Manual
SENTRON
SENTRON Powercenter 3000
Edition
08/2024
www.siemens.com/lowvoltage

Advertisement

loading
Need help?

Need help?

Do you have a question about the SENTRON Powercenter 3000 and is the answer not in the manual?

Questions and answers

Summary of Contents for Siemens SENTRON Powercenter 3000

  • Page 1 Manual SENTRON SENTRON Powercenter 3000 Edition 08/2024 www.siemens.com/lowvoltage...
  • Page 2 Introduction Safety information SENTRON Description IoT data platforms Installing, connecting, SENTRON Powercenter 3000 commissioning Equipment Manual Functions Application examples Service and maintenance FAQs Technical data Dimensional drawings Appendix Technical support V1.8 08/2024 L1V30579222003-10...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4 Mounting instructions....................... 25 Connecting the device...................... 26 4.3.1 Instructions for connection....................26 4.3.2 Connecting the ground conductor..................27 4.3.3 Connecting the power supply.................... 28 Connecting the device to networks................... 29 Commissioning a device....................30 SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 5 External Ethernet interface with the intranet..............33 4.6.2.1 Performance features of the external Ethernet interface............ 34 Security features....................... 34 4.7.1 Security performance features of the SENTRON Powercenter 3000........35 4.7.2 Further recommended security measures................37 Functions............................39 Commissioning......................... 41 5.1.1 Establishing a connection to the device prior to commissioning.........
  • Page 6 SENTRON Powercenter 3000 as a Modbus gateway............113 5.10.1 Addressing via the SENTRON Powercenter 3000 gateway..........114 5.10.2 Method of operation of the SENTRON Powercenter 3000 Modbus TCP gateway....115 5.11 Time synchronization......................115 5.11.1 Time synchronization of the connected devices..............116 5.12...
  • Page 7 Table of contents 6.8.1 Security aspects of the SENTRON Powercenter 3000 as a gateway........130 Interface with a wireless LAN interface................131 6.9.1 Security aspects of the wireless LAN interface..............131 6.10 Interface with a cellular network..................131 Service and maintenance........................132 Repair instructions......................
  • Page 8 Table of contents Glossary.............................. 159 Index..............................165 SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 9 SENTRON Powercenter 3000. Reference documents You can find further details in the following documents: Title Article number Quick Installation Guide for SENTRON Powercenter 3000 L1V30579222002 (https://support.industry.siemens.com/cs/ww/en/view/109766001) Further information Find out about additional training courses on offer via the following links: • Excel tool for creating annual reports based on the energy data archived by Powercenter 3000 (https://support.industry.siemens.com/cs/ww/en/view/109782120)
  • Page 10 Installation of expansions can damage the device, machine or plant. Device or system expansions can violate safety rules and regulations relating to interference suppression. The warranty is voided if you cause faults in the device due to installation or replacement of system expansions. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 11 In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks.
  • Page 12 Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to...
  • Page 13 Product or any OSS components contained in it if they are modified or used in any manner not specified by SIEMENS. The license conditions may contain disclaimers that apply between you and the respective licensor.
  • Page 14 Description Product description Overview The SENTRON Powercenter 3000 has high industrial functionality. • Compact dimensions • Highly robust SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 15 Because of this, there is no need to press the ON/OFF switch to switch on the device. 3.2.1 Operating displays of the devices LED name Status Description PC ON/WD No voltage Green BIOS active *) See: Settings → Actions → Device SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 16 This section contains the range of accessories available at the time of production of the manual. Wall mounting 6AG4021-0AA20-0AA2 Upright mounting 6AG4021-0AA20-0AA3 Upright mounting on DIN rails 6AG4021-0AA20-0AA5 Lithium battery A5E44491494 You will find further information on the Internet at: • Service & Support (https://support.industry.siemens.com/cs/ww/en/) SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 17 Not used 24 V DC Power supply Ethernet interface Short code Meaning LED 1 Off: 10 Mbps Lights up green: 100 Mbps Lights up yellow: 1000 Mbps LED 2 Lights up yellow: Connection established Flashing: Activity SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 18 NOTICE Damaged device – Ensure that the damaged device is not installed and commissioned. – Label the damaged device and keep it locked away. – Send the device for repair immediately. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 19 Enter the identification data of your rating plate in the following table. Order number 7KN1310-0MC00-0AA8 Production version (FS) Serial number (S) Production version Ethernet address 1 (MAC) Ethernet address 2 (MAC) See also Technical data (Page 148) SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 20 Make sure that the following clearances are maintained from other components or an enclosure wall: • Below the device: ≥ 50 mm (2 in.) • Above the device: ≥ 50 mm (2 in.) Order numbers for available mounting accessories: Wall mounting: 6AG4021-0AA20-0AA2 Upright / wall mounting: 6AG4021-0AA20-0AA3 Upright mounting / DIN rail: 6AG4021-0AA20-0AA5 SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 21 Mark out the mounting holes. Drill the mounting holes. Place the wall plugs in the drilled holes. Fasten the mounting bracket with 2 screws. Screw the device to the mounting bracket with the two screws supplied. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 22 Procedure – upright mounting on DIN rails Place the mounting bracket on the rear of the device. Fasten the mounting bracket with two screws supplied. Place the device on the mounting bracket onto the DIN rail. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 23 Pay attention to the orientation of the keyholes in the mounting bracket. Fasten the mounting bracket with the 4 screws supplied. Place the device with the mounting bracket onto the mounting surface. Screw the device on. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 24 Mounting on DIN rails The standard rail mounting is suitable for horizontal and vertical mounting of the device. Requirements • A SIEMENS 35-mm DIN rail TH35-15 in accordance with EN 60715:2001 The DIN rail is mounted. • A DIN rail clip NOTE Use only the screws supplied to mount the DIN rail clip.
