ZCS AZZURRO 3PH 100-110KTL-V4 User Manual

ZCS AZZURRO 3PH 100-110KTL-V4 User Manual

Grid-connected inverter
Table of Contents

Advertisement

Quick Links

3PH 100-110KTL-V4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AZZURRO 3PH 100-110KTL-V4 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ZCS AZZURRO 3PH 100-110KTL-V4

  • Page 1 3PH 100-110KTL-V4...
  • Page 2 Via Lungarno, 248 - 52028 Terranuova Bracciolini - Arezzo, Italy tel. +39 055 91971 - fax. +39 055 9197515 innovation@zcscompany.com - zcs@pec.it – www.zcsazzurro.com Pile Reg. IT12110P00002965 - Share Capital € 100,000.00 fully paid up AR Companies Reg. no. 03225010481 - REA AR - 94189...
  • Page 3: Table Of Contents

    Table of Contents Preliminary safety instructions ................................7 1.1. Safety instructions ..................................7 1.2. Symbols and icons .................................. 10 Product features ......................................12 2.1. Product presentation ................................12 2.2. Description of functions ..............................14 2.3. Module protection .................................. 15 2.4. Others ......................................16 2.5.
  • Page 4 6.1. Operating panel and display .............................. 52 6.2. Main interface ..................................53 6.3. Main menu ....................................56 6.4. Updating Inverter Software ............................... 62 Troubleshooting and maintenance ..............................64 7.1. Troubleshooting ..................................64 7.2. Maintenance ..................................... 72 7.3. PID Recovery .................................... 72 7.4.
  • Page 5 Connecting the LM2-485 PRO cell irradiance and temperature sensor to the datalogger ..124 10.4.8. Configuring the Datalogger ............................. 125 10.4.8.1. Configuring the Datalogger on the ZCS Azzurro portal ................127 10.4.8.2. Network configuration ............................128 10.4.9. Local monitoring .................................. 129 10.4.9.1.
  • Page 6 Technical support ZCS offers a support and technical consultancy service accessible by sending a request directly from the website www.zcsazzurro.com For the Italian territory, the following toll-free number is available: 800 72 74 64. 5 / 131 User’s Manual 3PH 100-110KTL-V4...
  • Page 7 Preface General information Please read this manual carefully before installation, use or maintenance. This manual contains important safety instructions that must be followed during installation and maintenance of the system. Scope This manual describes the assembly, installation, electrical connections, commissioning, maintenance and •...
  • Page 8: Preliminary Safety Instructions

    1. Preliminary safety instructions If you have problems or questions regarding the reading and understanding of the following information, please contact Zucchetti Centro Sistemi S.p.A. through the appropriate channels. Note General information in this chapter It mainly highlights the safety instructions to be followed during installation and use of the equipment. Safety instructions Introduces the main safety symbols on the inverter.
  • Page 9 Attention Do not remove the information label or open the inverter. Otherwise, ZCS will not provide any warranty or maintenance. Note 8 / 131 User’s Manual 3PH 100-110KTL-V4 Rev.
  • Page 10 Operation Contact with the electrical grid or the terminal of the equipment may cause electrocution or fire! Do not touch the terminal or the conductor connected to the electrical grid. • Follow all the instructions and safety requirements relating to the mains •...
  • Page 11: Symbols And Icons

    1.2. Symbols and icons Safety signals High voltage of inverter may be harmful to health! Only qualified personnel can operate the product. Keep this product out of the reach of children. Danger Pay attention to possible burns due to hot parts. Only touch the screen or press the keys while the inverter is in operation.
  • Page 12 Complies with the European Standards (CE) Ground connection point Read this manual before installing the inverter. Indication of the allowable temperature range Positive and negative polarities of the input voltage (DC). RCM (Regulatory Compliance Mark). The product complies with the requirements of the applicable Australian standards.
  • Page 13: Product Features

