ActronAir ADVANCE B EVV13BS Installation And Commissioning Manual

ActronAir ADVANCE B EVV13BS Installation And Commissioning Manual

Split ducted unit indoor r-32 series, single/split fan coil

Advertisement

Quick Links

ADVANCE B SPLIT DUCTED UNIT
Indoor R-32 Series
Installation and Commissioning Guide
Model Numbers
Single Fan Coil
EVV13BS
EVV15BS
EVV17BS
EVV19BS
Split Fan-Coil*
EAA13BS / EFV13BS
EAA15BS / EFV15BS
EAA17BS / EFV17BS
EAA19BS / EFV19BS
* Split fan coil has a separate coil and fan.
CAUTION:
The system is charged with flammable
refrigerant, safety checks are necessary to
ensure that the risk of ignition is minimised.
A2L
IMPORTANT NOTE:
This unit is designed for use with R-32 refrigerant only.
Please read the R-32 Safety Manual and this manual carefully
before installing or operating your air conditioning unit.
Information in this manual is to be used in conjunction with
the R-32 Safety Manual.
Make sure to save this manual for future reference.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ADVANCE B EVV13BS and is the answer not in the manual?

Questions and answers

Summary of Contents for ActronAir ADVANCE B EVV13BS

  • Page 1 ADVANCE B SPLIT DUCTED UNIT Indoor R-32 Series Installation and Commissioning Guide Model Numbers Single Fan Coil EVV13BS EVV15BS EVV17BS EVV19BS Split Fan-Coil* EAA13BS / EFV13BS EAA15BS / EFV15BS EAA17BS / EFV17BS EAA19BS / EFV19BS * Split fan coil has a separate coil and fan. CAUTION: IMPORTANT NOTE: The system is charged with flammable...
  • Page 2: Table Of Contents

    Advance B R-32 Indoor Units Installation and Commissioning Guide Table of Contents Introduction ��������������������������������������������������������������������������������������������������������������������������������� 3 Safety Instructions ����������������������������������������������������������������������������������������������������������������������� 4 Components Overview ����������������������������������������������������������������������������������������������������������������� 5 Indoor Unit Components Overview Indoor Unit Electrical Panel Overview Unit Dimensions and Clearances ��������������������������������������������������������������������������������������������������� 6 Indoor Unit - EVV13BS / EVV15BS / EVV17BS / EVV19BS Two-Piece Fan Coil Indoor Unit - Upright Fan Coil with Vertical Discharge Minimum Service Areas and Airflow Clearances...
  • Page 3: Introduction

    Check your air conditioning unit and all items against the invoice upon receiving your shipment. Inspect the unit, components and accessories for any sign of damage. If there is any damage to the unit, contact ActronAir Customer Care Department immediately on: 1300 522 722 to obtain a Goods Return Number.
  • Page 4: Safety Instructions

    Advance B R-32 Indoor Units Installation and Commissioning Guide Safety Instructions • Only licensed HVAC technicians* should install and service air conditioning equipment. Improper service or alteration by an unqualified technician could result in significant and major damage to the product or property which may render your warranty null and void.
  • Page 5: Components Overview

    Advance B R-32 Indoor Units Installation and Commissioning Guide Components Overview Indoor Unit Components Overview EC MOTOR COIL Single Fan for EVA10AS ELECTRICAL BOX COVER CONTROL PANEL Indoor Unit Electrical Panel Overview EMC FILTER EMC FILTER TRANSFORMER (for EVV19BS model) (for EVA20/23AS models) CONTROL BOARD Installation and Commissioning Guide - Advance B Split Ducted Indoor Units (R-32 Series)
  • Page 6: Unit Dimensions And Clearances

    Advance B R-32 Indoor Units Installation and Commissioning Guide EVA MODELS 25032024.TCW Unit Dimensions and Clearances EVA Dim Indoor Unit - EVV13BS / EVV15BS / EVV17BS / EVV19BS NOTES: W-RD Drawing is subject to change without notice. Image shown is for illustration purpose only. GAS PIPE INDOOR COIL Actual unit may vary depending on unit...
  • Page 7 1000 mm between the units or between the unit and the outside perimeter is available. 3. Minimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
  • Page 8: Two-Piece Fan Coil

