SERIES
USE AND INSTALLATION
GUIDE
Outdoor Unit
ALL phases of the installation must comply with NATIONAL, STATE, and LOCAL CODES.
IMPORTANT - This document is customer property and is to remain with this unit.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the
installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the
purchaser's purpose, the matter should be referred to the installing dealer and local distributor.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Q Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for innovair Q Series

  • Page 1 SERIES USE AND INSTALLATION GUIDE Outdoor Unit ALL phases of the installation must comply with NATIONAL, STATE, and LOCAL CODES. IMPORTANT - This document is customer property and is to remain with this unit. These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation.
  • Page 2 Q O S 1 2 H 2 X E 5 Outdoor 1 — Brand 4 — System Type 7 —Tier Q = Q Series C = Cool Only E = Entry (-4°F) H = Heat Pump M = Mid Tier (-13°F) H = Hyper (-22°F)
  • Page 3: Table Of Contents

    Contents S a fe t y l n st r ucti o n s P rep a r ati o n bef o re U s e P re s e t ·············································································································································· 3 Safeguarding t he Envir o nmen t S a fe t y P re cauti o n s ··········································································································...
  • Page 4: S A Fe T Y L N St R Ucti O N S

    Safety Instructions • 1. To ensure the unit functions properly, please carefully read the manual before installation. Follow the instructions to complete the installation as specified in the manual. • 2. Avoid allowing air to enter the refrigeration system and prevent refrigerant discharge when moving the air conditioner.
  • Page 5 Safety Instructions • 14. If the air conditioner is hardwired, it must include a disconnection method from the main power supply that ensures full contact separation across all poles, providing complete disconnection under over voltage category III conditions. This disconnection means must be integrated into the fixed wiring, following applicable wiring regulations.
  • Page 6: Preparation Before Use

    PREPARATION BEFORE USE Note • When charging refrigerant into the system, ensure it is in a liquid state if the refrigerant used is R32 or R454B. Otherwise, the chemical composition of these refrigerants may alter, impacting the air conditioner’s performance. •...
  • Page 7: Safety Precautions

    Safety Precautions Symbols in this Use and Care Manual are interpreted as shown below. Be sure not to do. Grounding is essential. Warning: Incorrect handling could Pay attention to such a situation. cause a serious hazard, such as death, serious injury, etc. Use the correct power supply as �...
  • Page 8: Sugge S T Ed To Ols

    Safety Precautions Precautions for using R32 and R454B refrigerant Pay attention to the following points: CAUTION 1. Transport of equipment containing flammable refrigerants Ensure compliance with all relevant transport regulations. 2. Marking of equipment using signs Adhere to local regulations for proper marking of equipment. 3.
  • Page 9: Si T E L N S T Ru C T I O N

    Safety Precautions CAUTION 6-5 Presence of fire extinguisher 7-If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. 8-Have a dry powder or CO2 fire extinguisher adjacent to the charging area. 6-6 No ignition sources 7-No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources...
  • Page 10: O U T D Oo R U Ni T L N S T A Ll A T I O

    Safety Precautions � CAUTION which are inherently resistant to being corroded or are suitably protected against being so corroded. Checks to electrical devices • Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. • lf a fault exists that could compromise safety , then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with.
  • Page 11 Safety Precautions CAUTION live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. • Replace components only with parts specified by the manufacturer. • Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
  • Page 12: P O Wer And Wiring 1

    Safety Precautions CAUTION • Pull a full vacuum on the system; • Purge again with inert gas; • Then, open up the line by cutting or brazing as needed. • The refrigerant charge shall be recovered into the correct recovery cylinders. •...
  • Page 13 Safety Precautions CAUTION "Before beginning the procedure, double-check the following: Mechanical handling equipment is on hand if needed to manage refrigerant cylinders. All personal protective equipment (PPE) is available and worn properly. A qualified person is supervising the recovery process at all times. The recovery equipment and cylinders meet the necessary standards.
  • Page 14 Safety Precautions � CAUTION instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. • In addition, a set of calibrated weighing scales shall be available and in good working arder. • Hoses shall be complete with leak-free disconnect couplings and in good condition. •...
  • Page 15 Safety Precautions CAUTION • Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification.
  • Page 16 Safety Precautions Explanation of symbols displayed on the indoor unit or outdoor unit. This symbol indicates that the appliance uses a flammable WARNING refrigerant. � If the refrigerant leaks and is exposed to an external ignition Caution, risk of fire source, there is a risk of fire.
  • Page 17 ACCESSORIES The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. The items are not included with the air conditioner must be purchased separately.
  • Page 18: Installation Instructions

    INSTALLATION INSTRUCTIONS NOTE ON ILLUSTRATIONS: Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly different. The actual shape shall prevail. Circuit breaker Wall Mounting Plate Drain hose Remote Controller Remote Control Holder Front Panel Communication Cable Outdoor Power Cable...
  • Page 19: Select Installation Location

    SELECT INSTALLATION LOCATION NOTE : PRIOR TO INSTALLATION Before installing the outdoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the outdoor unit Proper installation locations meet the following standards: ...
  • Page 20 0.32 (30) pipe size and length. 0.43 (40) NOTE: If the height or pipe length exceeds the limits specified in the table, please consult the Innovair for guidance. The maximum length and drop height based on models. Length of piping...
  • Page 21 INSTALLATION INSTRUCTIONS 1. Installing the Condensate Drain for the Outdoor Unit Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit. Please do the drainage work before the indoor unit and outdoor unit are connected. Otherwise, it will be difficult to install drainage elbow after the machine becomes immovable.
  • Page 22 Torque Requirement to connect pipes CAUTION WHEN CONNECTING REFRIGERANT PIPES, BE CAREFUL NOT TO USE EXCESSIVE TORQUE OR TO DEFORM THE PIPING IN ANY WAY. YOU SHOULD FIRST CONNECT THE LOW-PRESSURE PIPE, THEN THE HIGH-PRESSURE PIPE. MINIMUM BEND RADIUS ≥4in Radius (10cm) When bending connective refrigerant piping, the...
  • Page 23: Va C Uum Te S T Ing And Charging

    Connecting Piping to Outdoor Unit NOTE This section still needs to be operated according to the TORQUE REQUIREMENTS chart on the previous page. 1. Unscrew the cover from the packed valve on the side of the outdoor unit. Valve cover Outdoor unit 2.
  • Page 24: Connect Signal And Power Cables

    Connect signal and power cables - Before the Operation WARNING ALL WIRING WORK MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING ● DIAGRAM LOCATED INSIDE OF WIRE COVER OF THE OUTDOOR UNIT. BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK,TURN OFF THE MAIN POWER TO ●...
  • Page 25: Air Evacuation

    Air Evacuation NOTE : PREPARATIONS AND PRECAUTIONS Air and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which can damage the air conditioner, reduce its efficiency, and cause injury. Ensure to evacuate the air inside the indoor unit and pipes with vacuum pump.
  • Page 26 If there is a change in system pressure, refer to Gas Leak Check ● section for information on how to check for leaks. If there is no change in system pressure, unscrew the cap from ● Flare nut the packed valve (high pressure valve). Insert hexagonal wrench into the packed valve(high pressure valve) and open the valve by turning the wrench in a 1/4 counterclockwise turn.
  • Page 27 Electrical and Gas Leak Checks WARNING - RISK OF ELECTRIC SHOCK ALL WIRING MUST COMPLY WITH LOCAL AND NATIONAL ELECTRICAL CODES, AND MUST BE NSTALLED BY A LICENSED ELECTRICIAN. BEFORE TEST RUN Only perform test run after you have completed the following steps: •...
  • Page 28 Test Run Test Run Instructions DOUBLE-CHECK PIPE CONNECTIONS During operation, the pressure of the refrigerant circuit You should perform the Test Run for at least 30 minutes. will increase. This may reveal leaks that were not present Connect power to the unit. ●...
  • Page 29 SERIES INSTRUCCIONES DE USO E INSTALACIÓN (Para unidad externa) TODAS las fases de la instalación deben cumplir con los CÓDIGOS NACIONALES, ESTATALES y LOCALES. IMPORTANTE - Este documento es propiedad del cliente y debe permanecer con esta unidad. Estas instrucciones no cubren todas las variaciones en los sistemas ni contemplan todas las posibles contingencias que puedan surgir en relación con la instalación.
  • Page 30 CONTENIDO...
  • Page 31: Instrucciones De Seguridad