    2. Product features General information in this chapter The field of use and overall dimensions of the 3PH 100-110KTL-V4 inverters are indicated in this section. Product overview It describes how the 3PH 100-110KTL-V4 inverters and their internal operating modules work. Description of functions Describes the efficiency curves of the inverter.
  • Page 14 Dimensions description • Overall dimensions: L×W×H=970*695*325mm Figure 3 – Front, side and back view of the inverter and bracket • Labels on the inverter 13 / 131 Figure 4 – Do not remove the label on the side of the inverter User’s Manual 3PH 100-110KTL-V4 Rev.
  • Page 15: Description Of Functions

    2.2. Description of functions The DC voltage generated by the PV modules is filtered through the input board before entering the power board. The input board also has the function of detecting the insulation impedance and the DC input voltage/current. The power board converts the DC power into AC power. The current converted into AC is filtered through the output board and is then fed into the grid.
  • Page 16: Module Protection

    USB interface for uploading the firmware, remotely uploading is available. F. Software update The PlD efect can be recovered at night to protect the Pv modules. G. PID recovery 2.3. Module protection The inverter is equipped with a protection system that automatically shuts down the system during power A.
  • Page 17: Others

    2.4. Others Initial short-circuit AC current is 756.7A-peak As indicated in VDE-AR-N 4105:2018-11, section 6 Construction of the power generation • system/network and system protection (NS protection), the requirements for the network and system • protection differ depending on the maximum apparent power(SAmax∑SAmax) of the generating and storage units connected to the same network connection point.
  • Page 18: Inverter Storage

    2.5. 3. Inverter Storage If inverter is not installing immediately, storage condition need meet below requirements: Place inverter into the original package and leave desiccant inside, sealed tight with taps. Keep the storage temperature around -40°C~70°C, Relative humidity 5~95%, no conden- sation •...
  • Page 19: Installation

    3. Installation This chapter describes how to install the 3PH 100-110KTL-V4 inverter. General information in this chapter Installation notes: • DO NOT install 3PH 100-110KTL-V4 inverters near flammable materials. • DO NOT install 3PH 100-110KTL-V4 inverters in an area where flammable or explosive materials are stored.
  • Page 20: Installation Process

    Carefully check the contents of the packaging before installation, making sure that no element inside the Contents of the packaging packaging is missing or damaged. The package should contain the following components: Pictures Description Quantity AZZURRO 3PH 100-110KTL-V4 1 PCS Rear Panel 1 PCS 19 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev.
  • Page 21 PV+ input connector 20pcs PV- input connector 20pcs PV+ metal pin 20pcs PV- metal pin 20pcs M10*90Hexagon screws 4 PCS M6*30 Hexagon screws 2 PCS Manual 1PCS Warranty Card 1PCS 20 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev.
  • Page 22: Installation Tools

    Quality Certificate 1PCS COM 16pin connector 1PCS 3.3. Installation tools The following tools are required for installation of the inverter and electrical connections; therefore, they must be prepared before installation. Tool Function Drill To drill holes in the wall for Recommended drill bit: 10mm fixing the bracket To screw and unscrew screws for...
  • Page 23 To crimp the RJ45 connectors for RJ45 crimping tool the communication cables To insert the expansion plugs Rubber hammer into the wall holes To remove the DC connectors MC4 removal tool from the inverter Diagonal pliers To cut and tighten the cable ends To remove the outer sheath of Wire stripping tool the cables...
  • Page 24: Installation Position

    Level To make sure the bracket is level ESD gloves Protective clothing Safety goggles Protective clothing 3.4. Installation position Choose an appropriate installation location for the inverter. Follow the requirements below to determine the installation position. 23 / 131 User’s Manual 3PH 100-110KTL-V4 Rev.
  • Page 25 Figure 6 – Requirements for installing a single inverter 24 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev. 1.1 of 15/03/2021 - Application: GID...
  • Page 26 Figure 7 – Requirements for installing multiple inverters For safety reasons, ZCS S.p.A. and/or its partners may not carry out any technical repairs or maintenance work, or move the inverter from and to the ground if it is installed at a height of more than 180 Note: cm from the ground.
  • Page 27: Moving The 3Ph 100-110Ktl-V4 Inverter