  • Page 25 SEL1200 / SEL1400. That increases the availability in case of faults of individual devices. Alignment of the interfaces In standard rail mounting, the interface side of the device can point either upward or downward, right or left. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 26 • Connect only peripheral devices that are suitable for industrial use in accordance with EN 61000-6-2 and IEC 61000-6-2. • Peripheral devices that are not hotplug-capable must only be connected when the power supply of the device is switched off. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 27 • Never operate the device without a ground conductor. • Remove the nonconforming device from use immediately and label it as nonconforming. Requirements • T20 screwdriver • Cable lug for M4 • Ground conductor with minimum conductor cross-section 2.5 mm (12 AWG) SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 28 NEC Class 2 or an energy-limited circuit in accordance with UL/CSA 61010-1. NOTE The 24 VDC power supply must meet the voltage requirements specified in Technical data (Page 148). SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 29 Ethernet You can use the integrated Ethernet interfaces (10/100/1000 Mbps) for communication with the devices and applications stated in Application examples (Page 118). You network the SENTRON Powercenter 3000 and other devices via Industrial Ethernet. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 30 Alternatively, brief repeated pressing causes a restart of the SENTRON Powercenter 3000. 3. Press briefly 5 times until the LED "MAINT" flashes red to reset the device to the delivery condition. SENTRON Powercenter 3000 has to be commissioned again. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 31 Installing, connecting, commissioning 4.6 Interfaces of the SENTRON Powercenter 3000 Further information If the SENTRON Powercenter 3000 is disconnected from the power supply, the current processing status is backed up, if possible. The time continues to be kept during the power failure for as long as the battery remains active.
  • Page 32 Installing, connecting, commissioning 4.6 Interfaces of the SENTRON Powercenter 3000 • Powercenter 1000 with the following CP-COM devices: – 5SL6 COM miniature circuit breaker with EM or RCM version – 5SV6 COM arc fault detection device – 5ST3 COM combined auxiliary switch and fault signal contact –...
  • Page 33 Installing, connecting, commissioning 4.6 Interfaces of the SENTRON Powercenter 3000 Typical devices of a smart assembly network SENTRON Powercenter 3000 SENTRON Web-Interface powerconfig Ethernet-Interface X2P1 Ethernet Switch e.g. SCALANCE Ethernet RJ45 Patch cable CAT5e POWERCENTER 1000 Modbus device PAC4200 3VA line...
  • Page 34 • Interface with web browsers. Various browser types are supported. • Interface to Insights Hub, the Siemens operating system for the Internet of Things (IoT). • MQTT interface to different cloud systems for SENTRON and other Modbus devices •...
  • Page 35 If the project is to be used downstream in SENTRON Powerconfig, version (see Compatibility matrix (Page 139)) or higher is required. • IP firewall: In SENTRON Powercenter 3000, up to 5 different privileged IP addresses or IP subnets, the so-called firewall allowlist, can be selected. If this option is used, all further IP addresses/IP address ranges or subnets are excluded from communication if they are not entered in the firewall allowlist.
  • Page 36 The login is deactivated on delivery. After activation, the web interface switches to encrypted communication via https. • Security tests: SENTRON Powercenter 3000 is regularly subjected to security tests and is certified to Achilles Level 2. Further information on the scope of the Achilles certification tests can be found under the following link (https://support.industry.siemens.com/cs/us/en/view/109816857).
  • Page 37 4.7.2 Further recommended security measures The security disclaimer always applies, see Security instructions. Nevertheless, SENTRON Powercenter 3000 provides the most important security features for operation in an intranet. Moreover, the following measures are recommended against attacks from the Internet, using special devices such as Ethernet switches or IP routers: •...
  • Page 38 • Physical access protection: Unauthorized access or manipulation of networks and electronic devices is possible without leaving visible traces. For that reason, physical access protection for the installed SENTRON Powercenter 3000 is necessary. The SENTRON Powercenter 3000 should also be protected from unauthorized access when it is not installed, because the device could be manipulated without leaving visible traces.
  • Page 39 Security • Login for the web interface using https (http via TLS [Transport Layer Security]) • Firewall functions and encrypted communication, e.g. MQTT via TLS. See section Security features (Page 34) SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 40 The external and internal communication interfaces have been deliberately separated to ensure the security and functional independence. The device types mentioned in "Internal Ethernet interface for the smart assembly network (Page 31)" are supported in SENTRON Powercenter 3000. In future versions, additional device types will be supported. SENTRON Powercenter 3000...
  • Page 41 Assign a new IP address via the powerconfig network scan Connect the X2P1 internal Ethernet interface of the SENTRON Powercenter 3000 to the plant network and ensure that a network connection with your engineering PC is possible. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 42 IP configuration does not yet match the subnet. The IP address, subnet mask and gateway can be changed as long as you set the switch to "Unlocked". Then load the changed communication parameters onto the device. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 43 Commissioning via SENTRON Powercenter 3000 web user interface 5.1.3.1 Commissioning by means of network scan To commission the SENTRON Powercenter 3000 by means of a network scan, proceed as follows: • Click the three dots in the top line. A context menu appears: •...
