Carrier Gemini 38AX 07 Series Installation, Start-Up And Service Instructions Manual
Carrier Gemini 38AX 07 Series Installation, Start-Up And Service Instructions Manual

Carrier Gemini 38AX 07 Series Installation, Start-Up And Service Instructions Manual

Air-cooled condensing units with puron advance (r-454b) refrigerant
Table of Contents

Advertisement

Quick Links

Installation, Start-Up and Service Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
Detection of Flammable Refrigerants . . . . . . . . . . . . 2
Ignition Source Mitigation . . . . . . . . . . . . . . . . . . . . . 2
Ventilation Requirements . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION GUIDELINES . . . . . . . . . . . . . . . . . . . 2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . 6
Step 4 - Rig and Mount the Unit . . . . . . . . . . . . . . . 7
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Step 8 - Install Accessories . . . . . . . . . . . . . . . . . . 17
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
System Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Turn On Crankcase Heater . . . . . . . . . . . . . . . . . . . . 22
Preliminary Charge . . . . . . . . . . . . . . . . . . . . . . . . . . 22
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Start Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
OPERATING SEQUENCE . . . . . . . . . . . . . . . . . . . . . 29
Base Unit Controls . . . . . . . . . . . . . . . . . . . . . . . . . . 29
All Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
initial start) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Seasonal Maintenance . . . . . . . . . . . . . . . . . . . . . . . 30
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . 31
Comfort Alert Diagnostic Module . . . . . . . . . . . . . . 32
Compressor Protection . . . . . . . . . . . . . . . . . . . . . . 35
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fastener Torque Values . . . . . . . . . . . . . . . . . . . . . . 36
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 36
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53380057-01
with Puron Advance™ (R-454B) Refrigerant
Printed in U.S.A.
Form No. 38AX-7-14-01SI
Air-Cooled Condensing Units
DECOMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . .39
Page
WITH PURON ADVANCE™ - QUICK REFERENCE
APPENDIX B - WIRING DIAGRAMS. . . . . . . . . . . . .41
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Improper
installation,
maintenance, or use can cause explosion, fire, electrical shock or
other conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloths for brazing operations and have a fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult local
building codes and appropriate national electrical codes (in
U.S.A., ANSI/NFPA70, National Electrical Code (NEC); in
Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety-
alert symbol
instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning will result in personal injury or
death.
Before performing service or maintenance operations on unit,
turn off main power switch to unit and install lock(s) and
lockout tag(s). Ensure electrical service to rooftop unit agrees
with voltage and amperage listed on the unit rating plate. Do
not check compressor ohms at compressor terminals. Unit
may have more than one power switch.
38AX**07-14
adjustment,
alteration,
. When you see this symbol on the unit and in
DANGER
Pg 1
1-25
Gemini™
service,
Replaces: NEW

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Gemini 38AX 07 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier Gemini 38AX 07 Series

  • Page 1: Table Of Contents

    Gemini™ 38AX**07-14 Air-Cooled Condensing Units with Puron Advance™ (R-454B) Refrigerant Installation, Start-Up and Service Instructions CONTENTS EVACUATION, REMOVAL, AND RECOVERY ..39 DECOMMISSIONING ......39 Page APPENDIX A —...
  • Page 2: Detection Of Flammable Refrigerants

    Electronic leak detectors may be used to detect refrigerant leaks, but in the case of flammable refrigerants the sensitivity may not WARNING be adequate, or may need recalibration. Detection equipment shall be calibrated in a refrigerant-free area. Ensure that the de- UNIT OPERATION AND SAFETY HAZARD tector is not a potential source of ignition and is suitable for the Failure to follow this warning could cause personal injury,...
  • Page 3: Matching 38Ax Model To Evaporator Coil