    3.5. Moving the 3PH 100-110KTL-V4 inverter 1) When opening the packaging, insert your hands into the slots on both sides of the inverter and take a This section describes how to move the inverter correctly hold of it as shown in Figure below. Two people are needed to carry out this operation in order to ensure the safety of people and the correct handling of the inverter.
  • Page 28 4) Insert the expansion bolt vertically into the hole; 5) Align the rear panel with the hole positions, fix the rear panels on the wall by tightening the expansion bolt with the nuts. 6) Lifting equipment. Lift the inverter and hang it on the rear panel, and fixing both side of inverter with M6 screw (accessories). 27 / 131 User’s Manual 3PH 100-110KTL-V4 Rev.
  • Page 29 Fastened and tied the rope through two rings. Lifting inverter 50 mm above ground by using lifting equipment, check the tightening device of the hoisting ring and rope. After confirming that the binding connection is secure, lift the inverter to the destination. 28 / 131 User’s Manual 3PH 100-110KTL-V4 Rev.
  • Page 30 • Keep balance when lifting the inverter, avoid to crash on wall or other objective . • Stop working in bad weather condition such as raining, heavy fog, winding. Attention 29 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev.
  • Page 31: Bracket Installation

    3.6. Bracket Installation 1) Placed the rear panel on the mounting wall, determine the mounting height of the bracket and mark the mounting poles accordingly. Drilling holes by using Hammer Drill, keep the hammer drill perpendicular to the wall and make sure the position of the holes should be suitable for the expansion bolts. Figure 9 - Drilling holes on the mounting wall 2) Use wall mount bracket, ensure the pole position are in same level by using level rule and take a mark with maker.
  • Page 32 Figure 12 - Fix wall bracket 5) Repeat step 4). Note: if height between ground and bracket is less than 1.3m, use auxiliary handle for installation. Otherwise, use lifting equipment. 31 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev.
  • Page 33: Electrical Connections

    4. Electrical connections This chapter describes the electrical connections of the 3PH 100-110KTL-V4 inverter. Carefully read this section before connecting the cables. NOTE: Before making any electrical connections, ensure that the DC and AC circuit breakers are open. Remember that the accumulated electrical charge remains in the inverter capacitor after the DC and AC circuit breakers have been switched off.
  • Page 34: Electrical Connections

    4.1. Electrical connections Figure 13 - Flowchart for connecting cables to the inverter 4.2. Terminal connector Connector description as below: *take picture as reference Name Description DC input terminals PVX+/PVX- PV connector USB/WIFI port USB/WIFI For WIFI Communication RS485 Modbus/DRMs RS485/DRMs RS485 Communication port/DRMs port AC output terminals...
  • Page 35: Connecting Pngd Cables (Grounding)

    4.3. Connecting PNGD cables (grounding) Connect the 3PH 100-110KTL-V4 inverter to the ground electrode using ground protection cables (PGND). 3PH 100-110KTL-V4 The inverter does not have a transformer, therefore the positive and negative polarities of the photovoltaic string do NOT need to be grounded.
  • Page 36: Connecting The Ac Output Power Cables

    3) Remove the screw from the bottom side of inverter (Shown as figure), connect the grounding cable to the grounding point and tighten the grouping screw. Torque is 6-7Nm. Note: To ensure the anti-corrosion performances of the ground terminals, apply silica gel on them after connecting the ground cable.
  • Page 37 If open the wiring box on snowing or raining day, please take protective measures to avoid the snow and rain enter wiring box. Otherwise, should not open the wiring box. Please do not unused screw in the wiring box. Figure 17- Open wiring box Wiring Terminal and Precautions Note: Before connect to grid, please ensure the grid voltage and frequency of local grid meet the requirement...
  • Page 38 Figure 19 - AC Terminal size The section will use a five core wire as a sample, four core wire has same connection process. Wring Procedure The table below presents recommend AC cable size. Cable cross - Type Cable cross-sectional Multi-core cable Single-core cable sectional area of...
  • Page 39 5) Crimp the Terminal. 6) Depending on the grid configuration, connect L1, L2, L3 and N to the terminals according to the label and tighten the screw on the terminal using a screwdriver. 38 / 131 User’s Manual 3PH 100-110KTL-V4 Rev.
  • Page 40: Connecting The Dc Input Power Cables