  • Page 44 NOTE Calculating device licenses A license is required for every device that is used in SENTRON Powercenter 3000. Communications modules (e.g. COM100/COM800) and CP-COM slave devices are an exception to this rule. In the case of a SENTRON Powercenter 1000/1100, which counts as one device, the slave devices that are connected to it do not require separate licenses.
  • Page 45 90°. • Use button ⑤ to center the display. When a scan is running in a subnode, a progress indicator appears at this node. Features at network nodes SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 46 3. Import the project. Variant 2: Import a Modbus device type and then create the device as an instance. You can find the exact procedure in section Integrating Modbus devices via type import (Page 49). SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 47 1. Click the three dots in the top line. A shortcut menu appears: 2. Set a check mark next to "Edit mode". Edit mode is activated. 3. Click the "+" button. The window "Add to project" appears. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 48 If the check was successful, the brief message "Action completed successfully" appears. Otherwise, the message "Connection failed" is displayed. In that case, check the communication parameters used and whether the device is in operation. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 49 Modbus devices using Powerconfig as an alternative. You can find the Power Device Engineer tool on the download page (https://support.industry.siemens.com/cs/document/109814517/update-version-sentron- power-device-engineer-v7-0?dti=0&lc=en-WW) with the current firmware version of SENTRON Powercenter 3000. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 50 • "RTU Communication Only" specifies that the device supplies the data via a serial communication, e.g. Modbus RTU. • "Offset" causes the value "1" to always be subtracted in the register addressing of the data points. • "Endian Byte Order" - only "Big" is supported. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 51 Functions 5.1 Commissioning The next step is to edit the data points of the Modbus device. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 52 ACTIVE_ENERGY_EXPORT_T­ Energy 15min float Active energy exported ARIFF2 at tariff 2 ACTIVE_ENERGY_IMPORT_T­ Energy 15min float Active energy imported ARIFF1 at tariff 1 ACTIVE_ENERGY_IMPORT_T­ Energy 15min float Active energy imported ARIFF2 at tariff 2 SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 53 Total power factor eous ACTIVE_POWER_MAX Energy instantan­ float Maximum total active eous power APPARENT_POWER_MAX Energy instantan­ float Maximum total apparent eous power POWER_FACTOR_MAXTS Energy instantan­ float eous Maximum total power factor SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 54 Explanation Description (English/German) Display name Data Type The basic data type in the Modbus register (without specification of the register width) • FLOAT • • UINT • STRING • BOOL Unit Displayed unit SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 55 The input step Device Configuration is not applicable for import in SENTRON Powercenter 3000, and the configuration can be completed by saving. Now click on the Save button to save the configuration as a <*.json> file. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 56 Import Modbus device type Once you have created a Modbus device type using the Power Engineer tool, you can import it into SENTRON Powercenter 3000 as follows in the web interface: 1. Settings → Actions → Project → Import Modbus Device Types 2.
  • Page 57 Once a device instance has been created, a table widget is created in the device dashboard in SENTRON Powercenter 3000 for each group of properties from the Power Device Engineer: Once a device instance has been created, a table widget is created in the device dashboard in...
  • Page 58 There, the individual devices, including SENTRON Powercenter 3000, will be supplied with network addresses and other parameters and operated in the normal way. The connected devices are located in the project tree and in the gateway hierarchy below the SENTRON Powercenter 3000. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 59 Because the identification and communication data can be changed through the web user interface of the SENTRON Powercenter 3000, the setup data can be kept consistent and further processed in SENTRON powerconfig. You will find further details in FAQs (Page 139). SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 60 The data points can be grouped in categories. Some typical categories in the power distribution system are current, voltage L-N, etc. The categories can be given names in each of the languages of the web user interface. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 61 Attributes of a data Description Notes point Language-specific name In SENTRON Powercenter 3000, data points are handled in various lan­ guages, e.g. in the web user interface. These names can be defined for the individual languages here. Uniform name This attribute is optional. It is used by SENTRON Powercenter 3000 for uni­...