    1000 mm between the units or between the unit and the outside perimeter is available. 3. Minimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
  • Page 9 1000 mm between the units or between the unit and the outside perimeter is available. 3. Minimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
  • Page 10: Indoor Unit - Upright Fan Coil With Vertical Discharge

    PROJECTION mounting hole details. 2. Minimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow. 3. For installation with release height less than or equal to 0.6m, minimum area will be computed based on release height of 0.6m 4.
  • Page 11: Minimum Service Areas And Airflow Clearances

    3. Minimum service access clearances are TOP VIEW DUCT WORK pipe connections are responsibilities of the installer, ActronAir located on the Right side of the indoor unit. will not be held liable for any extra charges incurred due to lack of access.
  • Page 12: Installation Instructions

    Compliance and consultation with the authorities having jurisdiction with the installation of this equipment is the responsibility of the installer. ActronAir will not be held liable for any damages or costs as a result of the installer’s failure to comply. Please refer to the matching outdoor unit Installation and Commissioning Guide for further information and details.
  • Page 13 AS/NZS 3000 (also known as Australian Wiring Rules). NOTES This indoor unit is designed to match only with an ActronAir Series outdoor unit as specified in the Technical Selection Catalogue.
  • Page 14: Airflow Application Guidelines

    NOTE Supply and Return Air Plenums must be as per ActronAir Plenums or equal to, or lower static pressure. Installation and Commissioning Guide - Advance B Split Ducted Indoor Units (R-32 Series)
  • Page 15: Return Air Grille Sizes

    Advance B R-32 Indoor Units Installation and Commissioning Guide Return Air Grille Sizes Careful consideration is to be given to pressure drops through return air grilles, air filters and crimped or tight bends in duct. Grille sizes shown are based on a velocity of 2.5 m/s, sizes shown are free area, please ensure your suppliers are aware of these requirements.
  • Page 16: Unit Lifting Procedures

    Advance B R-32 Indoor Units Installation and Commissioning Guide Unit Lifting Procedures WARNING WH&S regulations must be observed and will take precedence during lifting process. Do not use pipes or tube coming out from the unit to lift the unit. Crane Lifting Method DANGER Make sure rigging equipment, accessories and plant are sufficiently and safely capable to lift the unit in order to prevent...
  • Page 17: Fork Lift Method

    Advance B R-32 Indoor Units Installation and Commissioning Guide Procedure: 1. Slip nylon slings through the pallet as shown in Figure 1. 2. Use Bow or Dee shackle to connect the slings. 3. Ensure slings are protected by rubber pads or similar if slings are draped across unit edges, corners, or air grilles . This will prevent the unit from being damaged during lifting.
  • Page 18: Pallet Dimensions

    Advance B R-32 Indoor Units Installation and Commissioning Guide Pallet Dimensions PALLET FORK LIFTING HOLE DIMENSIONS ALL DIMENSIONS IN MM. EVV13BS / EVV15BS / EVV17BS / EVV19BS Installation and Commissioning Guide - Advance B Split Ducted Indoor Units (R-32 Series) Doc.
  • Page 19: Condensate Drainage Instructions

    Advance B R-32 Indoor Units Installation and Commissioning Guide Condensate Drainage Instructions NOTES • Do not use pipes or tube coming out from the unit to lift the unit. • Support drain line for long pipe run. • Parts for the Condensate Trap are not supplied with the unit. •...
  • Page 20: Zone Barrel Installation Instructions

    (positions that range from 9 o’clock to 3 o’clock), as shown below: It is also recommended that only ActronAir 24V zones be connected to this system using RJ45 cable connections.RJ12 connections are not compatible on these systems. Warranty may be void if third party zones cause damage to the system.
  • Page 21: Electrical Installation