    Single core cable is wired as follows: Phase lines use M12 terminal connector, PE line use M8 terminal connector. The position of“PE”Line Note: and “N”Line should not be opposite. Opposite position may cause inverter permanently faulty. As shown in the figure below ,for HV model ,the N-wire does not need to be connected. 7) Closed wiring box cover, and tighten the screw.
  • Page 41 Note: Connecting PV strings into inverter must following the below procedure. Otherwise, any faulty cause by inappropriate operation will be including in the warranty case. Ensure the maximum short circuit current of PV strings should less than the maximum inverter DC current input.And three “DC switch”...
  • Page 42 2) Crimp the PV metal contact pin to the striped cable using a proper crimping pliers. 3) Insert wire into the connector cap nut and assemble into the back of male or female plug, When you heard a “click”, the pin tact assembly is seated correctly. (3. Positive Connector, 4. negative connector). 4) Measure PV voltage of DC input with multimeter, verify DC input cable polar and connect DC connector with inverter until hearing a slight sound indicated connection succeed.
  • Page 43 Note: Please use multimeter to make sure the PV array positive pole and negative pole! Dealing:If need to remove the PV connector from inverter side, please use the Removal Tool as below diagram, move the connector gently. To remove the positive and negative connectors from the inverter, insert a removal tool in the bayonet Removal procedure coupling and press the tool with adequate force, as shown in the figure below.
  • Page 44: Wiring Method Recommended

    4.6. Wiring method recommended The inverter has a total of 20 DC input terminals, of which the branch route of MPPT1~MPPT4 is controlled by DC SwlTCH 1, the branch route of MPPT5~MPPT7 is controlled by DC SwlTCH 2 and the branch route of MPPT8~MPPT10 is controlled by DC SwlTCH 3.
  • Page 45: Connecting The Communication Cables

    By the USB acquisition stick (WiFi), transfer the inverter power output information, alarm WIFI information, operation state to the PC terminal or local data acquisition device, then uploaded to the server. Register remote monitoring of AZZURRO 3PH 100-110KTL-V4 at its relevant website or APP according to monitoring device SN. 44 / 131 User’s Manual 3PH 100-110KTL-V4...
  • Page 46 COM-Multi function communication port The table below presents recommend com cable size. Outer diameter Area Name Type (mm) (mm²) RS485 Communication Outdoor shielded twisted pair meets local 3 core: 4~8 0.25~1 Wire standards Port Description: Define Function Note RS485A RS485 signal+ RS485A RS485 signal+ Wire connection monitoring or...
  • Page 47 Procedure: Communications Port Description A. Logic interface for AS/NZS 4777.2:2020, also known as inverter demand response modes (DRMs). Logic interface The inverter will detect and initiate a response to all supported demand response commands within 2 s. The inverter will continue to respond while the mode remains asserted. DRM1/5 Function DRM2/6...
  • Page 48 Connected to (RRCR) Pin name Relay contact 1 input K1 - Relay 1 output Description Relay contact 2 input K2 - Relay 2 output Relay contact 3 input K3 - Relay 3 output Relay contact 4 input K4 - Relay 4 output Relays common node Function description of the terminal Relay status: close is 1, open is 0...
  • Page 49 C. Logic interface for EN50549-1:2019, is in order to cease active power output within ive seconds following an instruction being received at the input interface. Figure 24 – Inverter – RRCR Connection Connected to (RRCR) Pin name Description Relay contact 1 input K1 - Relay 1 output K1 - Relay 1 output Relay status: close is 1, open is 0...
  • Page 50 If only one AZZURRO 3PH 100-110KTL-V4 is used, use a communication cable, refer to section for COM pin definition, and choose either of the two RS485 ports. Note: The length of the RS485 communication cable should be less than 1000 m. The length of the WiFi communication cable should be less than 100m.
  • Page 51: Commissioning The Inverter

