Ziton ZP755V-P Installation Sheet
Ziton ZP755V-P Installation Sheet

Ziton ZP755V-P Installation Sheet

Addressable visual indicator

Advertisement

Quick Links

ZP755V Addressable Visual Indicator
Installation Sheet
Description
The ZP755V-P is an addressable visual indicator designed for
use in Ziton addressable fire detection and alarm systems. The
visual indicator provides visual warnings from a single,
addressable, loop-wired unit.
Caution:
This product does not comply with EN 54-23 and
must not be used in fire alarm installations where fire
notification beacons are required.
The unit includes a DIP switch for setting the device address
and two jumpers to set the operating power source (loop or
external 24 VDC supply).
The visual indicator must be mounted onto the ZP7-SBB-P
Base (not supplied).
Installation
To install the visual indicator:
1.
Wire the base
2.
Set the operating power (loop or external)
3.
Set the address
4.
Mount the visual indicator onto the base
The details of each step are given below.
© 2024 Carrier. All rights reserved.
Wiring the base
Wire the base (not supplied) as shown in Figure 1. There is no
wiring between the visual indicator and base.
Figure 1: Wiring the base
(1) Ext. 24 VDC+ IN/OUT
(4) Ext. 24 VDC ground IN/OUT
(5) Loop+ IN/OUT
Setting the operating power
Use jumpers J1 and J2 to set the operating power source, as
shown in Figure 2.
Figure 2: Setting the operating power
(1) Loop powered
Caution:
The external power supply must be EN 54-4
compliant and of sufficient capacity for the installation
requirements.
1 / 3
(7) Shield
(8) Loop− IN/OUT
(2) External 24 VDC
powered
P/N 501-1782ZE-1-10 • ISS 25APR24

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZP755V-P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ziton ZP755V-P

  • Page 1 Figure 1: Wiring the base Description The ZP755V-P is an addressable visual indicator designed for use in Ziton addressable fire detection and alarm systems. The visual indicator provides visual warnings from a single, (1) Ext.
  • Page 2 Setting the address Visual indicators per loop Use DIP switches 1 to 7 (see Figure 3) to set the device The unit can be powered directly from the loop. Use Figure 4, address from 1 to 127. in conjunction with Table 1, to determine the quantity of detectors and visual indicators that can be connected to a two- Each switch has a decimal value, as shown below.
  • Page 3 Strobe frequency Flash rate 1.1 seconds Loop monitoring Operating power level tested continuously Addressing method DIP switch Mounting Surface with stand-alone visual indicator base Wiring Two-core shielded loop Material Moulded thermoplastic Colour Polar White (similar to RAL 9003) Environmental Operating temperature −10 to +60°C Storage temperature −20 to +70°C...