    10 11 12 13 14 15 16 17 18 3 8 A X D T 1 2 A 0 A 6 A 0 A 0 A 0 Model Type Packaging 38AX = Carrier Condensing Unit 0 = Standard Puron Advance™ R-454B Refrigerant Electrical Options Type of Coil...
  • Page 4 Fig. 3 — 38AXD/Z 07-14 Base Unit Dimensions...
  • Page 5 Table 4 — 38AX Corner Weights STD. UNIT WT. CORNER A CORNER B CORNER C CORNER D CENTER OF GRAVITY UNIT HEIGHT UNIT 38AXZ*07 18 [457.2] 24 [609.6] 21 [533.4] 42 3/8 [1076.0] 38AXZ*08 18 [457.2] 24 [609.6] 21 [533.4] 42 3/8 [1076.0] 38AXZ*12 18 [457.2] 24 [609.6]...
  • Page 6: Installation

    Table 6 — 38AXD*12-14 Two Circuit Models – Physical Data UNIT 38AXD(T,U)12 38AXD(T,U)14 NOMINAL CAPACITY (tons) 12.5 OPERATING WEIGHT (lb) Refrigeration System No. Circuits / No. Comp. / Type 2 / 2 / Scroll 2 / 2 / Scroll Refrigerant Type Puron Advance™...
  • Page 7: Step 2 - Complete Pre-Installation Checks

    Table 4 to make the proper selection. adjustments for refrigeration specialties. Refer to Part 3 of the Step 3 — Prepare Unit Mounting Support Carrier System Design Manual for additional data and information on equivalent lengths. SLAB MOUNT Provide a level concrete slab that extends a minimum of 6 in.
  • Page 8 Table 8 — Liquid Line Diameter — Condenser Above Evaporator LINEAR LENGTH (ft) 0-25 26-50 51-75 76-100 101-125 126-150 151-175 176-200 UNIT NOMINAL CIRCUITS EQUIV. LINEAR TONNAGE 0-37 38-74 75-112 113-149 150-187 188-224 225-262 263-300 LENGTH (ft) Nominal Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Liquid Line Dia (in.)
  • Page 9 Table 9 — Suction Line Diameter — Condenser Above Evaporator a,b,c,d LINEAR LENGTH (ft) 0-25 26-50 51-75 76-100 101-125 126-150 151-175 176-200 SUCTION UNIT NOMINAL CIRCUITS RISER EQUIV.LINEAR TONNAGE 0-37 38-74 75-112 113-149 150-187 188-224 225-262 263-300 TYPE LENGTH (ft) Nominal Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Suction Line Dia (S) 1-1/8...
  • Page 10 Table 9 — Suction Line Diameter — Condenser Above Evaporator a,b,c,d (cont) LINEAR LENGTH (ft) 0-25 26-50 51-75 76-100 101-125 126-150 151-175 176-200 SUCTION UNIT NOMINAL CIRCUITS RISER EQUIV.LINEAR TONNAGE 0-37 38-74 75-112 113-149 150-187 188-224 225-262 263-300 TYPE LENGTH (ft) Nominal Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Suction Line Dia (S) 1-5/8...
  • Page 11 Table 10 — Liquid Line Diameter — Condenser Below Evaporator LINEAR LENGTH (ft) 0-25 26-50 51-75 76-100 101-125 126-150 151-175 176-200 UNIT NOMINAL CIRCUITS EQUIV.LINEAR TONNAGE 0-37 38-74 75-112 113-149 150-187 188-224 225-262 263-300 LENGTH (ft) Nominal Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Liquid Line Dia (in.) Max Lift (ft) Liquid Line Dia (in.)
  • Page 12 Table 11 — Suction Line Diameter — Condenser Level or Below Evaporator LINEAR LENGTH (ft) 0-25 26-50 51-75 76-100 101-125 126-150 151-175 176-200 UNIT NOMINAL CIRCUITS EQUIV.LINEAR TONNAGE 0-37 38-74 75-112 113-149 150-187 188-224 225-262 263-300 LENGTH (ft) Nominal Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Nominal Allowable Suction Line Dia (in.) 1 1/8 1 1/8...
  • Page 13: Liquid Lift