  • Page 62 For that reason, we recommend creating a Modbus device in full and in detail, testing it and copying this Modbus device multiple times within the project with copy and paste or exchanging it between projects with "Export device(s)" and "Import device(s)". SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 63 If a future version of the Modbus device is to be operated on a RS485 network, a Modbus address is required. The addressing via the Modbus gateway (see section SENTRON Powercenter 3000 as Modbus gateway (Page 113)) is implemented via the external identifier. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 64 Functions 5.1 Commissioning To ensure communication with the slightly slower RS485 devices, it is recommended that the response time of 0 ms be set to 15 ms or higher in the communication parameters. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 65 2. Choose the menu item "Go online". The measured variables are displayed in categories in the "Measurements" view. 3. Check the measured variables and their values and correct the parameter settings, if necessary. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 66 24 23 16 15 Highest byte 2nd byte Seconds 3rd byte Seconds 4th byte Seconds Seconds Modbus register address +0 Modbus register address +1 High Byte Low Byte High Byte Low Byte SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 67 For example, a device view showing the most important information about a device is available for each device. In the case of the 3VA molded-case circuit breaker, this includes the circuit breaker health indicator and the remaining service life, among other things. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 68 The contents of the web user interface, including graphics displayed, can be printed using the browser print function (key combination <Ctrl> + <P>). NOTE The project tree and menu commands are not printed. It is also possible to export to PDF or graphics files. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 69 • Ten different languages can be selected for the web user interface via the globe icon ⑤ – German – English – Spanish – French – Italian – Polish – Portuguese – Russian – Turkish – Chinese SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 70 Top left corner is marked - clarification is required • Click on the plus symbol ⑨ to create new tabs for different work areas (e.g. Room 1, Room 2) in the Overview area. See section Dashboards (Page 77). SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 71 1. Click the icon below in the project navigation: A menu appears. 2. Set a check mark next to "Edit mode". Edit mode is activated. The icon below indicates that edit mode is active: SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 72 5.2 Web user interface 3. When you click a device, you can edit the specific properties, as shown in the example screenshot below: 4. To exit edit mode, click the x in the display: SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 73 3. Drag and drop the device/folder onto another device/folder to add it below the respective device/folder. 4. Deactivate Edit mode. Information on deactivation can be found in chapter Editing devices (Page 71). SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 74 Widgets can only be changed when the web user interface is not write-protected. See chapter Write protection in the web user interface (Page 80). Widget library The widget library shows all available display elements for the selected object, e.g. a device. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 75 In the current version, the full function scope of the classical view has not yet been integrated in the new view. The following new functions are available however: • Benchmark widget (new view) (Page 76) • Archive graph for energy values (new view) (Page 77) SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 76 In the section above the bar diagram, the energy consumption of all the selected measuring devices in the basic date range and the reference range are totaled and displayed as an absolute value. The change compared to the basic date range is displayed as a relative change. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 77 4. Position the widget where you want it to appear in the menu by clicking it with the left mouse button, holding the button down and dragging the widget to the desired position. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 78 1. Choose the menu that you wish to delete, "My Dashboard" in the screenshot example. 2. Click the button next to the name of the menu. 3. Confirm deletion in the confirmation prompt. The menu is erased. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 79 5.2 Web user interface 5.2.2 Settings via the web user interface SENTRON Powercenter 3000 is the first SENTRON device to provide a way of making important parameter settings via the web interface, alongside the option provided via SENTRON Powerconfig. In particular, these settings are for •...
  • Page 80 Security aspects must be considered when making these settings. All settings are saved in a <*.splx> project file, which can be exported via Settings → Actions → Project and used in SENTRON Powerconfig or another SENTRON Powercenter 3000. 5.2.3 Write protection in the web user interface.
  • Page 81 During the initial login as "admin", the password must be changed. The password for the "guest" role can also be changed at this time. The password for the guest user can only be changed in the Supervisor role, i.e. by the admin user. → SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 82 1. When the login is activated, access to the corresponding interface is only possible via https. http communication is automatically redirected to port 443 (see section Security performance features of the SENTRON Powercenter 3000 (Page 35)). 2. When the login is activated, access with SENTRON Powerconfig is no longer possible via the corresponding interface.
  • Page 83 Internet-Router & Firewall Web-Interface IP-Address: 192.168.0.1 IP-Address: 192.168.0.3 Ethernet Ethernet Switch z. B. SCALANCE Redirect-URI: https://220.0.0.1:443 No action required Ethernet-Interface X1P1 IP-Address: 192.168.0.2 powerconfig SENTRON Powercenter 3000 smart assembly network Redirect URI: https://220.0.0.1.443 SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 84 5.3.1 Data records SENTRON Powercenter 3000 can record the energy counters and the average values 2 of connected SENTRON devices every 15 minutes. In this way, the energy balance for each device is acquired as import and export and can be used as a basis for the energy management according to ISO 50001.
  • Page 85 For toggling between archive 1 and archive 2 • The period for display and export with the archive chart can be configured user-defined or in time units, e.g. Today, Current week, ..SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 86 • If you find cells containing "NaN" in the export file, this could be for a number of reasons, e.g. archiving of the data point is not activated, device is not making the data point available or archive service in the Powercenter 3000 is not activated. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 87 The period "Yearly" is not recommended with multiple devices because the .zip file can be over 10 Mbytes in size. Various email servers could reject it. NOTE The energy counters of devices that only offer one tariff are exported as high tariff or tariff 1. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 88 If, for example, the cursor is positioned on the resolution "15 minutes" on the X axis, and this is changed by operating the scroll wheel of the mouse so that a larger time range is to SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 89 See "Settings → General → Miscellaneous". – Date – Time of day – and all other columns: Device designation as in navigation area 3. Row 3 and all following rows, the values acc. to the column heading SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 90 SENTRON Powercenter 3000. Statistics can be retrieved both globally for the whole SENTRON Powercenter 3000 and for each individual device. • Click the project name in the navigation area to retrieve the statistics for the whole SENTRON Powercenter 3000. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 91 Time stamp of the first value Recording period • 1 day for archive 1 • 420 days for archive 2 Number of enabled data points Min. and max. values are also included in the number displayed. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 92 On many SENTRON devices, the cycle can be varied between 3 seconds and 31536000 seconds (= one year). For archiving, SENTRON Powercenter 3000 uses the cycle of the device that is actually set, provided that this set value can be read from the device.
