Use, Installation and Maintenance Manual MODULATING WARM AIR HEATER LRP - RAPID PRO AND CONDENSING WARM AIR HEATER LK - KONDENSA TRANSLATION OF ORIGINAL Manual LRP - RAPID PRO and LK - KONDENSA code HG0141.11GB ed.A-2403...
Page 2
APEN GROUP S.p.A. 20042 Pessano con Bornago (MI) Via Isonzo, 1 Tel +39.02.9596931 r.a. Fax +39.02.95742758 Internet: http://www.apengroup.com Il presente documento dichiara che la macchina: With this document we declare that the unit: Modello: Generatore d’aria calda LRP, LK, LKC Model: Warm Air Heater LRP, LK, LKC è...
Page 3
Tel +39.02.9596931 r.a. VER. 01.2020 Fax +39.02.95742758 UK Declaration of Conformity Internet: http://www.apengroup.com With this document we declare that the unit: Model: Warm Air Heater LRP, LK, LKC has been designed and manufactured in compliance with the prescriptions of the following Regulations: APEN GROUP S.p.A.
Page 4
LRP and LK WARM AIR HEATER TABLE OF CONTENTS GENERAL CAUTIONS ........................5 SAFETY-RELATED WARNINGS ....................5 2.1. Fuel ........................................5 2.2. Gas Leaks ......................................5 2.3. Power supply...................................... 6 2.4. Use ........................................6 2.5. Maintenance ...................................... 6 2.6. Transport and Handling ..................................6 2.7.
37/2007 (ex 46/90) the unit; • move away from the unit For more information, visit our website www.apengroup.com or • call for qualified staff. contact Apen Group directly. • call the Fire Brigade.
LRP and LK WARM AIR HEATER 2.3. Power supply All repairs must be carried out by using genuine spare parts. Failure to comply with the above instructions could compromise The heater must be correctly connected to an effective earthing the safety of the equipment and invalidate the warranty. system, made in compliance with current regulations (IEC 64-8, If the equipment is not used for long periods, shut the gas applies to Italy only).
LRP and LK WARM AIR HEATER 2.7. Unpacking INFORMATION FOR DISPOSAL valid abroad (EU COUNTRIES except Italy). The unpacking operation must be carried out by using suitable The European Directive 2012/19/EC shall be implemented in tools or safety devices where required. Recovered packaging every EU member state.
LRP and LK WARM AIR HEATER TECHNICAL FEATURES Inherent Safety The efficiency increase at minimum power is achieved by using The LRP-RAPID PRO and LK-KONDENSA series modulating a sophisticated air/gas mixing technique and by regulating at warm air heaters have been designed to heat industrial and the same time the combustion air flow and the fuel gas flow.
LRP and LK WARM AIR HEATER 3.1. Technical Data Model LRP055-0X00 LRP075-0X00 LRP102-0X00 Type of equipment B23 - B23P - C13 - C33 - C43 - C53 - C63 EC approval PIN. 0476CQ0451 NOx class [EN17082:2019] Type of fuel Gaseous Heater Performance Burner heat output (Hi) 29.8...
Page 10
LRP and LK WARM AIR HEATER Model LK045-0X00 LK065-0X00 LK080-0X00 LK105-0X00 Type of equipment B23 - B23P - C13 - C33 - C43 - C53 - C63 EC approval PIN. 0476CQ0451 NOx class [EN17082:2019] Type of fuel Gaseous Heater Performance Burner heat output (Hi) 8.50 42.00...
Page 11
LRP and LK WARM AIR HEATER 3.2. Technical data of centrifugal models LRP055 LRP075 LKC045- LKC065- Model -0XC0 -0XC0 0X00 0X00 Type of equipment B23 - B23P - C13 - C33 - C43 - C53 - C63 EC approval PIN. 0476CQ0451 NOx class [EN17082:2019] Type of fuel...
Page 12
LRP and LK WARM AIR HEATER Following is a graph reading example: 60,0 Model LKC065-0X00 Available pressure: 100 Pa 50,0 Air flow rate: 6000 m ΔT: 30°C 40,0 30,0 20,0 10,0 3000 3500 4000 4500 5000 5500 6000 6500 7000 Portata Aria [m Graph "Air flow rate - pressure drop"...
Page 13
LRP and LK WARM AIR HEATER 3.3. REGULATION (EU) 2016/2281 Product Information in accordance with Annex 2 point 5 a) Model: See table Warm air heaters B1 [yes/no]: Warm air heaters C2 [yes/no]: Warm air heaters C2 [yes/no]: Type of fuel Gaseous [gaseous/liquid/electricity]: Consumption of...
Page 14
LRP and LK WARM AIR HEATER 3.4. Noise LRP055-0X00 / LK045-0X00 Sound power 75,7 The sound power of a source (energy emitted per unit time) is a 70,1 characteristic of the same source and does not depend on the 69,6 68,2 environment in which the sound is emitted: this measurement 66,2...
LRP and LK WARM AIR HEATER 3.5. Air flow performance The air flow range, or air throw, is the distance reached by the air jet before its speed decreases and equals the reference speed, assumed to be 0.2 m/s. The throw depends on the speed of the air leaving the heater, which in turn depends on the air flow rate and on the section of the heater air passage.
Page 16
LRP and LK WARM AIR HEATER 3.6. Dimensions HG0140.00_C2_001 HG0140.00_C2_001 HG0140.00_C2_007 HG0140.00_C2_007 HG0140.00_C2_007 HG0140.00_C2_007 HG0140.00_C2_001 HG0140.00_C2_001 Mod. Overall dimensions Louvre Shelf Supply GAS LRP and LK IS IS ID ID ØG ØG [mm] LRP055-0X00, LK045-0X00 LRP075-0X00, 1310 1010 LK065-0X00 LRP102-0X00, 1515 1180 LK080-0X00...
Page 17
LRP and LK WARM AIR HEATER HG0140.00_C2_001 HG0140.00_C2_001 Mod. Mod. Vertical drains (OPT.) Horizontal exhausts (STD) LRP and LK LRP and LK [mm] [mm] LRP055-0X00, LRP055-0X00, LK045-0X00 LK045-0X00 LRP075-0X00, LRP075-0X00, LK065-0X00 LK065-0X00 LRP102-0X00, LRP102-0X00, LK080-0X00 LK080-0X00 100* 100* 100* 100* LK105-0X00 LK105-0X00 * Obtained by using the adaptors supplied as standard...
Page 18
LRP and LK WARM AIR HEATER Packaging Mod. LRP and LK Bi Bi Li Li Hi Hi [mm] LRP055-0X00, 1065 LK045-0X00 LRP075-0X00, 1395 LK065-0X00 LRP102-0X00, 1595 1040 LK080-0X00 LK105-0X00 1820 1040 LRP035-0XC0 1165 1065 LRP055-0XC0, 1165 1065 LKC045-0X00 LRP075-0XC0, 1115 1400 LKC065-0X00 LRP - RAPID PRO and LK - KONDENSA...
LRP and LK WARM AIR HEATER USER'S INSTRUCTIONS 4.2. Interface Panel The LRP and LK heaters are fitted as standard with a multifunction LCD panel located on the front panel of the suspended heater, 4.1. Operating Cycle which is used to control, configure and diagnose all operating The wall mounted LRP and LK heaters operation is fully parameters of the equipment.
Page 20
LRP and LK WARM AIR HEATER Use the ↑ (up arrow) and ↓ (down arrow) buttons to scroll through Input - InP Menu the menus. To select the menu, or select the parameter, press Allows to display the value and/or status of analogue and digital ENTER.
Page 21
LRP and LK WARM AIR HEATER 4.4. Flame indication LED Entering the password • From the home screen (rdy/Sty/rOF/OFF/HEA/Air/COO/ An orange LED is present on board the CPU PCB, indicating SAn/EXX) press ENTER then use the ↑ (up arrow) and ↓ the opening of the gas valve and/or the presence of flame.
Page 22
LRP and LK WARM AIR HEATER 4.5. Navigation map of LCD display menu CPUE G26800 Level Level Level ENTER ENTER ENTER “Confirm” type of operation ENTER “Confirm” ENTER ENTER “Confirm” adjustment burner ENTER “Confirm” display machine status ENTER ENTER “Confirm” function degasser “Axx”...
Page 23
LRP and LK WARM AIR HEATER - "input management" - "output management" ENTER ENTER “Value” “Value” “Value” “Value” “Value” “Value” ENTER “Value” “Value” “Value” “Value” ENTER “Value” “OPn/CLS” “Value” “OPn/CLS” “OPn/CLS” “OPn/CLS” “OPn/CLS” “OPn/CLS” “OPn/CLS” “OPn/CLS” “OPn/CLS” “OPn/CLS” - “PCB parameters” ENTER “PWD”...
