1-2: Up to 4 units can be paralleled.The outputs are paralleled to increase the load capacity of the power Parallel system system and for redundancy.
Page 23
— BEFORE REMOVING A UNIT, MAKE SURE THE TOTAL LOAD DEMAND WILL BE WITHIN THE OUTPUT RATING 4.4.1-3: parallel communication OF THE PARALLEL SYSTEM AFTER THE OPERATION. cable INSTALLATION OF PARALLEL CABLES MUST BE PERFORMED BY QUALIFIED SERVICE ENGINEER. — WARNING 4.4.1-4: LOAD SHARING CABLES ARE CONNECTED TO PRIMARY CIRCUIT.
Switch the MBS • Select "Redundancy" in "SYSTEM" menu. (Figure 4.4.2-3). • Set "Total Power" and "Redundancy". (Figure 4.4.2-4). Please refer to Table 10 for details of the setting Item. ABB 31TX SYSTEM ON SYSTEM ON ABB 31TX SYSTEM ON...
5 seconds as shown in Figure 4.5.1-1 — 4.5.1-1 4 .5 .2 Main Screen SYSTEM ON ABB 31 TX (1 ) 1 0KVA Standby M ode After initialization, the main screen will display as Figure 4.5.2-1. Main screen is divided into five parts.
Cancel Shutdow n 4.5.4-4: Confirmation screen Charger Turn On — 4.5.5-1: Charger Turn Off Measurement submenu tree ABB 31 TX ABB 31 TX SYSTEM ON SYSTEM ON 1 0KVA Standby M ode Standby M ode 1 0KVA CONTROL CONTROL Page1 /2...
Page 27
” button to go into the — submenu, as shown in Figure 4.5.5 -3. 4.5.5-3: Measurement Submenu Screen SYSTEM ON SYSTEM ON ABB 31 TX ABB 31 TX 1 0KVA 1 0KVA Standby M ode Standby M ode M EASUREM ENT M EASUREM ENT...
When the SETUP option is selected by pressing “ ” button, screen requesting to enter password will pop up, as shown in Figure 4.5.6-2. SYSTEM ON ABB 31 TX Standby M ode 1 0KVA Enter Passw ord Enter Passw ord: 0 7 2 9...
Page 29
The default password is “0729”. It could be changed by user. Table 8 lists the relevant information. Table 8: All setting items in Setup Menu UPS operation Mode Setting item Model Name Language TIME Change Password General Audible Alarm Factory Reset Standard Mode EPO Function Output Voltage...
A B B U P S P R O D U C T S A N D S O L U T I O N S 4 .5 .6 .1 Setup-General Screen — SYSTEM ON ABB 31 TX 4.5.6.1-1: Use “ ” or “...
Page 31
Table 9: Setup-General setting list Setting Item Sub Item Explanation Model Name Enter UPS Name (xxxxxxxxxx). The max. Length is 10 characters. Language Provides 4 optional LCD languages: • English (Default) • German • French • Italian TIME Adjust Time Set current date and time.
A B B U P S P R O D U C T S A N D S O L U T I O N S 4 .5 .6 .2 Setup-System Screen — SYSTEM ON ABB 31 TX 4.5.6.2-1: Use “ ” or “...
Page 33
Table 10: Setup-System setting list Setting Item Sub Item Explanation Output Voltage Set output voltage. • 208Vac • 220Vac • 230Vac(Default) • 240Vac MUST be reviewed after UPS installation ECO Setting ECO Voltage Set ECO voltage range: Range Upper Range •...
MUST be set after UPS installation in parallel system Charger Test Set charger test • Disable (Default) • Enable SYSTEM ON 4 .5 .6 .3 Setup-Battery Screen ABB 31 TX Standby M ode 1 0KVA Use “ ” or “ ” button to switch different BATTERY Page1 /2 sub-menus.
Page 35
Table 11: Setup-Battery setting list Setting Item Sub Item Explanation Nominal Battery • 20x12V Voltage Battery voltage is fixed as +/-240VDC Battery Capacity Set battery capacity. in Ah • 7, 9 (Default), 10, 12, 17, 26, 40, 65, 100Ah MUST be set after UPS installation or Battery capacity is changed . Battery Groups* Set battery groups (1~4).
