11. Performance curves
11.1 Guide to performance curves
Each pump setting has its own performance curve. However,
AUTO
covers a performance range.
ADAPT
A power curve, P1, belongs to each performance curve. The
power curve shows the pump power consumption in watt at a
given performance curve.
11.2 Curve conditions
The guidelines below apply to the performance curves on the
following pages:
•
Test liquid: airless water.
The curves apply to a density of ρ = 983.2 kg/m
•
temperature of 60 °C.
•
All curves show average values and must not be used as
guarantee curves. If a specific minimum performance is
required, individual measurements must be made.
•
The curves for speeds I, II and III are marked.
The curves apply to a kinematic viscosity of = 0.474 mm
•
(0.474 cSt).
•
The conversion between head H [m] and pressure p [kPa] has
been made for water with a density of 1000 kg/m
with other densities, for example hot water, the outlet pressure
is proportional to the density.
•
Curves are obtained according to EN 16297-2.
3
and a liquid
2
/s
3
. For liquids
21