    LIQUID LIFT A liquid lift condition exists when the outdoor unit is located be- low the indoor (evaporator) unit and liquid flows vertically up in a portion of the liquid line. The vertical column of liquid reduces the available state point sub-cooling at the evaporator coil’s thermal expansion valve.
  • Page 14 When a single piece evaporator coil with two separate circuits is Installation of liquid line moisture indicating sight glass in each connected to a 38AXD, the lower coil circuit should be connected circuit is recommended. Locate the sight glass(es) between the to the 38AXD unit’s Circuit 1 so that the evaporator’s lower coil outlet of the filter drier and the TXV inlet.
  • Page 15 Select the filter drier for maximum unit capacity and minimum pressure drop. Complete the refrigerant piping from the indoor EQUALIZER LINE unit to the outdoor unit before opening the liquid and suction lines SENSING BULB at the outdoor unit. AIRFLOW INSTALL LIQUID LINE SOLENOID VALVE 15 DIAMS CKT 2...
  • Page 16: Make Piping Connections

    GTAC II, Module 4, System For linear line lengths longer than 125 ft (38 m), contact your local Dehydration. Carrier representative for system charge value. A2L CHARGING REQUIREMENTS WARNING In addition to conventional charging procedures, the following re- quirements shall be followed.
  • Page 17: Step 8 - Install Accessories

    • Ensure that the refrigerating system is earthed prior to charging the system with refrigerant. WARNING • Label the system when charging is complete (if not already). • Extreme care shall be taken not to overfill the refrigerating FIRE HAZARD system.
  • Page 18: Convenience Outlets

    informative plate. See Fig. 14 for power wiring connections to CONVENIENCE OUTLETS the unit contactor and terminal block and equipment ground. Provide a ground-fault and short-circuit over-current protection WARNING device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over- ELECTRICAL OPERATION HAZARD current Protection) device size.
  • Page 19: Field Control Wiring

    Figures 18 (38AXZ) and 19 Treat all units as electrically energized until the convenience (38AXD) depict typical connections to a Carrier 40RL fan coil outlet power is also checked and de-energization is confirmed. unit. Plan for field connections carefully and install control wir- Observe National Electrical Code Article 210, Branch ing correctly per the project plan.
  • Page 20: External Devices

    (Note 1) (Note 3) (Note 2) (Note 3) (Note 2) (Note 2) (Note 1) LEGEND Field Wiring NOTES: LEGEND 1. Connect only if thermostat requires 24-vac power source. Field Wiring 2. Connect W1 and W2 if supplemental heaters are installed. NOTES: Fig.
  • Page 21 Table 18 — 38AXZ 07-14 Electrical Data without Powered Convenience Outlet COMPRESSOR VOLTAGE POWER SUPPLY DISCONNECT SIZE NOMINAL RANGE NUMBER No. 1 No. 2 POWER UNIT SIZE Fuse or SUPPLY STAGES FLA (ea) HACR V-Ph-Hz Brkr 575-3-60 — — 38AXZD07 208/230-3-60 18.9 —...
  • Page 22: Step 10 - Wind Baffles For Low Ambient Control

    Table 21 — 38AXD 12-14 Electrical Data with Powered Convenience Outlet COMPRESSOR VOLTAGE POWER SUPPLY DISCONNECT SIZE NOMINAL RANGE NUMBER No. 1 No. 2 POWER UNIT SIZE Fuse or SUPPLY STAGES FLA (ea) HACR V-Ph-Hz Brkr 575-3-60 38AXDT12 208/230-3-60 14.0 18.6 46/46 60/60...
  • Page 23: Start-Up