    5. Commissioning the inverter 5.1. Safety inspection before commissioning Make sure that the DC and AC voltages fall within the range permitted by the inverter. Attention Before turning on the inverter, it is necessary to examine the photovoltaic string. Check the open- Photovoltaic strings •...
  • Page 52: Starting The Inverter

    5.2. Starting the inverter 1) Turn ON the DC switch both on the field panel and on the photovoltaic inverter (if present); wait for the screen to turn on. 2) Turn ON the AC switch installed on the wall. When the photovoltaic string generates enough direct current, the inverter will start automatically. The word “normal”...
  • Page 53: Operating Interface

    6. Operating interface This section describes the display and its operation, as well as the buttons and LED indicators of the 3PH General information in this chapter 100-110KTL-V4 inverters. 6.1. Operating panel and display Buttons and LED indicators Figure 24 - LCD display with buttons and LED indicators Main buttons: ˄...
  • Page 54: Main Interface

    6.2. Main interface LCD interface indicated inverter status, alarm information, communication connection, PV input current and voltage, grid voltage,current and frequency, today generation, total generation. Inverter working status, PV 1 -12 PV input voltage and current. Inverter working status, PV generated power. Inverter working status, today generated electricity.
  • Page 55 Inverter working status, grid voltage and current. Inverter working status, grid voltage and frequency. Inverter working status, Wi-Fi/ RS485 status. Inverter faulty alarm. When power turn on, LCD interface displays INITIALIZING, refer below picture. 54 / 131 User’s Manual 3PH 100-110KTL-V4 Rev.
  • Page 56 When control board successfully connected with communication board, the LCD display the current state of the inverter,display as shown in the figure below. Inverter states includes: wait, check, normal, fault and permanent Wait: Inverter is waiting to Check State when reconnect the system. In this state, grid voltage value is between the max and min limits and so on;...
  • Page 57: Main Menu

    6.3. Main menu Long press the down button under standard interface to enter into main interface, Main interface including below information: Normal ---------Long press DOWN button 1.Enter Setting 2.Event List 3.SystemInfo 4.Display Time 5.Software Update The “Settings” menu contains the following sub-menu: Enter setting Interface as below --------Long press DOWN button...
  • Page 58 Set the address (when you need to monitor multiple inverters simultaneously),Default 01. Set address • Azzurro 3PH 100-110KTL-V4 has 10 MPPT, these MPPTs can work interdependently, or divided into Set Input mode • parallel mode. User can change the setting according to the configuration.
  • Page 59 Set hard anti-reflux switch and percentage. Hard Reflux • Enable or disable logical interfaces. It is use for below standard Australia (AS4777), Europe General Logic interface • (50549), German(4105) Shadow scanning, when the component is blocked or abnormal, causing multiple power peaks, by enabling •...
  • Page 60 User can modify the Safety parameters of the machine through the USB flash disk, and the user needs to SetSafety • copy the parameter information that needs to be modified into the USB flash disk card in advance. Once the USB stick is inserted into the inverter, press the up and down keys to select the safety standard region, press and hold the down key to enter the standard selection under the region, and then turn the page to select the safety standard.
  • Page 61 TrinaHome Thai-MEA HongKong SKYWORTH 50Hz LV-50Hz CSISolar CHINT South Africa China-MV SA-HV China-HV China-A DEWG JOLYWOOD Dubai DEWG-MV France FAR Arrete23 047-106 FR VDE0126-HV Croatia Croatia France VFR 2019 Lithuania Lithuania France Estonia Estonia VDE0126 Enedis VDE0126-HV Enedis Columbia Columbia Columbia-LV VFR2019 Enedis 112-120...
  • Page 62 “SystemInfo” Interface as below ------Long press DOWN button 3.SystemInfo 1.Inverter Type 11.Reflux Enable 2.Serial Number 12.Reflux Power 3.General Soft Version 13.DRMs0 4.General Hard Version 14.DRMn 5.Safety 15.Mppt Scan 6.Safetyswer 16.Active Power 7.Safety Hardver 17.PC Select 8.Safety Hardver 18.Poer Ration 9.Input Mode 19.Ground Detection 10.Remote State The user enters the main menu by long pressing the DOWN button, short press and turns the page to select...
  • Page 63: Updating Inverter Software

