Page 1
AFRISO sp. z o.o. Szałsza, ul. Kościelna 7 42-677 Czekanów Poland Phone +48 32 330 33 55 zok@afriso.pl www.afriso.pl Installation and operation manual Pump assemblies BPG BPG 240 BPG 241 Read the manual before using the device! Pay attention to all information regarding safety! Keep the instruction manual! 953.001.0192...
Table of contents Explanations to the installation and operation manual ..........3 Safety messages and hazard categories ............. 3 Information on safety ....................4 Intended use of the device ................4 Quality control ....................4 Qualification of personnel ................4 Personal protective equipment..............
Instruction manual Explanations to the installation and operation manual Installation and operation manual is an important part of the scope of delivery. That is why we recommend: Read the installation and operating instruction before installing the device. Keep the installation and operating instruction for the entire life of the device.
Pump assemblies BPG are designed for use only in closed heating and cooling systems, where the medium is water or a mixture of water and glycol with a maximum concentration of 30%. BPG 240 assembly is used to pump the medium from the source directly to the receiving installation.
+48 32 330 33 55. Product description Pump assemblies BPG come in two models: direct BPG 240 and with rotary mixing valve BPG 241. In all models, all fittings and pipes, are in EPP insulation. The shut-off valves and mixing valve are made of brass.
Instruction manual Figure 3: Dimensions of BPG assemblies 3.3 Operation BPG assemblies are used to pump the medium from the source / buffer tank to the heat / cooling emitters. The assembly with a mixing valve additionally makes it possible to regulate the temperature of the medium.
Instruction manual valve built into the ball of the shut-off valve on the return prevents backflows. Turning the knob 45° to the right forces the check valve open to facilitate filling the system. The valve located on the supply has a special pocket for a temperature sensor with a maximum diameter of 6 mm.
Instruction manual Examples of application schemes Figure 4: BPG assembly mounted on the wall in a surface heating system with a heat pump* *buffer tank ABT 50 has 125 mm connection spacing Pump assemblies BPG...
Page 12
Instruction manual Figure 5: BPG assemblies mounted on a KSV 90-2 boiler manifold in a surface heating system with a heat pump Pump assemblies BPG...
Page 13
Instruction manual Figure 6: BPG assemblies mounted on a KSV 90-2 HW boiler manifold with integrated hydraulic separator in a mixed system with a gas boiler Pump assemblies BPG...
Medium water or a mixture of water and glycol with a maximum concentration of 30% Circulating pump AFRISO APH 161 15-7/130 mm, with a 1,6 m wire Electric actuator ARM 141, 5 Nm, 120 sec., 3-point Electrical parameters of the pump and actuator...
CE marked. The circulating pump included in the product equipment has a declara- tion of conformity, which is available on the website: www.afriso.pl. The electric actuator included in the equipment of the assembly with the mixing valve BPG 241 has a declaration of conformity, which is available on the website: www.afriso.pl.
It is not possible to directly install BPG assemblies with AFRISO KSV 90-3 boiler manifold on AFRISO ABT 160 buffer tank. Before connecting the assembly to the heating / cooling system, the installation should be thoroughly flushed, paying special attention to the removal of residues from soldering, pipe cutting, threading, etc.
G1" nuts. The source should be connected to G1" threads. When using boiler manifold KSV 90 AFRISO or boiler manifold with hydraulic separator KSV 90 HW AFRISO, the corresponding gaskets are included in the delivery of the manifold.
Instruction manual 8.4 Use of the actuator and the mixing valve The BPG 241 assembly is equipped with a mixing valve and an electric actuator. The electric actuator ARM 141 operates in automatic mode (rotates the closing element according to signals from the automation) or in manual mode (rotating the closing element through the actuator mechanism using an Allen key).
Page 19
Instruction manual If the valve is set in a different position, manually (using, for example, a flathead screwdriver) adjust the closing element as shown in Figure 12. If the indicator on the actuator does not indicate the center of the scale, switch it to manual operation mode, adjust the actuator with an Allen wrench so that the indicator points to the center of the scale.
Page 20
Instruction manual Figure 14: The position of the closing element where the flow of the medium returning from the receiver is cut off, all the medium from the source goes to the receiver The graph below shows the flow characteristics of the mixing valve. Figure 15: Flow characteristics of the mixing valve installed in the BPG 241 assembly Pump assemblies BPG...
Instruction manual 8.5 Filling and venting After completing the installation of the assemblies and the rest of the installation, fill it with medium. To fill the installation, use water or a mixture of water and glycol with a maximum concentration not exceeding 30%.
Pump assemblies BPG consist of materials that can be recycled. Return Before returning a product, please contact the manufacturer: zok@afriso.pl, phone +48 32 330 33 55. Warranty Product warranty in accordance with the general conditions of sale and delivery.
Need help?