    side pressures to equalize before starting compressor. If pressure check the circuit through the overload with an ohmmeter or con- do not equalize readily, charge vapor on low side of system to as- tinuity tester. sure charge in the evaporator. Refer to GTAC II, Module 5, ADVANCED SCROLL TEMPERATURE PROTECTION Charging, Recover, Recycling, and Reclamation for liquid (ASTP)
  • Page 24: Start Unit

    operating conditions. Accurate pressure gauge and temperature Start Unit sensing device are required. Connect the pressure gauge to the ser- Set the space thermostat to a set point above space temperature so vice port on the liquid line service valve. Mount the temperature that there is no demand for cooling.
  • Page 25 7.5 Tons Dual Stage R-454B Charging Chart Add Charge if Above the Curve Fig. 23 — 38AXZ*08 Charging Chart (RTPF)
  • Page 26 10 Tons Dual Stage R-454B Charging Chart Add Charge if Above the Curve Fig. 24 — 38AXZ*12 Charging Chart (RTPF)
  • Page 27 12.5 Tons Dual Stage R454B CHARGING CHART 12.5 Tons Dual Stage R-454B Charging Chart (Unit must run both compressors and outdoor fans on high speed) 59.9 48.8 Add Charge if Above the Curve 37.7 26.6 Remove Charge if Below the Curve 15.5 -6.7 1034...
  • Page 28 10 Tons Circuit B R454B CHARGING CHART 10 Tons Circuit B R-454B Charging Chart 10 Tons Circuit A R454B CHARGING CHART 10 Tons Circuit A R-454B Charging Chart (Unit must run both compressors and (Unit must run both compressors and outdoor fans on high speed) outdoor fans on high speed) 59.9...
  • Page 29: Operating Sequence

    38AXD 12, 14 (Two Circuits/3-Stage Cooling) OPERATING SEQUENCE On a thermostat call for Cooling the indoor (supply) fan motor Base Unit Controls runs (subject to there being no fan fault or shutdown condition, see Indoor (Supply) Fan section). Thermostat output Y1 is energized; INDOOR (SUPPLY) FAN terminal Y1 at 38AXD unit receives 24-v and the Compressor If the thermostat fan operation is selected as Continuous, the...
  • Page 30: Quarterly Inspection (And 30 Days After  Initial Start)

    NOTE(S): • Power wire connections a. The above list may not include all maintenance items. Inspection intervals may vary depending on climate and opening hours. Consult your Carrier dealer • Fuses ready about a service contact for seasonal inspections b. Monthly maintenance items and outdoor unit rinsing may be performed by the •...
  • Page 31: Service

    Place terry cloth shop towel inside unit immediately under SERVICE component(s) to be serviced and prevent lubricant run-offs Refrigeration System through the louvered openings in the base pan. Perform required service. WARNING Remove and dispose of any oil contaminated material per local codes.
  • Page 32: Comfort Alert Diagnostic Module

    Outdoor Fan 2 Outdoor Coil Outdoor Fan 1 Service Valves Fig. 29 — Typical Exterior, Two-Circuit Unit Fig. 31 — Typical Interior, Two-Circuit Unit (38AXD*14 shown) (38AXD*14 shown) FACTORY HIGH-FLOW ACCESS PORTS The brass fittings are two-piece High Flow valves, with a recep- tacle base brazed to the tubing and an integral spring-closed There are two additional access ports in the system - on the suction check valve core screwed into the base.
  • Page 33 anti-recycle time delay to compressor cycling. Each compressor main power to the 38AX unit be recycled after the cause for the has a separate CADM module. Alert condition has been detected and corrected. The CADM detects causes for electrical and system related fail- Power ures without any sensors.
  • Page 34 Table 26 — LED Status Codes STATUS LED STATUS LED DESCRIPTION STATUS LED TROUBLESHOOTING INFORMATION Green “POWER” Module has power Supply voltage is present at module terminals 1. Compressor protector is open 2. Condensing unit power disconnect is open Thermostat demand signal Y is 3.
  • Page 35: Compressor Protection