    6.4. Updating Inverter Software On first installation, all Zucchetti inverters must be updated to the latest firmware version found in the www.zcsazzurro.com website, unless the inverter is already updated to the version on the website or to a later version (see image below). 3PH 100-110KTL-V4 inverters must be upgraded using an 8 GB USB 2.0 stick.
  • Page 64 Figure 25 - Remove communication broad cover 2) Insert USB into computer. 3) Download the firmware of your inverter from the products section (storage inverters) of the 4) Insert USB drive into the USB port of inverter. www.zcsazzurro.com website, selecting the inverter model you own 5) Save only the firmware folder containing the .bin files on the USB stick.
  • Page 65: Troubleshooting And Maintenance

    7. Troubleshooting and maintenance 7.1. Troubleshooting This section describes the potential errors for this product. Please read carefully for the following tips when doing the troubleshooting: 1) Check the warning message or faulty codes on the inverter information panel. 2) If not any error code display on the panel, please check the following lists: Is inverter be installed in a clean, dry, ventilated environment? Is the DC switch turn off? Are the cable cross section area and length meet the requirement?
  • Page 66 If the fault occurs occasionally, the possible cause is that the external circuits are abnormal occasionally. inverter automatically returns to normal operating status after the fault is GFCIFault GFCI Fault rectified.If the fault occurs frequently and lasts a long time,check whether the ID05 insulation resistance between the PV array and earth(ground) is too low, then...
  • Page 67 DC input current sampling HwADFaultIdc faulty ID24 ID25 HwADErrDCI(DC) HwADErrIdcBranch ID26 The GFCI sampling value ConsistentFault_GFCI between the master DSP and salve DSP is not consistent ID29 The Grid voltage sampling ConsistentFault_Vgrid value between the master and salve is not consistent ID29-ID38 Internal faults of inverter, ID30 switch OFF inverter, wait for 5 minutes,...
  • Page 68 Heat sink1 over-temperature TempFault_HeatSink1 protection Heat sink2 over-temperature ID50 TempFault_HeatSink2 protection Heat sink3 over-temperature ID51 TempFault_HeatSink3 protection For Inner BMS battery, make sure that Heat sink4 over-temperature ID52 the battery NTC cable is properly TempFault_HeatSink4 protection connected. Make sure the inverter is Heat sink5 over-temperature ID53 installed where there is no direct...
  • Page 69 LLC BUS overvoltage LLCBusOVP protection ID71 SwBusRmsOVP BUS overvoltage ID72 Inverter bus voltage SwBusInstantOVP overvoltage software ID73 Inverter bus voltage Reserved instantaneous value overvoltage software ID81 Dci overcurrent DciOCP protection ID82 SwOCPInstant Dci overcurrent faulty Output instantaneous current Reserved ID83 protection Output effective value ID84...
  • Page 70 PV hardware HwPVOCP overflows ID102 HwACOCP ID103 Ac output hardware overflows Hardware differential over- HwDiffOCP current ID104 Check whether the meters wiring is MeterCommFault Meters communication fault correct. ID105 This faulty only cause alarm, It will not OverTempDerating Overtemperature derating directly cause the system to enter a fault state.
  • Page 71 unrecoverHwPVOCP Input hardware overcurrent permanent fault ID139 unrecoverRelayFail Relay permanent fault Internal faults of inverter, switch OFF inverter, wait for 5 minutes, then ID140 unrecoverVbusUnbalan switch ON inverter. Check whether the Unbalanced permanent fault problem is solved. If no, please contact technical ID141 support.
  • Page 72 The inverter is performed for remote RemoteDerating RemoteDerating load reduction ID165 inverter loaded by the LogicInterfaceDerating Logical interface derating execution logic interface ID166 The inverter is implemented to AlarmAntiRefluxing Anti Refluxing derating prevent countercurrent load drop ID167 Please check whether the fan 1 of FanFault1 Fan 1 Alarm inverter is running normally...
  • Page 73: Maintenance