Page 24
LRP and LK WARM AIR HEATER 4.6. Adjustment 4.7. Accessories Ambient temperature adjustment The LRP or LK heaters have three heat output regulation modes: • 0-10 Vdc; The LRP and LK heaters are supplied without remote control • ModBus; and/or thermostat to regulate the room temperature as they can •...
Page 25
LRP and LK WARM AIR HEATER Operation with chronothermostat (OPTIONAL) An integrated temperature probe allows the management of the The heater operation is entirely automatic and, by using a room temperature of the controlled area; the remote controls chronothermostat, the ambient temperatures can be regulated. of the Smart series also offer the possibility to connect up to 3 The chronothermostat and the PCB monitor all the control and individually programmable remote probes, in addition to the one...
LRP and LK WARM AIR HEATER INSTALLATION INSTRUCTIONS Fixed shelves To install the fixed shelves to the walls: Instructions for installing and setting the heater are intended for • fix it to the wall and level the bracket with a spirit level; suitably qualified personnel only.
Page 27
LRP and LK WARM AIR HEATER Suspended heater Vertical heater FOR ALL LRP and LK HEATERS ONLY FOR LRP HEATERS To install a suspended heater by using chains or threaded bars, The heater can be installed with air intake from top to bottom a kit containing supporting hooks is available as an accessory by requesting the G27980 kit.
LRP and LK WARM AIR HEATER 5.3. Condensate drain The trap, installed inside the heater, has a condensate detection electrode that shuts down the generator in case the condensate The LK series heaters are flue gas condensing appliances. The does not flow out correctly from the drain, in order to prevent lowering of the flue gas temperature in the tube bundle of the condensate from remaining inside the heat exchanger.
LRP and LK WARM AIR HEATER 5.4. Connections to the Flue CAUTIONS Special attention must be paid to the condensate drain; an The LRP and LK heaters are fitted with a watertight combustion incorrectly installed draining system, in fact, could jeopardize circuit and with a fan located upstream of the heat exchanger.
Page 30
LRP and LK WARM AIR HEATER All components must be CE marked, certified in compliance with EN 1856-1 and EN1856-2 standards and identified by an N O T E : I f t h e m o d u l e i s i n s t a l l e d i n d o o r : ID plate showing their features.
Page 31
LRP and LK WARM AIR HEATER LRP models Pressure available at the exhaust [Pa] Component Pressure drop [Pa] Code SMOOTH Ø80 PIPE [l=1 m] 10.7 18.2 G15820-08-XXX BEND Ø80 WIDE RADIUS 90° 10.0 18.1 31.0 G15810-08-90 BEND Ø80 WIDE RADIUS 45° 14.6 G15810-08-45 Ø80 WALL-MOUNTED TERMINAL FROM SEPARATE TO COAX...
Page 32
LRP and LK WARM AIR HEATER Fume exhaust and rear air intake Installing the terminals The LRP and LK heaters are fitted with a top and bottom provision for air inlet and fume exhaust. According to installation requirements, the terminals can be fitted at the back or at the top.
Page 33
LRP and LK WARM AIR HEATER Type C53 terminal Fumes OUT Combustion circuit watertight to the environment. One of the ducts is connected to the roof, the other to the wall. of the pipe routing made with the Ø shown, excluding the terminal.
Page 34
LRP and LK WARM AIR HEATER Horizontal coaxial C13 terminal Combustion circuit watertight to the environment. The ducts go directly through the wall. of the pipe routing made with the Ø shown, excluding the 1max terminal. HG140.00_IM_024 The terminal consists of: •...
Page 35
LRP and LK WARM AIR HEATER C33 type coaxial roof-mounted terminal Combustion circuit watertight to the environment. The ducts are connected to the outside with a coaxial terminal. of the pipe routing made with the Ø shown, excluding the terminal. The terminal consists of: •...
LRP and LK WARM AIR HEATER 5.5. Electrical connections Analogue and digital inputs Should it be necessary to control one or more analogue inputs, Cautions through the connection of an external NTC probe, the relevant cable sections are indicated below according to the cable length: All remote controls must have a maximum connection length of less than 10 m and up to 500 m in the case of Smart series chronothermostats.
Page 37
LRP and LK WARM AIR HEATER Smart X Web/Easy connection Summer ventilation Use the connector provided to connect the To enable the fans only (summer ventilation with burner off), Smart X Web/Easy. Connect power supply with three types of controls are available: shielded wiring with a minimum cross-section of 0.5 mm2, •...