    RTPF coils. This cleaner is The heater minimizes absorption of liquid refrigerant by oil in the available from Carrier Replacement parts division as part number crankcase during brief or extended shutdown periods. The heater P902-0301 for a one gallon container, and part number P902-0305 is wired to cycle with the compressor;...
  • Page 36: Fastener Torque Values

    Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up-and-down motion. Avoid spraying in horizontal pattern to minimize potential for fin damage. Rigid Ensure cleaner thoroughly penetrates deep into finned areas. Support Interior and exterior finned areas must be thoroughly cleaned. Cover 10.
  • Page 37 Table 29 — Troubleshooting PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open 1. Power off. 1. Restore power. 2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse. 3. No control power. 3.
  • Page 38 Table 29 — Troubleshooting (cont) PROBLEM SOLUTION COMPRESSOR RUNNING BUT COOLING INSUFFICIENT Suction Pressure Low 1. Refrigerant charge low. 1. Add refrigerant. 2. Head pressure low. 2. Check refrigerant charge. Check outdoor-air fan thermostat settings. 3. Air filters dirty. 3. Clean or replace filters. 4.
  • Page 39: Evacuation, Removal, And Recovery

    EVACUATION, REMOVAL, AND RECOVERY DECOMMISSIONING When breaking into the refrigerant circuit to make repairs - or for Before carrying out this procedure, it is essential that the techni- any other purpose - conventional procedures shall be used. How- cian is completely familiar with the equipment and all its detail. It ever, for flammable refrigerants it is important that best practice be is recommended good practice that all refrigerants are recovered followed, since flammability is a consideration.
  • Page 40: Appendix A - Air Conditioner And Heat Pump With Puron Advance™ - Quick Reference Guide

    APPENDIX A — AIR CONDITIONER AND HEAT PUMP WITH PURON ADVANCE™ – QUICK REFERENCE GUIDE • Puron Advance™ (R-454B) refrigerant operates at 50 per- • POE oils absorb moisture rapidly. Do not expose oil to cent to 70 percent higher pressures than R-22. Be sure that atmosphere.
  • Page 41: Appendix B - Wiring Diagrams

    APPENDIX B — WIRING DIAGRAMS UNIT ELECTRICAL CHARACTERISTICS DIAGRAM NUMBER PAGE NUMBER 575-3-60 38AU002408 38AXZ*07 208/230-3-60 38AU002409 460-3-60 38AU002409 575-3-60 38AU002411 38AXZ*08 208/230-3-60 38AU002412 460-3-60 38AU002413 575-3-60 38AU002415 38AXZ*12 208/230-3-60 38AU002416 460-3-60 38AU002417 575-3-60 38AU002422 38AXZ*14 208/230-3-60 38AU002423 460-3-60 38AU002424 575-3-60 38AU002418 38AXD*12...
  • Page 42 APPENDIX B — WIRING DIAGRAMS (cont) Fig. A — Single Circuit Wiring Diagram, 6 Ton — 575-3-60 Unit...
  • Page 43 APPENDIX B — WIRING DIAGRAMS (cont) Fig. B — Single Circuit Wiring Diagram, 6 Ton — 208/230-3-60 and 460-3-60 Unit...
  • Page 44 APPENDIX B — WIRING DIAGRAMS (cont) Fig. C — Single Circuit Wiring Diagram, 7.5 Ton — 575-3-60 Unit...
  • Page 45 APPENDIX B — WIRING DIAGRAMS (cont) Fig. D — Single Circuit Wiring Diagram, 7.5 Ton — 208/230-3-60 Unit...
  • Page 46 APPENDIX B — WIRING DIAGRAMS (cont) Fig. E — Single Circuit Wiring Diagram, 7.5 Ton — 460-3-60 Unit...
  • Page 47 APPENDIX B — WIRING DIAGRAMS (cont) Fig. F — Single Circuit Wiring Diagram, 10 Ton — 575-3-60 Unit...
  • Page 48 APPENDIX B — WIRING DIAGRAMS (cont) Fig. G — Single Circuit Wiring Diagram, 10 Ton — 208/230-3-60 Unit...
  • Page 49 APPENDIX B — WIRING DIAGRAMS (cont) Fig. H — Single Circuit Wiring Diagram, 10 Ton — 460-3-60 Unit...
  • Page 50 APPENDIX B — WIRING DIAGRAMS (cont) Fig. I — Single Circuit Wiring Diagram, 12.5 Ton — 575-3-60 Unit...
  • Page 51 APPENDIX B — WIRING DIAGRAMS (cont) Fig. J — Single Circuit Wiring Diagram, 12.5 Ton — 208/230-3-60 Unit...
  • Page 52 APPENDIX B — WIRING DIAGRAMS (cont) Fig. K — Single Circuit Wiring Diagram, 12.5 Ton — 460-3-60 Unit...
  • Page 53 APPENDIX B — WIRING DIAGRAMS (cont) Fig. L — Dual Circuit Wiring Diagram, 10 and 12.5 Ton — 575-3-60 Unit...
  • Page 54 APPENDIX B — WIRING DIAGRAMS (cont) Fig. M — Dual Circuit Wiring Diagram, 10 and 12.5 Ton — 208/230-3-60 Unit...
  • Page 55 APPENDIX B — WIRING DIAGRAMS (cont) Fig. N — Dual Circuit Wiring Diagram, 10 and 12.5 Ton — 460-3-60 Unit...
  • Page 56: Operation