  • Page 93 4. Configure the alarm in line with your requirements. 5. Save the alarm. The alarm appears in the list and is displayed as defined in the configuration: - Disabled alarm - Enabled alarm SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 94 "Value" field. See the graphic below for the effects of delay and hysteresis. Severity Specifies a severity class for the limit value violation or the generated message: • Information • Warning • Alarm SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 95 By defining the severity/alarm class, you specify whether and how you are informed when an alarm is activated. Under Settings → Notifications, you specify the severity an alarm must have for you to be informed in the web user interface or by email. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 96 Benefits: Insights Hub (https://new.siemens.com/global/en/products/software/mindsphere.html) is a cloud-based, open IoT (Internet of Things) operating system from Siemens which allows you to connect your low-voltage power distribution system to the digital world. SENTRON Powercenter 3000 is used to transfer data, such as energy values or statuses, from the smart switchgear assembly to Insights Hub in settable cycles.
  • Page 97 SENTRON Powermind, and displayed in dashboards, curves and comparisons. Further details on SENTRON Powermind and ordering are available in the Insights Hub store (DEX - Digital EXchange (https://www.dex.siemens. com/ccrz__ProductList?operation=quickSearch&searchText=powermind)): There you will also find further details on the open cloud-based Eco system of Siemens. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 98 This procedure must be repeated if changes to the configuration are required. Changes to the configuration may be required due to changes in the SENTRON Powercenter configuration or due to an increased demand for information from SENTRON Powermind. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 99 (https://documentation.mindsphere.io/resources/pdf/getting-connected-en.pdf) must be fulfilled. Installation / Setup Operation / Maintenance MindSphere configuration using powerconfig SENTRON device engineering using powerconfig Device configuration SPLX file Device settings e. g. parameters, communication, configuration data online values SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 100 "Cloud" view and be given a name and transmission cycle. These groupings are handed over to the SENTRON Powercenter 3000 via the splx file to be imported (see First commissioning (Page 58)). SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 101 5.7 Communication with Insights Hub 5.7.2.2 Onboarding with SENTRON Powercenter 3000 Onboarding connects SENTRON Powercenter 3000 to the appropriate Insights Hub account. Onboarding is required for all types of Insights Hub communication. The SENTRON Powercenter 3000 becomes a "tenant" or "subtenant" of an Insights Hub and is logged in using an asset onboarding key of the type "MindConnect Lib".
  • Page 102 After the manual settings have been transferred, the data points must be individually assigned to the aspects and types in the Insights Hub asset manager. See section Configuring data in the Asset Manager (https://documentation.mindsphere.io/resources/pdf/getting-connected-en.pdf)". SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 103 MQTT topic. The cloud service functions as an MQTT broker to which other applications can connect and subscribe to the relevant MQTT topics. The information that SENTRON Powercenter 3000 provides can be further processed in this way. See: •...
  • Page 104 • Full provision of the attributes of a data point in the form of a JSON file, see section Structure of the SENTRON Powercenter 3000 data points (Page 109). • If communication with the cloud system is interrupted, up to 250,000 data points are buffered in SENTRON Powercenter 3000 and are subsequently transmitted when...
  • Page 105 Functions 5.8 Cloud service with MQTT 5.8.2 Connecting SENTRON Powercenter 3000 to the cloud Parameter settings are made via the web user interface "Settings → Cloud → MQTT". In the upper part, the parameters relating to communication are set. Including: •...
  • Page 106 Information about the project tree can be read out at http://{IP address}/api/v1/items using any browser. The individual items can then be analyzed with http://{IP address}/api/v1/items/{item-id}   The following analysis methods are recommended:   "count": 32, SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 107      "name": "B166",      "address": "",      "parent_id": "00000000-0000-0000-0000-000000000000",      "child_ids": [       "659be757-222b-485c-964a-8dda6c42412d"      ],      "_links": {       "self": {        "href": "/api/v1/items/81969b12-4725-47b5-8e9c-0a5736fd64cd"       }      }   },   {      "id": "659be757-222b-485c-964a-8dda6c42412d",      "type_name": "powercenter3000",      "name": "B166",      "address": "192.168.2.36:80",      "plant_id": "",      "mbgw_address": "192.168.2.36:502/255",      "parent_id": "81969b12-4725-47b5-8e9c-0a5736fd64cd",      "afd63aa4-c685-4a77-8208-c3ce26c0b3ec",      "child_ids": [       "4045dd71-c5ac-4a67-ad58-89dc281daa8e",       "fe0c9c0e-deb0-4dec-96cf-0078d14967a9",       "6bc89b91-347b-40b9-baec-a6ff875363e6",       "25b7aa44-92d2-454a-98c3-f19cf70e98c3",       "2f178eb1-44b2-4f8a-ae49-937efa39e1da",       "011df560-e700-49f7-8a1f-e817a5d48455"      ],      "_links": {       "self": {        "href": "/api/v1/items/659be757-222b-485c-964a-8dda6c42412d"       } SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 108      "name": "1.Floor",      "address": "",      "parent_id": "659be757-222b-485c-964a-8dda6c42412d",      "child_ids": [       "a51ea5dc-d0f6-4150-8dd5-f3a8851473e9",       "de87cd09-f9df-4b96-8484-6e5dfaff3a83",       "f0d651ac-3746-483b-9738-bac29c9220c8",       "52e81910-810c-4036-bb41-852c70b2cdb4"   ],   "_links": {    "self": {     "href": "/api/v1/items/afd63aa4-c685-4a77-8208-c3ce26c0b3ec"    }   }  },  {   "id": "a51ea5dc-d0f6-4150-8dd5-f3a8851473e9",   "type_name": "PAC2200",   "name": "F1.AirCon PAC2200",   "plant_id": "B166.F1.AirCon",   "address": "192.168.2.61:502",   "mbgw_address": "192.168.2.36:502/1",   "monitoring": {    "state": "connected"   },   "parent_id": "afd63aa4-c685-4a77-8208-c3ce26c0b3ec",   "child_ids": [],   "_links": {    "self": {     "href": "/api/v1/items/a51ea5dc-d0f6-4150-8dd5-f3a8851473e9"    }   }  }, SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 109 • Plant identifier • And its internal identifier, which can be used to identify the data source. See also Connecting SENTRON Powercenter 3000 to the cloud (Page 105) 5.8.4 Structure of the SENTRON Powercenter 3000 data points The subscribed data points are supplied with the following structure:  "item_id": "ea86dfb4-cf6b-47c6-8261-8b215efcd1f3",...
