Installation and Operating Instructions Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
For more information go to www.P65Warnings.ca.gov. NOTICE Improper operation, product damage! Generation 4 Mini-Split (R454B) cannot be combined or paired with previous Mini-Split generations (R410A). Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 5
Do not operate your air conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water can cause electrical components to short circuit. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
• TA: The total area of the conditioned space connected by air ducts . Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 7
Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 8
≥ 50% of Anvmin ≥20mm ≥1.5m Anvmin ≥20mm' ≥ 50% of Anvmin ≤300mm ≤200mm ≤100mm Figure 1 Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 9
The minimum area for installation must be met. The minimum room area or minimum room area of conditioned space is based on releasable charge and total system refrigerant charge. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 10
The ventilation should safely disperse covered or enclosed. any released refrigerant and preferably expel it externally into the atmosphere. 10 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 11
Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 11...
Using the packing belt if necessary. It is recommended to keep all packaging items in case you may need them in the future. 12 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Description Model # Part # Wired Wall Thermostat for BMS-WT2-XXD 8-733-962-707 9K to 60K Duct unit Table 6 Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 13...
Connect the refrigerant pipes (Page 29) (Page 26) (Page 23) Perform a test run (Page 32) Figure 2 14 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly diff erent. The actual shape shall prevail. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 15...
>0.8in (2cm) >0.8in (2cm) Air inlet 31.5inx31.5in (80cmx80cm) Service access Ceiling checking orifice Floor Figure 8 Figure 5 16 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 17
9k / 12k 27.6 19.9 17.7 21.1 23.6 29.2 14.2 34.7 26.5 23.6 27.8 30.8 36.2 20.0 Table 7 Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 17...
Page 18
Drain pipe connection OD Ø25 ID Ø20 Drain pump ― Power supply connection ― Air discharge flange ― Table 9 18 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
The indoor unit must be completely aligned with the hole. Ensure that the unit and the hole are the same size before proceeding. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 19...
Page 20
An internal duct under-layer can be added to reduce noise. Figure 18 Keep the drain pipe sloping downwards at a gradient of at least 1/100. 20 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 21
Figure 24 Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 21...
Page 22
All the figures in this manual are for demonstration purposes only. The air conditioner you have purchased may be slightly diff erent in design, though similar in shape. 22 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 23
Air return flange Figure 33 Figure 32 Dimension: Duct joint for fresh air 24K~48k Ø126mm(5.0") Ø100mm(3.93") Ø125mm(4.92") Ø160mm(6.3") Figure 34 Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 23...
Page 24
Then connect the drainpipe to the connector D. Connector A Connector D Connector B Connector C Hose Figure 36 24 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 25
Unplug the pump power supply and water level switch cable. Detach the pump. Connector Pump Connector Figure 42 Figure 40 Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 25...
Page 26
Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan. 26 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 27
U or S pipe to catch (20.8in) or less odors that might otherwise come into the house. 10cm (4in) or more Figure 49 Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 27...
Page 28
The display board will connect to the CN10 (Refer to Indoor unit wiring Fill the water pan with 2 liters of water. diagram in page 27 for more details). 28 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Protected from prolonged periods of direct sunlight or rain ◦ Where snowfall is anticipated, take appropriate measures to prevent ice buildup and coil damage. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 29...
If water drains too slowly, it can freeze in the hose and flood the unit. Figure 58 Base pan hole of outdoor unit Seal Seal Drain fitting Figure 59 30 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Then,bolt the unit firmly to the brackets. If allowed, you can install the wall-mounted unit with rubber gaskets to reduce vibration and noise. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 31...
Figure 61 H: Unit height L: Height of the wall behind the unit A: Distance between unit and wall Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 33...
Be extra careful not to damage, kink, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit. 34 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Page 35
Clamp flaring block on the end of the pipe. The end of the pipe must extend beyond the edge of the flare form in accordance with the dimensions shown in the Table 6. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 35...
Align the center of the two pipes that you will connect. See Figure 32. Indoor unit tubing Flare nut Pipe Figure 69 36 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Exposed piping may cause condensation or may cause Repeat Steps 3 to 6 for the remaining pipe. burns when touched. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 37...
For 9K, 12K, 18K, 24K CN13 CN15 PUMP AUTO 5~7K 8~10K 11~14K 24~28K 29~33K 36~38K 48~49K Figure 77 Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 39...
Page 40
Electric The indoor unit needs to be ceiling mounted. control Ceiling box cover Display box Figure 80 40 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
The unit turn off The failure of the unit Capacity test The unit was turned off by controller. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 41...
500 microns in one (1) minute. Once evacuation is complete, turn off the vacuum pump and micron gauge, and close the valves on the manifold gauge set. 42 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
DO NOT remove refrigerant out of the equipment when linenset is shorter than 10ft (3meters). Use only recommended lineset minimum length of 10ft (3meters). Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 43...
All wiring must comply with local and national electrical codes and must be installed by a licensed electrician. 44 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024)
Test Run to double-check that all refrigerant pipe connection points do not have leaks. Refer to Gas Leak Check section for instructions. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 45...
Disposing of this product correctly will help ensure that the waste undergoes the necessary treatment, recovery and recycling. Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump - BTC 769203310 A (11.2024) | 47...
Page 48
United States and Canada Bosch Thermotechnology Corp. 65 Grove St. Watertown, MA 02472 Tel: 800-283-3787 www.bosch-homecomfort.us BTC 769203310 A / 11.2024 Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances.