9 812 25
BASE PDU replacement (maintenance only)
ON
ON
6
Power On the PDU.
9
Redo cascading if necessary
(see user guide ref. LE14531xx).
BASE:
1
6- PIN connector: Plug in to NODE controller
2
Link-A RJ45 port: RS485 port for input cascading link
from NODE Controller OR upstream PDU units.
3
Link-B RJ45 Port: RS485 port for output cascading
link to downstream BASE PDU units.
4
RS485 toggle resistor: Toggle to end RS485 cascading chain (see user guide)
5
Maintenance side-clips: Safely remove and replace the BASE electronic components and power
supply in case of disaster recovery (will turn o all outlets on switched units) Spare part 9 812 25
6
QR code with product identi cation numbers
7
LED indicator: to be informed at a glance of existing alerts and to know the status of wireless sensor pairing
8
Wireless sensors pairing button: Direct pairing with selected wireless sensors
7
Wait until the LED is green.
AG13098_A
7
3
2
8
5
Plug the new BASE on the PDU.
9 812 25
Press and hold the BASE push button for 7 seconds.
8
Release it, the LED status indicator flashes blue and
finally becomes green.
AG13098_A
7 s
Redo sensor pairing if necessary
(see user guide LE14531xx).
5
1
4
6
5
Need help?
Do you have a question about the 981225 and is the answer not in the manual?
Questions and answers