  • Page 110 Description Reference of the data point in the device. internal_name Internal name in the SENTRON Powercenter 3000 display_name Name to be displayed on the user interface. This name is identical to the name in the web user interface of the SENTRON Powercen­...
  • Page 111 For the SENTRON Powercenter 3000, notification via the web user interface (see Messages (Page 75)) and by email can be activated. This can be done either with SENTRON powerconfig or in the web user interface under "Settings → General → Notifications". SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 112 If an email server is used that requires both user name and password, e.g. gmx or yahoo, the setup can be done only via the web user interface for security reasons. On completion of setup or commissioning, a test email can be sent to test the settings. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 113 5.10 SENTRON Powercenter 3000 as a Modbus gateway SENTRON Powercenter 3000 provides a Modbus TCP interface for a smart switchgear assembly. Not only Siemens systems such as SENTRON powerconfig, powermanager and SIMATIC Energy Manager PRO but also other SCADA, energy monitoring and maintenance management systems can communicate via this interface.
  • Page 114 On a SENTRON Powercenter 3000, identifiers can be assigned in the value range 1 to 247. The number of devices actually supported on a SENTRON Powercenter 3000 is shown in the technical data. See Functional scope of the SENTRON Powercenter 3000 (Page 149). The external identifiers are assigned automatically by SENTRON powerconfig and stored in the SENTRON Powercenter 3000 configuration.
  • Page 115 (2 Bytes) (1 Byte) (1 Byte) (varies) 5.10.2 Method of operation of the SENTRON Powercenter 3000 Modbus TCP gateway The Modbus TCP Gateway serializes all incoming access, irrespective of the particular applications (= TCP connections). It is then • possible that multiple applications may access the connected devices in parallel, and •...
  • Page 116 The "Time synchronization" function is activated via the web user interface: "Toolbar → Services overview (Settings)". • If SNTP mode is active for a connected device, time synchronization is rejected by the device. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 117 To archive, document, and further use these changes, the setup can be exported. See "Settings → Actions → Project → Export project". This project can be further processed with SENTRON powerconfig, e.g. printed out. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 118 • The communications interface with software applications on site, e.g. Powermanager or SENTRON Powerconfig, or even SCADA systems (Supervisory Control and Data Acquisition) • Cloud-based application, e.g. in Siemens Insights Hub with the SENTRON Powermind application • Other cloud systems •...
  • Page 119 It is assumed that the smart assembly network is a physically protected network installed in the switchboard that is accessible only via SENTRON Powercenter 3000. In particular, routers to additional networks are not recommended. SENTRON Powercenter 3000 in the smart assembly network SENTRON Powercenter 3000 SENTRON Web-Interface powerconfig...
  • Page 120 The failure of one of the devices interrupts communication to the devices behind it. This can be avoided by building a ring with the Switched Ethernet module PROFINET and a SCALANCE switch with MRP (Media Redundancy Protocol). SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 121 Ethernet Ethernet Switch / Router e. g. SCALANCE XM408-4C powerconfig Ethernet Interface X1P1 SENTRON Powercenter 3000 smart assembly network ① SENTRON Powercenter 3000 is connected to a router via the external Ethernet interface X1P1. This router, e.g. SCALANCE XM408‑4C, represents the intranet. ②...
  • Page 122 Communication with a defined cloud via MQTT is established by SENTRON Powercenter 3000. Port 8883 must be enabled in the network infrastructure/firewall. ⑨  SENTRON Powercenter 3000 can generally communicate with partners on the internet. It is important to activate write protection for the web interface. ⑩...
  • Page 123 It suffices to enter the IP address or the hostname (see "Settings → General → Communication") in the address line of the browser if IP communication between web application and SENTRON Powercenter 3000 is assured.
  • Page 124 These csv files can be stored for documentation and evaluated individually as required. They can be displayed as curves using standard tools, e.g. Excel. Siemens also provides more advanced energy monitoring systems with powermanager and SENTRON powermind. SENTRON Powercenter 3000 supports both powermanager, via the Modbus gateway (Page 113) function, and SENTRON powermind (Page 97).
  • Page 125 Information must be recorded and evaluated over a long time period (e.g. one year) in order to achieve this. Siemens offers Insights Hub (https://new.siemens.com/global/en/products/software/mindsphere.html), a cloud-based, open IoT (Internet of Things) operating system, for this purpose.
  • Page 126 They are expanded, converted and must be integrated into digitalization solutions that already exist or came about in another way. SENTRON Powercenter 3000 provides the following options for both upward (northbound) and downward (southbound) integration. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 127 6.5 Integrating existing power distribution systems into the digitalization 6.5.1 Cloud applications with SENTRON Powercenter 3000 Digitalization solutions, such as energy management and status monitoring, e.g. with SCADA systems (Supervisory Control and Data Acquisition), have so far often been implemented based on PCs.
