User Manual
GT-5914 HART Protocol Module
4 analog input, 4 - 20 mA, 16 bit resolution, cage clamp, 18 pt removable terminal
Doc ID: 148117
2025-02-20

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GT-5914 and is the answer not in the manual?

Questions and answers

Summary of Contents for Beijer Electronics GT-5914

  • Page 1 User Manual GT-5914 HART Protocol Module 4 analog input, 4 - 20 mA, 16 bit resolution, cage clamp, 18 pt removable terminal Doc ID: 148117 2025-02-20...
  • Page 2 The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document.
  • Page 3: Table Of Contents

    11. Hardware Setup ..................19 11.1. Space Requirements ................19 11.2. Mount Module to DIN Rail ..............20 11.3. Mount Removable Terminal Block ............22 11.4. Connect Cables to Removable Terminal Block ..........23 Beijer Electronics, Doc ID: 148117 2025-02...
  • Page 5: About This Manual

    About This Manual 1. About This Manual This manual contains information on the software and hardware features of the Beijer Electronics GT-5914 HART Protocol Module. It provides in-depth specifications, guidance on installation, setup, and usage of the product. 1.1. Symbols Used in This Manual This publication includes Warning, Caution, Note and Important icons where appropriate, to point out safety-related, or other important information.
  • Page 6: Safety

    Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions! In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product. The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.
  • Page 7: About The G-Series System

    IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc. • Expansion Module - Expansion module types: Digital IO, Analog IO, and Special modules. • Messaging - The system uses two types of messaging: Service messaging and IO messaging. Beijer Electronics, Doc ID: 148117 2025-02...
  • Page 8: Io Process Data Mapping

    Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data. 2025-02 Beijer Electronics, Doc ID: 148117...
  • Page 9: Specifications

    Voltage range: 18 - 30 VDC Power dissipation: Max. 10 mA @ 24 VDC Wiring I/O cable max. 0.75 mm² (AWG18) Weight 60 g Module size 12 mm x 109 mm x 70 mm Beijer Electronics, Doc ID: 148117 2025-02...
  • Page 10: Analog Input Specifications

    4 common, field power 0V is common (AGND) 4.4. HART Specifications HART version Revision 5 Open circuit detection Imeas < 3.5 mA Short circuit detection Imeas > 22 mA HART devices per channel 1 device (single-drop, no multi-drop) 2025-02 Beijer Electronics, Doc ID: 148117...
  • Page 11: Wiring Diagram

    Wiring Diagram 5. Wiring Diagram Pin no. Signal description HART0+ HART0 AGND SHIELD HART1+ HART1- AGND SHIELD HART2+ HART2- AGND SHIELD HART3+ HART3- AGND SHIELD Not connected Not connected Beijer Electronics, Doc ID: 148117 2025-02...
  • Page 12: Led Indicator

    Analog input data range is within 4 – 20 mA. The analog input data range does not fall within 4 – 20 mA or disconnection. 6.2. LED Error Status Status Indication HART HART communication does not work. communication HART communication works normally. 2025-02 Beijer Electronics, Doc ID: 148117...
  • Page 13: Mapping Data Into The Image Table (Basic Mode)

    Bit 2 Bit 1 Bit 0 Control word 0 Variable data 1 Channel select Variable data 0 Channel select select select Variable data 3 Channel select Variable data 2 Channel select select select Reserved Reserved Beijer Electronics, Doc ID: 148117 2025-02...
  • Page 14 SV variable data 0 select: 1 → bit 01 Channel select: 0 → bit 00 Example 2: Variable data 3 = 1ch QV variable data 3 select: 3 → bit 11 Channel select: 1 → bit 01 2025-02 Beijer Electronics, Doc ID: 148117...
  • Page 15: Mapping Data Into The Image Table (Extend Mode)

    *** CMD error = Command error **** Run = Communication running Output image data (output image value: 4 byte) Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Control word 0 Beijer Electronics, Doc ID: 148117 2025-02...
  • Page 16 Output Data = 0x01, 0xFF (read response data), 0x00 (communication count), 0x00 If the number of response data exceeds 15 bytes, if you send the command (FF) by increasing communication count, you can check the response data after 15 bytes. Byte 0x01 0xFF 0x10 0x00 2025-02 Beijer Electronics, Doc ID: 148117...
  • Page 17: Configuration Parameter Data

    Retry time Filter time Reserved Reserved Mode: 0 = Basic mode, 1 = Extend mode. Retry time: Min. 5, max. 10 (hart communication retry time/If fail). Filter time: Min. 20, max. 255 (analog input filter). Beijer Electronics, Doc ID: 148117 2025-02...
  • Page 18: Supported Commands

    Read current and percent of range Read all dynamic variables and current Read message Read tag, descriptor, date Read primary variable sensor information Read primary variable output information Read final assembly number Common practice Read additional transmitter status command 2025-02 Beijer Electronics, Doc ID: 148117...
  • Page 19: Hardware Setup

    Installation position is valid vertical and horizontal. The drawings are illustrative and may be out of proportion. CAUTION NOT following the space requirements may result in damaging the product. Beijer Electronics, Doc ID: 148117 2025-02...
  • Page 20: Mount Module To Din Rail

    • GT-5XXX • GT-7XXX GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module. Mount to DIN rail Dismount from DIN rail 2025-02 Beijer Electronics, Doc ID: 148117...
  • Page 21 11.2.2. Mount GN-9XXX Module To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example GN-9251 or GN-9371, see the following instructions: Mount to DIN rail Dismount from DIN rail Beijer Electronics, Doc ID: 148117 2025-02...
  • Page 22: Mount Removable Terminal Block

    Hardware Setup 11.3. Mount Removable Terminal Block To mount or dismount a removable terminal block (RTB), see the instructions below. Mount a removable terminal block Dismount a removable terminal block 2025-02 Beijer Electronics, Doc ID: 148117...
  • Page 23: Connect Cables To Removable Terminal Block

    To connect/disconnect cables to/from the removable terminal block (RTB), see the instructions below. WARNING Always use the recommended supply voltage and frequency to prevent damage to the equipment and ensure optimal performance. Connect cable Disconnect cable Beijer Electronics, Doc ID: 148117 2025-02...