LRP and LK WARM AIR HEATER 5.6. Modulation PCB Parameters All values of the parameters of the CPU PCB are shown for all LRP and LK heater models. The “LCD” column shows the parameters that could be modified with "007" Password via remote LCD control (even with modbus address ≠...
Page 39
LRP and LK WARM AIR HEATER Parameters of G26800 CPU PCB version 8.03.xx Parameter Name LRP018 LRP035 LRP055 LRP075 LRP102 LRP028 LRP045 LK045 LK065 LK080 Smart U.M. DESCRIPTION LK020 LK034 REG 03 rGL R30 Control 03 - NOT USED ON LRP-LK Adjustment enabling REG_03 0 = disabled...
Page 40
LRP and LK WARM AIR HEATER Parameters of G26800 CPU PCB version 8.03.xx Parameter Name LRP018 LRP035 LRP055 LRP075 LRP102 LRP028 LRP045 LK045 LK065 LK080 Smart U.M. DESCRIPTION LK020 LK034 CTRL 08 CrL C80 Counter and reset control HOURS Burner operating hours counter CYCLES Ignition cycles counter FAULT...
Page 41
LRP and LK WARM AIR HEATER Parameters of G26800 CPU PCB version 8.03.xx Parameter Name LRP018 LRP035 LRP055 LRP075 LRP102 LRP028 LRP045 LK045 LK065 LK080 Smart DESCRIPTION LK020 LK034 RS485 Serial Communication Configurations slave serial baud rate (SMART X) 0 = baud rate 19,200 - Even Parity 1 = baud rate 9,600 - Even Parity D_SL 2 = baud rate 19,200 - Odd Parity...
Page 42
LRP and LK WARM AIR HEATER Parameters of G26800 CPU PCB version 8.03.xx Parameter Name LRP018 LRP035 LRP055 LRP075 LRP102 LRP028 LRP045 LK045 LK065 LK080 Smart DESCRIPTION LK020 LK034 Y0 Analogue Output Configuration - DO NOT CHANGE! Direct/reverse output configuration 0 = direct output: the maximum calculation value (100%) 1 (Reverse) corresponds to the maximum output value...
LRP and LK WARM AIR HEATER 5.7. Analysis of lockouts- faults The CPU-SMART manages two types of lockouts: • preventive, it warns the customer that the LRP and LK heaters require maintenance; • operational, it stops the LRP or LK heater for safety reasons or to ensure its correct operation. Some operational faults require manual reset;...
Page 44
LRP and LK WARM AIR HEATER CODE DESCRIPTION CAUSE RESET Flue Gas Fan Fault Alarms (VAG) • Flue gas fan (VAG) power supply interrupted; • Flue gas fan (VAG) fault; • CPU PCB fault. No flue gas fan (VAG) start-up or speed To check possible CPU failure, disconnect 4-wire connector Manual too low in start-up phase...
Page 45
LRP and LK WARM AIR HEATER CODE DESCRIPTION CAUSE RESET Parameter configuration error alarms Not used. Programming error of par. CTRL_01. Set par. Pressure probe error CTRL_01 = 0 Not used. Programming error of par. CTRL_01. Set par. Pressure less than ST_H20 setpoint CTRL_01 = 0 Not used.
LRP and LK WARM AIR HEATER GAS CONNECTION NOTE: For ease of maintenance, connect the heater by means of a seal and swivel gasket. Use the gas line connections only with CE certified components. Avoid using threaded connections directly on the gas connection. The heater is supplied complete with: Current legislation allow a maximum pressure inside the •...
LRP and LK WARM AIR HEATER SERVICING INSTRUCTIONS The first start-up must be carried out only by authorised service centres. The first start-up also includes a combustion analysis, which is compulsory. The equipment is certified in the EC and non-EC countries, according to the gas categories shown below. 7.1.
Page 48
LRP and LK WARM AIR HEATER 7.2. Gas Settings Table LRP-RAPID PRO Table If a Hydrogen-ready installation is provided for H2 percentages up to 20% (referred to gas distributed in the network), all gas valve calibration operations must refer to the O2 values in table G20 TYPE OF GAS G20 - Cat.
Page 49
LRP and LK WARM AIR HEATER TYPE OF GAS G2.350 - Cat. Ls (Only for PL-Poland) LRP055- LRP075- TYPE OF MACHINE 0X00 0X00* CATEGORY according to the country of destination - see reference table SUPPLY PRESSURE [mbar] 13 [min 10-max 16] PILOT NOZZLE Ø...