    INSTRUCCIONES DE SEGURIDAD...
  • Page 32 INSTRUCCIONES DE SEGURIDAD...
  • Page 33 INSTRUCCIONES DE SEGURIDAD...
  • Page 34: Precauciones De Seguridad

    PRECAUCIONES DE SEGURIDAD...
  • Page 35 PRECAUCIONES DE SEGURIDAD...
  • Page 36 PRECAUCIONES DE SEGURIDAD...
  • Page 37 PRECAUCIONES DE SEGURIDAD...
  • Page 38 PRECAUCIONES DE SEGURIDAD...
  • Page 39 PRECAUCIONES DE SEGURIDAD...
  • Page 40 PRECAUCIONES DE SEGURIDAD...
  • Page 41 PRECAUCIONES DE SEGURIDAD...
  • Page 42 PRECAUCIONES DE SEGURIDAD...
  • Page 43 PRECAUCIONES DE SEGURIDAD...
  • Page 44 PRECAUCIONES DE SEGURIDAD...
  • Page 45: Instrucciones De Instalación

    INSTRUCCIONES DE INSTALACIÓN...
  • Page 46 INSTRUCCIONES DE INSTALACIÓN...
  • Page 47 INSTRUCCIONES DE INSTALACIÓN...
  • Page 48 INSTRUCCIONES DE INSTALACIÓN...
  • Page 49 INSTRUCCIONES DE INSTALACIÓN...
  • Page 50 INSTRUCCIONES DE INSTALACIÓN...
  • Page 51 SERIES CONSIGNES D'INSTALLATION ET D'UTILISATION (Unite Exterieur) Toutes les phases de l'installation doivent être conformes aux CODES NATIONAUX, RÉGIONAUX et LOCAUX IMPORTANTE - Ce document est la propriété du client et doit rester avec cette unité. Ces instructions ne couvrent pas toutes les variations possibles dans les systèmes ni ne prévoient toutes les éventualités pouvant survenir lors de l'installation.
  • Page 52 TABLE DES MATIÈRES...
  • Page 53: Consignes De Sécurité

    CONSIGNES DE SÉCURITÉ...
  • Page 54 CONSIGNES DE SÉCURITÉ...
  • Page 55 PRÉPARATION POST-UTILISATION...
  • Page 56 CONSIGNES DE SÉCURITÉ...
  • Page 57 CONSIGNES DE SÉCURITÉ...
  • Page 58 CONSIGNES DE SÉCURITÉ...
  • Page 59 CONSIGNES DE SÉCURITÉ...
  • Page 60 CONSIGNES DE SÉCURITÉ...
  • Page 61 CONSIGNES DE SÉCURITÉ...
  • Page 62 CONSIGNES DE SÉCURITÉ...
  • Page 63 CONSIGNES DE SÉCURITÉ...
  • Page 64 CONSIGNES DE SÉCURITÉ...
  • Page 65 CONSIGNES DE SÉCURITÉ...
  • Page 66: Consignes D'installation

    CONSIGNES D’INSTALLATION...
  • Page 67 CONSIGNES D’INSTALLATION...
  • Page 68 CONSIGNES D'INSTALLATION...
  • Page 69 CONSIGNES D'INSTALLATION...
  • Page 70 CONSIGNES D'INSTALLATION...
  • Page 71 CONSIGNES D'INSTALLATION...
  • Page 72 CONSIGNES D'INSTALLATION...

Table of Contents