” button to switch 4.5.7.1-2. Use “ 4.5.7.1-2: between different pages. Identification screen page 2 — SYSTEM ON SYSTEM ON ABB 31 TX ABB 31TX SYSTEM ON ABB 31 TX 4.5.7.2-1: 1 0KVA Standby Mode Standby M ode 10KVA Standby M ode...
A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .5 .7 .3 Information - Battery Screen 4.5.7.3-1: Information Battery When Battery submenu is selected, the battery screen page 1 information such as nominal battery voltage, —...
4 .5 .8 .1 Current Events — When event occurs, it will display Module ID and 4.5.8.1-1: Current Events screen alarm code in Current Events screen. It can save up to 50 events in current list. Only 4 events can —...
Page 40
A B B U P S P R O D U C T S A N D S O L U T I O N S Table 13: Important setting changed Item No . Description Item No . Description Setup! Model Name Setup! Language Setup! Adjust Time Setup! System Installed Date...
— 4 .6 LCD Structure The entire LCD structure is demonstrated as below diagram. Turn On Batt Test Press button “Enter ” Turn To Bypass Control Press button “Esc” SR On/Off Charger On/Off Press button “Enter ” Local System Press button “Esc ” Measurement Master Slave 1...
A B B U P S P R O D U C T S A N D S O L U T I O N S — 5 Control Module & Communication — 5-1: Communication ports Battery start button Input dry contacts Load Sharing Port Output dry contacts Intelligent Slot...
5 .2 .1 Configuration Step 1: Please get this software “Communication Setting Tool” from the USB disk and install this tool in your computer. Connect your computer to the UPS via RS232 serial cable, which is not included in the UPS package. Note that the connector of the cable to UPS should be DB9 male. Step 2: Start this tool in your computer.
Page 44
A B B U P S P R O D U C T S A N D S O L U T I O N S Step 4: Check all settings. There are 18 options to select for contact and listed in Table 16 Once output dry contact settings are selected, click “Setting Confirm”...
Step 5: “Default setting” button: It’s to reset all configurations back to default value. — 5 .3 . Input Dry Contact Port There are two sets of input dry contact to receive external signals for UPS to take response. Pin 13 Pin 14 Pin 15 Pin 16...
A B B U P S P R O D U C T S A N D S O L U T I O N S — 5 .4 EPO Port This UPS is equipped with an Emergency Power off (EPO) port that can be operated by a remote contact assigned by the user.
— 5 .7 Connectivity card (optional) The PowerValue 31TX is equipped with two SNMP Web Pro uses DHCP by default. If there intelligent slots for optional cards for remote is no DHCP server in the LAN, the SNMP web management of the UPS through the Internet/ pro will use the default static network Intranet.
A B B U P S P R O D U C T S A N D S O L U T I O N S — 6 Troubleshooting — 6 .1 Accessing alarms Alarms and events indicate warnings and faults in the system. The output of the UPS is not necessarily affected when an alarm arises but taking the correct actions may prevent loss of power to the load.
Page 49
LCD Message Explanation Solution Fault 1A:Nega Power R R phase inverter output negative Contact service personnel. power is beyond the range. Fault 21:Inv STS Open Inverter relay or STS is open. Contact service personnel. Fault 22:Inv STS Short Inverter relay or STS is short Contact service personnel.
A B B U P S P R O D U C T S A N D S O L U T I O N S 6 .1 .2 Warning Reference Code LCD Message Explanation Solution Warning 01:BatLow Battery voltage is low. Charge the battery when the mains is normal.
Page 51
Warning 1A:BypassDiff Each module gets different bypass Contact service personnel. voltage when they are in parallel. Warning 1C:BpsUnstable UPS switches between bypass mode Contact service personnel. and standby mode five times in 30 minutes due to abnormal utility. Warning As stated. Check if redundancy setting is correct or 1D:RedundancyFail not.
Failure to perform mandatory preventative maintenance on fans, AC capacitors, DC capacitors and battery as recommended in the ABB product manuals may result in thermal damage to the equipment, its surroundings, and an increased risk of personnel injury.
ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches any unauthorized access, interference, intrusion, leakage and/or theft of data or information.