    Advance B R-32 Indoor Units Installation and Commissioning Guide Electrical Installation All electrical work must be carried out by a qualified technician. Make sure all wiring is in accordance with local wiring rules. Wiring connections should be made in accordance with the wiring diagram provided in accordance with the latest edition of the AS/NZS 3000 “Australian / New Zealand Wiring Rules”.
  • Page 22: Wiring Diagram

    Advance B R-32 Indoor Units Installation and Commissioning Guide Wiring Diagram EVV/EFV13BS Description: Base Model No.: Variation Code: Variation: Description: STANDARD WIRING DIAGRAM INDOOR BOARD + 8 ZONES WIRING DIAGRAM EVV/EFV13BS WITH 2 WALL CONTROLLERS WITH 2 WALL CON Drawing No: Sheet: Revision: Drawn:...
  • Page 23 Advance B R-32 Indoor Units Installation and Commissioning Guide EVV/EFV15BS Description: Base Model No.: Variation Code: Variation: Description: STANDARD WIRING DIAGRAM INDOOR BOARD + 8 ZONES WIRING DIAGRAM EVV/EFV15BS WITH 2 WALL CONTROLLERS WITH 2 WALL CO Drawing No: Sheet: Revision: Drawn: Approved:...
  • Page 24 Advance B R-32 Indoor Units Installation and Commissioning Guide EVV/EFV17BS Description: Base Model No.: Variation Code: Variation: Description: WIRING DIAGRAM INDOOR BOARD + 8 ZONES WIRING DIAGRA EVV17BS STANDARD WITH 2 WALL CONTROLLERS WITH 2 WALL CO Drawing No: Sheet: Revision: Drawn: Approved:...
  • Page 25 Advance B R-32 Indoor Units Installation and Commissioning Guide EVV/EFV19BS Description: Base Model No.: Variation Code: Variation: Description: STANDARD WIRING DIAGRAM INDOOR BOARD + 8 ZONES WIRING DIAGRA EVV/EFV19BS WITH 2 WALL CONTROLLERS WITH 2 WALL CO Drawing No: Sheet: Revision: Drawn: Approved:...
  • Page 26: Electrical Connection

    Advance B R-32 Indoor Units Installation and Commissioning Guide Electrical Connection NOTES • To minimise noise interference, Data and Power cable clearance should be maintained as much as possible. • All drawings are for illustration purposes only. Actual unit may vary depending on the model. •...
  • Page 27: Data Cable Shielding Instructions

    Advance B R-32 Indoor Units Installation and Commissioning Guide Data Cable Shielding Instructions 2 Core Twisted (ActronAir Part Number: AEDC2) NOTES • Maintain the twist of the core wires up to the Green Terminal Plug. • Maximum strip length of outer insulation to the Green Terminal Plug is 50mm.
  • Page 28: Circuit Breaker Size And Cable Size Recommendation

    Advance B R-32 Indoor Units Installation and Commissioning Guide Circuit Breaker Size and Cable Size Recommendation Circuit Breaker Size Amps Model CRV13BS / EVV13BS / EFV13BS CRV15BS / EVV15BS / EFV15BS CRV17BS / EVV17BS / EFV17BS CRV13BT / EVV13BS / EFV13BS CRV15BT / EVV15BS / EFV15BS CRV17BT / EVV7BS / EFV17BS CRV19BT / EVV9BS / EFV19BS...
  • Page 29: Wall Controller Options

    Advance B R-32 Indoor Units Installation and Commissioning Guide Wall Controller Options Wall Controller Options A maximum of three (3) wall controllers in the below combinations is allowed per unit. See below table. Wall Controllers Options 1st Option 2nd Option 3rd Option LR7-1 / LC7-2 4th Option...
  • Page 30: Wiring Configuration : Recommended

    Advance B R-32 Indoor Units Installation and Commissioning Guide Wiring Configuration : Recommended NOTES • Diagram shown below is a general representation only. Refer to individual unit wiring diagram for complete wiring connection details. • Long runs beside Mains cables or TV antenna cables should be avoided. •...
  • Page 31: Wiring Configuration : Alternate