    APPENDIX C — LOW AMBIENT OPTION Units with the factory-installed low ambient control option are Troubleshooting equipped with a solid-state head pressure control which regulates OBSERVATION POSSIBLE REMEDY fan speed. A temperature sensor, mounted on either circuit 1 (38AXZ units) or both circuits 1 and 2 (38AXD units) of the out- All fans: Check power and wiring door coil controls the speed of approved outdoor fan motors in or-...
  • Page 57 APPENDIX C — LOW AMBIENT OPTION (cont) Low Ambient Sensor must be positioned on Feeder Tube (bottom tube on Top Header) between Header Tube and Tube Sheet Low Ambient Sensor must be positioned on Feeder Tube Low Ambient Sensor (eighth from bottom) must be positioned between Header Tube on Feeder Tube...
  • Page 58 APPENDIX C — LOW AMBIENT OPTION (cont) Low Ambient Sensor 2 must be positioned on Feeder Tube (second from top on the Top Header) between Header Tube and Tube Sheet Low Ambient Sensor 2 must be positioned on Feeder Tube (second from bottom on the Top Header) between Header Tube and...
  • Page 59 APPENDIX C — LOW AMBIENT OPTION (cont) Fig. Q — Wind Baffles...
  • Page 60 APPENDIX C — LOW AMBIENT OPTION (cont) Table A — Wind Baffle Dimension DIMENSIONS - INCHES UNIT BAFFLE LEFT SIDE 28 1/2 29-3/4 35-1/4 1-1/4 9-1/4 17-1/4 25-1/4 33-1/4 — 38AXZ 07 BACK 40-3/4 41-1/2 35-1/4 4-1/4 11-1/4 18-1/4 25-1/4 32-1/4 —...
  • Page 62 © 2025 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53380057-01 Printed in U.S.A. Form No. 38AX-7-14-01SI Pg 62 1-25 Replaces: NEW...
  • Page 63: Start-Up Checklist

    START-UP CHECKLIST (Remove and use for Job File) NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this Installation, Start-Up, and Service document.
  • Page 64 ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ © 2025 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53380057-01 Printed in U.S.A. Form No. 38AX-7-14-01SI CL-2 1-25...

Table of Contents

Save PDF