  • Page 128 • Protection through the security features of the SENTRON Powercenter 3000. See section Security features (Page 34) • Access via the transparent Modbus gateway. See section SENTRON Powercenter 3000 as Modbus gateway (Page 113) This requires knowledge of the application and structure of the device.
  • Page 129 Notifications from SENTRON Powercenter 3000 V1.1 or higher are provided via the web user interface and by email. See Notification of exceptional situations (Page 111). Only such prompt notification enables an employee to intervene before a failure occurs. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 130 Emails can be received any place, any time with modern devices, such as smartphones. Modbus TCP communication with higher-level applications Via SENTRON Powercenter 3000, multiple higher-level applications can communicate with the connected devices via IP networks with Modbus TCP. See SENTRON Powercenter 3000 as a Modbus gateway (Page 113). Power monitoring software...
  • Page 131 M874-3 Station wireless network SENTRON Powercenter 3000 ADSL Internet SCALANCE M812-1 Station Industrial Ethernet VPN tunnel Setting up a secure mobile wireless interface requires specialist knowledge that is not provided in this manual. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 132 Repair instructions This device cannot be repaired. However, a nonconforming device should be returned to Siemens because only then is it possible to issue a credit note in the event of a warranty claim. The device can be ordered as a spare part.
  • Page 133 SENTRON Powercenter 3000. If the SENTRON Powercenter 3000 has been in use for a long time, a newly added device might have a newer, and therefore unknown, version. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 134 Powercenter 3000, it is actually in the firmware. The firmware therefore contains not only the program of the SENTRON Powercenter 3000, but also "knowledge" about the features of the connectable devices. For this reason, a firmware update of the SENTRON Powercenter 3000 is useful for all extended use, e.g. in additional devices. NOTE For SENTRON Powercenter 3000, signed firmware is used for security reasons.
  • Page 135 7.4 Replacing the backup battery 7.3.1 Find update The firmware of the SENTRON Powercenter 3000 can be found in Industry Online Support (https://support.industry.siemens.com/cs/ww/en/view/109762951). For the download, registration is required by legal regulations. 1. Read the current download information to find out about the innovations.
  • Page 136 ● Reset the time setting on the device or use time synchronization. Proceed as follows to replace the backup battery: 1. Remove the ground connection. 2. Unscrew the screws on the two connection sides ③ and remove the covers. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 137 1. Insert the new battery by placing it on the Velcro strap. NOTE Make sure that the cable connection points towards the board. 2. Screw the cover of the enclosure side into place with the connectors. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 138 Disposal of batteries Batteries must not be disposed of as unsorted municipal waste, e.g. household waste. When disposing of batteries, the current local national/international regulations must be observed. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 139 – It is also possible to skip versions (e.g. to upgrade from version 1.3 to version 1.5) • SPLX compatibility: SPLX versions from earlier versions can always be imported, i.e. – SENTRON Powercenter 3000 can always read older splx versions – SENTRON Powerconfig can always read older splx versions Compatibility matrix SENTRON Powercenter 3000 version Compatible Powercon­...
  • Page 140 FAQs 8.2 Version management between SENTRON powerconfig and SENTRON Powercenter 3000 * However, you can import an splx project file from Powerconfig 3.28 or lower. NOTE When configuring the SENTRON Powercenter 3000, ensure that the SENTRON Powerconfig versions are compatible as indicated in the figure above.
  • Page 141 After adding or deleting devices or after modifying the communication parameters ①, the setup file must be saved in SENTRON powerconfig and updated in SENTRON Powercenter 3000 ②. Otherwise, the devices cannot be accessed in the smart assembly network or are reported as faulty. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 142 FAQs 8.4 Installation of upgrade licenses for SENTRON Powercenter 3000 Installation of upgrade licenses for SENTRON Powercenter 3000 Software requirements • Powercenter 3000 firmware V1.7.1 or higher • Powerconfig V3.25 or higher • Automation License Manager Purchase the license under the following link (https://mall.industry.siemens.com/mall/en/en/Catalog/Products/10375782?tree=CatalogTree)
  • Page 143 FAQs 8.4 Installation of upgrade licenses for SENTRON Powercenter 3000 Applying license in Powercenter 3000 via Powerconfig 1. Start Powerconfig. 2. Use the "Search for accessible devices" function to identify Powercenter 3000 in the network. 3. Load Powercenter 3000 into the PC project from Powerconfig.
  • Page 144 FAQs 8.4 Installation of upgrade licenses for SENTRON Powercenter 3000 5. Click on "Load license information". This is how you retrieve the license status from the device. Depending on the licenses available, the relevant license types will be marked "Not applied".
  • Page 145 FAQs 8.4 Installation of upgrade licenses for SENTRON Powercenter 3000 6. Select the license which you would like to apply and click on "Apply". SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 146 FAQs 8.4 Installation of upgrade licenses for SENTRON Powercenter 3000 7. After transferring the license, the license is displayed with a check icon. 8. The license is displayed as "active" in Powercenter 3000. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 147 FAQs 8.4 Installation of upgrade licenses for SENTRON Powercenter 3000 The increased number of licenses will be visible. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 148 (SELV/PELV) in accordance with IEC/EN/UL 61010-2-201. • When operated outside an enclosure in accordance with UL/CSA 61010-2-201, the device must be supplied with NEC Class 2 or an energy-limited circuit in accordance with UL/CSA 61010-1. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 149 Technical data 9.2 Range of functions of the SENTRON Powercenter 3000 Electromagnetic compatibility Interference immunity to conduc­ ± 2 kV according to IEC 61000-4-4; burst ted interference on power cables ± 0.5 kV according to IEC 61000-4-5; surge symmetrical ± 1 kV according to IEC 61000-4-5; surge asymmetrical Interference immunity on signal ± 1 kV according to IEC 61000-4-4;...