Page 50
LRP and LK WARM AIR HEATER TYPE OF GAS G30 - Cat. 3B-P LRP055- LRP075- LRP102- TYPE OF MACHINE 0X00 0X00 0X00* CATEGORY according to the country of destination - see reference table SUPPLY PRESSURE [mbar] 30 [min 25-max 35] - 37 [min 25-max 45] - 50 [min 42.5-max 57.5] PILOT NOZZLE Ø...
Page 51
LRP and LK WARM AIR HEATER LK-KONDENSA Table If a Hydrogen-ready installation is provided for H2 percentages up to 20% (referred to gas distributed in the network), all gas valve calibration operations must refer to the O2 values in table G20 TYPE OF GAS G20 - Cat.
Page 52
LRP and LK WARM AIR HEATER TYPE OF GAS G2.350 - Cat. Ls (Only for PL-Poland) LK045- LK065- TYPE OF MACHINE 0X00 0X00* CATEGORY according to the country of destination - see reference table SUPPLY PRESSURE [mbar] 13 [min 10-max 16] PILOT NOZZLE Ø...
Page 53
LRP and LK WARM AIR HEATER TYPE OF GAS G30 - cat. 3B-P * LK045- LK065- LK080- LK105- TYPE OF MACHINE 0X00 0X00 0X00** 0X00*** CATEGORY according to the country of destination - see reference table SUPPLY PRESSURE [mbar] 30 [min 25-max 35] -37 [min 25-max 45] - 50 [min 42.5-max 57.5] PILOT NOZZLE Ø...
LRP and LK WARM AIR HEATER 7.3. Starting up for the first time ATTENTION: IT IS FORBIDDEN to loosen the gas connections, the pressure connectors, the pilot burner The LRP and LK heaters are supplied with settings entered and duct, or any other gas connection point located inside tested for the gas specified on the nameplate.
LRP and LK WARM AIR HEATER 7.5. Conversion to LPG 7.6. Conversion to gas G25 - G25.1 - G25.3 - G27 Conversion is strictly prohibited in some countries, such Conversion for gasses from G20 to G25 or G25.1 or G25.3 or G27 as Belgium, which do not allow the double gas category.
Page 56
LRP and LK WARM AIR HEATER 7.7. Conversion to gas G2.350 7.8. Replacing the Gas Valve Conversion is allowed only for Poland. If the gas valve must be replaced, it is required to proceed with Conversion from one type of gas to another can only be performed an inspection and possibly calibrate the CO level through the by authorised service centres.
LRP and LK WARM AIR HEATER 7.10. Replacing the modulation PCB MAINTENANCE When replacing the CPU modulation PCB, it is required to carry To keep the heater efficient and guarantee a long lifetime of the out some essential operations, described below. same, it is advisable to run some inspections at regular intervals: 1.
Page 58
LRP and LK WARM AIR HEATER 1) Inspection of electrodes To check that the salts inside the tray are still active, use Dismantle the complete pilot flame and use a jet of compressed litmus paper to check that the pH level of water flowing out of air to clean the mesh and nozzle.
LRP and LK WARM AIR HEATER LIST OF SPARE PARTS 10.1. Parts for the control panel CPU PCB case G16881.02 Base G16882.02 Cover CPU BOARD G26800.03 Modulation Connector ModBus Connector Burner fan ON/OFF Connector G10054 G10054 G04763 Connector G11099 NTC1 Connector G04763 Connector G11101...
LRP and LK WARM AIR HEATER 10.2. Parts for the burner unit Gas valve Venturi G14067 LRP018-075 G14898 LRP018 Pilot solenoid valve LK020-080 LK020 G14378 For all models G14281-R LRP102 G14899 LRP028 LK105 G14990 LRP035 Butterfly gasket LK034 G14129 LRP018-075 G14068 LRP045 LK020-080...
Page 62
LRP and LK WARM AIR HEATER Water trap complete with electrode for condensation detection G27810.01 Water trap pipe Cable RVK condensation detection G27576 G28303 Condensation detection electrode G27806 Electrode gasket G28826 Water trap gasket G28827.02 Tabs G27582 no.7 LRP018-028 LK020 G27583 no.7 LRP035-045...
Page 63
LRP and LK WARM AIR HEATER LRP - RAPID PRO and LK - KONDENSA code HG0141.11GB ed.A-2403...
Page 64
LRP and LK WARM AIR HEATER LRP - RAPID PRO and LK - KONDENSA code HG0141.11GB ed.A-2403...