Page 2
Table of Contents 1. Introduction ................2 2. Appearance ................. 3 3. Features ..................3 4. Set up Instructions ..............4 5. Data Report ................. 5 5.1 Example of ReportDataCmd ..........5 5.2 Example of ConfigureCmd ..........7 5.3 Example of GlobalCalibrateCmd ......... 8 5.4 Set/GetSensorAlarmThresholdCmd ........
Page 3
1. Introduction R718CKAB The temperature/humidity sensor and K-type thermocouple can detect the temperature, humidity, and an object's surface temperature. The temperature measurement range of R718CK is -40°C to +375°C. R718CK has the features of good linearity, larger thermal electromotive force, high sensitivity, and stability. It should not be used in sulfuric environments, reducing, oxidizing, vacuum atmospheres, or weak oxidizing atmospheres.
Page 4
Temperature and Humidity detection Compatible with LoRaWAN Class A device Frequency hopping spread spectrum Support third-party platforms: Actility/ThingPark, TTN, MyDevices/Cayenne Low-power design for longer battery life Note: Please visit http://www.netvox.com.tw/electric/electric_calc.html for battery life calculation and other detailed information.
Page 5
4. Set up Instructions On/Off Power on Insert batteries. (User may need a screwdriver to open the battery cover.) Turn on Press and hold the function key for 3 seconds until the green indicator flashes. Turn off (Factory resetting) Press and hold the function key for 5 seconds until the green indicator flashes 20 times. Power off Remove Batteries.
Page 6
1. The interval of the data reports might vary due to the firmware. 2. The interval between two reports must be the minimum time. 3. Please check Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver http://cmddoc.netvoxcloud.com/cmddoc to resolve uplink data.
Page 7
0.01% Bit4_LowAirHumidityAlarm Bit5_HighAirHumidityAlarm Bit6-7:Reserved Example of Uplink: 01C40124028A0B0E1A9001 byte (01): Version byte (C4): DeviceType 0xC4-R718CKAB byte (01): ReportType byte (24): Battery-3.6v , 24 Hex=36 Dec 36*0.1v=3.6v byte (028A): Temperature-65°C, 028A(HEX)=650(DEC),650*0.1°C =65.0°C byte (0B0E): Air Temperature-28.3°C, 0B0E(HEX)=2830(DEC),2830*0.01°C =28.30°C byte (1A90): Air Humidity-68%, 1A90(HEX)=6800(DEC),6800*0.01%=68.00% byte (01): Threshold Alarm-Low Temperature Alarm, Bit 0 =1...
Page 11
5.4 Set/GetSensorAlarmThresholdCmd Fport: 0x10 Note: The threshold value could be configured by users. If the sensor shows 0xFFFFFFFF, the high / low threshold function is disabled. CmdID CmdDescriptor Payload (10 bytes) (1 byte) Channel (1 byte) SensorType (1 byte) SensorHigh SensorLow SetSensorAlarm 0x00_Channel1,...
Page 12
5.5 Example of NetvoxLoRaWANRejoin (NetvoxLoRaWANRejoin command is to check if the device is still in the network. If the device is disconnected, it will automatically rejoin back to the network.) Fport: 0x20 CmdID CmdDescriptor Payload (5 bytes) (1 byte) RejoinCheckPeriod (4 bytes, Unit: 1s SetNetvoxLoRaWANRejoinReq 0x01...
Page 13
5.5 Example for MinTime/MaxTime logic Example#1 based on MinTime = 1 Hour, MaxTime = 1 Hour, Reportable Change i.e. BatteryVoltageChange =0.1V MaxTime MaxTime sleeping (MinTime) sleeping (MinTime) Wakes up and collect data Wakes up and collect data Wake up and collect data REPORTS 3.6V REPORTS 3.6V REPORTS 3.6V...
Page 14
Note: 1) The device only wakes up and performs data sampling according to MinTime Interval. When it is sleeping, it does not collect data. 2) The data collected is compared with the last data reported. If the data variation is greater than the ReportableChange value, the device reports according to MinTime interval.
Page 15
6. Installation 1. The Wireless Temperature and Humidity Sensor with Applications: Oven Thermocouple Sensor (R718CXAB) has a built-in Industrial control equipment magnet. When installed, it can be attached to the surface Semiconductor industry of an object with iron which is convenient and quick. To make the installation more secure, use screws (purchased) to secure the unit to a wall or other surface.
Page 16
7. Battery Passivation Many of Netvox devices are powered by 3.6V ER14505 Li-SOCl2 (lithium-thionyl chloride) batteries that offer many advantages including low self-discharge rate and high energy density. However, primary lithium batteries like Li-SOCl2 batteries will form a passivation layer as a reaction between the lithium anode and thionyl chloride if they are in storage for a long time or if the storage temperature is too high.
Page 17
8. Important Maintenance Instructions Kindly pay attention to the following to achieve the best maintenance of the product: • Keep the device dry. Rain, moisture, or any liquid might contain minerals and thus corrode electronic circuits. If the device gets wet, please dry it completely.