  • Page 150 Technical data 9.2 Range of functions of the SENTRON Powercenter 3000 Main functions from version Article number Support of 3VA Condition Monitoring with 3VA V4.4 in the web interface and in Power­ V1.3 mind Support for Powercenter 1000 V1.4 Support for 3WA V1.4...
  • Page 151 5 W (for all USB devices) NOTE Device can overheat The power supply cannot provide unlimited power. The additional components consume energy and produce heat. The device can overheat and additional components can be damaged. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 152 Input voltage 24 V DC (19.2 to 28.8 V DC) Protection class Protection class I (device must be connected to ground con­ ductors) Typical power consumption Power consumption (at 24 V rated voltage) Basic device with Intel Atom E3930 13 W SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 153 The mounting holes on the device are arranged symmetrically. The mounting parts can be mounted in all orientations of the device based on your requirements. Mounting on DIN rails All dimensions in mm (inch) SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 154 Extensible Firmware Interface Integrated Graphics Device Local Area Network​ Measuring Instruments Directive MQTT Message Queuing Telemetry Transport Media Redundancy Protocol Network Time Protocol SCADA Supervisory Control and Data Acquisition Uniform Resource Identifier Virtual Private Network SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 155 NOTICE Storage and transport If you have to store or transport the component in non-conductive packaging, you must first pack the component in ESD-safe, conductive material, e.g., conductive foam rubber, ESD bag. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 156 Warning, read and follow the documentation sup­ Lock is closed plied Caution, radio equipment Lock is open Pull out the power plug before opening Hole for the Kensington lock Caution ESD (components sensitive to electrostatic Warning, hot surface charge) SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 157 ON/OFF switch, without electrical isolation Ejecting CD/DVD ON/OFF pushbutton, without electrical isola­ tion A.3.4 Certificates, approvals and labels You will find all available certificates, approvals and labels in the Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/cert). SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 158 Service and support You will find further information and support on the described products in the Internet at the following address: • Technical support (https://support.industry.siemens.com/cs/ww/en) • Industry Mall (https://mall.industry.siemens.com) Current documentation Always use the current documentation for your product. You will find the current edition of this manual and additional important documents by searching for the article number of your device in the Internet.
  • Page 159 Buffer memory in which the most frequently requested data are temporarily stored (buffered) to increase the speed of access. CE marking Communauté Européene: The CE symbol confirms the conformity of the product with all applicable EC directives, such as the EMC Directive. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 160 I/O devices (e.g. hard disks, monitors, printers). EMC Directive EU Directive governing electromagnetic compatibility. Conformity is confirmed by the CE symbol and the EC certificate of conformity. ESD guidelines Guidelines for handling electrostatic sensitive devices. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 161 This technology provides diagnostics, management, and remote control of PCs. It is only effective if it is supported by all the system components affected, such as the processor, operating system, and application software. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 162 The devices connected to a LAN are called nodes. Networks are used to share the use of files, printers, or other resources. License key License key is the electronic license stamp of a license. Siemens AG issues a license key for license-protected software. Low-Voltage Directive EC directive for the safety of products operated with low voltage (50 to 1000 V AC, 70 to...
  • Page 163 Read Only Memory. The ROM memory is a read-only memory in which each memory cell can be individually addressed. The stored programs or data are hard-programmed and are retained even through a power failure. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 164 Warm restart A warm restart is understood as a restart after program termination. The operating system is reloaded and started again. A warm restart is performed with the hotkey CTRL + ALT+ DEL. SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 165 Certificates, 157 Cloud applications Environmental conditions, 151 Mechanical, 151 Applications, 127 Cloud connection Ethernet, 29 Function, 104 Ethernet interface, 17 Commissioning Device level, 31 Requirements, 30 Events Communication Setting, 113 Modbus TCP, 113 SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 166 Applications, 126 Notification, 111 Security aspects, 126 Notifications Installation Setting, 111 Backup battery, 136 Backup battery, 137 Interface WLAN, 131 Mobile service interface, 131 Interfaces, 17 Ethernet, 17 Internal Ethernet interface Performance features, 32 SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 167 Rectifying a fault, 132 Symbols Redirect Safety, 156 Login, 83 Operator controls, 157 Removal System expansions DIN rail, 24 Safety information, 10 Repair instructions, 132 Replacement Backup battery, 136 Required basic knowledge, 9 SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 168 Settings, 79 Web user interface Arrangement of devices, 73 Widget library, 74 Messages, 75 Firmware update, 135 Widget library Web user interface, 74 Widgets, 74, 74 Wireless LAN Security aspects, 131 WLAN Interface, 131 SENTRON Powercenter 3000 Equipment Manual, 08/2024, L1V30579222003-10...
  • Page 169 Further information Published by Siemens AG Smart Infrastructure Electrical Products P. O. Box 10 09 53 93055 Regensburg, Germany For the U.S. published by Siemens Industry Inc. 3617 Parkway Lane Peachtree Corners, GA 30092 United States SI EP online...