    Advance B R-32 Indoor Units Installation and Commissioning Guide Wiring Configuration : Alternate NOTES • Diagram shown below is a general representation only. Refer to individual unit wiring diagram for complete wiring connection details. • Long runs beside Mains cables or TV antenna cables should be avoided. •...
  • Page 32: Cable Length - Zoning

    * All Zone Device Power Cable : Cat5E Spec Cables with RJ45 Connectors and Cable Boots - Green Colour • ** Total Cumulative length of all the aggregate cable must not exceed 250 meters. Consult ActronAir for longer cable length requirement.
  • Page 33: Lr7-1 / Lr7-2

    1 to 4 (Optional 4 Zones Piggy-Back Configuration), if 1 to 3 is 75m, then 3 to 4 must be 25m to make a total of 100m. *** Recommended maximum cable length, providing total of preceding cable connections are only 5m. ^ Total Cumulative length of all the aggregate cable must not exceed 500 meters. Consult ActronAir for longer cable length requirement.
  • Page 34: Wiring Connections

    Advance B R-32 Indoor Units Installation and Commissioning Guide Wiring Connections LR7-1 and LC7-2 Wall Control Wiring Connections INDOOR WALL CONTROL WIRING CONTROL BOARD POWER: - BROWN / ORANGE 485 A: - BLUE WALL CONTROLLER +12V A 485 B: - BLUE-WHITE GND: - BROWN-WHITE / ORANGE-WHITE NOT USED: - GREEN / GREEN-WHITE...
  • Page 35: Lm-Rs-2 Optional Sensor Wiring Connections

    Advance B R-32 Indoor Units Installation and Commissioning Guide LM-RS-2 Optional Sensor Wiring Connections INDOOR CONTROL REMOTE SENSOR WIRING BOARD PAIR 1: - BLUE / BLUE-WHITE PAIR 2: - ORANGE / ORANGE-WHITE TEMP PAIR 3: - GREEN / GREEN-WHITE SENSORS PAIR 4: - BROWN / BROWN-WHITE OPTIONAL OPTIONAL...
  • Page 36: Indoor Commissioning Guide

    Advance B R-32 Indoor Units Installation and Commissioning Guide Indoor Commissioning Guide Before activating the self-learn mode, ensure the following: 1. System should be in the OFF mode. 2. Ensure all connected zones are able to be turned on. If a connected zone cannot be opened, refer to Troubleshooting guide for more information.
  • Page 37: Zone Commissioning

    Advance B R-32 Indoor Units Installation and Commissioning Guide Zone Commissioning When the unit is powered on, zone detection will automatically start. This will take 2 minutes to complete. A zone detection can also be manually triggered on the LR7-1/LC7-2 controller by pressing the ON/OFF button and Zone 1 button for 3 seconds.
  • Page 38: Maintenance Frequency Checklist

    Advance B R-32 Indoor Units Installation and Commissioning Guide Maintenance Frequency Checklist Regular servicing of equipment by a qualified technician is recommended every 12 months for residential applications and every quarter for commercial applications. Regular servicing of your unit helps in maintaining its optimum performance and reliability.
  • Page 39: Version History

    Advance B R-32 Indoor Units Installation and Commissioning Guide Version History DOCUMENT VERSION BOM VERSION UPDATE HISTORY Ver 1 1st Released Installation and Commissioning Guide - Advance B Split Ducted Indoor Units (R-32 Series) Doc. No. 0525-138 Ver. 1 241130...
  • Page 40 ©Copyright 2024 Actron Engineering Pty Limited ABN 34 002767240. ®Registered Trade Marks of Actron Engineering Pty Limited. ActronAir is constantly seeking ways to improve the design of its products. Therefore, specifications are subject to change without notice. Installation and Commissioning Guide - Advance B Split Ducted Indoor Units (R-32 Series)

Table of Contents