    7.2. Maintenance Inverters generally do not require daily or routine maintenance. In any case, for proper long-term operation of the inverter, make sure that the heatsink for cooling the inverter has enough space to ensure adequate ventilation and that it is not obstructed by dust or other items. Use an air compressor, a soft dry cloth or soft-bristled brush to clean the inverter.
  • Page 74: Fan Maintenece

    7.4. Fan maintenece 1. Before replacing a fan, power f the inverter. Follow below steps for maintenance: 2. when replacing a fan, use insulation tools and wear personal protective devices. Step 1: Remove the screw on the fan tray and save it, Extract the fan bracket about 5-10cm. Step 2: Cut the ties holding the fan cable, unplug the connection terminals, and pull out the fan bracket.
  • Page 75: Replacing A Fan

    Step 4: Follow step 2 to align the fan bracket with the mounting position, push in the fan bracket and connect the connection terminals. Then tighten the screws on the fan bracket according to step 1. 7.4.1. Replacing a fan 1.
  • Page 76 Step 4: Remove the faulty fan. Step 5: lnstall the new fan, following the order of steps 4,3. Step 6: Clean the fan bracket to make sure there are no foreign objects left behind. Step 7: Follow step 2 to align the fan bracket with the mounting position, push in the fan bracket and connect the connection terminals.
  • Page 77: Uninstalling

    8. Uninstalling 8.1. Uninstallation steps Disconnect the inverter from the AC grid by opening the AC circuit breaker. Disconnect the inverter from the photovoltaic strings by opening the DC circuit breaker. • Wait 5 minutes. • Remove the DC connectors. •...
  • Page 78: Technical Data

    9. Technical data 9.1. Technical data 3PH 100-110 KTL-V4 77 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev. 1.1 of 15/03/2021 - Application: GID...
  • Page 79: Monitoring Systems

    10. Monitoring systems ZCS monitoring Product code Product photo Portal Possibility to send commands and monitoring monitoring to update the inverter remotely in case of technical support ZSM-WIFI ZSM-ETH ZSM-4G Datalogger 4-10 Inverters Datalogger up to 31 Inverters 78 / 131 User’s Manual 3PH 100-110KTL-V4...
  • Page 80: External Wi-Fi Adapter

    10.1. External Wi-Fi adapter 10.1.1. Installation Unlike the internal Wi-Fi card, the external adapter must be installed for all compatible inverters. However, the procedure is quicker and easier as there is no need to open the front cover of the inverter. In order to monitor the inverter, the RS485 communication address must be set to 01 directly from the display.
  • Page 81: Configuration

    Figure 27 – Inserting and securing the external Wi-Fi adapter 4) Switch on the inverter by following the procedure described in the manual. 10.1.2. Configuration Configuration of the Wi-Fi adapter requires the presence of a Wi-Fi network near the inverter in order to achieve stable transmission of data from the inverter adapter to the Wi-Fi modem.
  • Page 82 If the Wi-Fi signal does not reach the inverter, a system must be installed to amplify the signal and bring it to the installation location. 1) Activate the search for the Wi-Fi networks on your telephone or PC so that all the networks visible by your device are displayed.
  • Page 83 2) Connect to a Wi-Fi network generated by the inverter's Wi-Fi adapter (i.e. AP_*******, where ******* indicates the serial number of the Wi-Fi adapter shown on the label of the device), which operates as an access point. Figure 30 - Connection to Access Point for Wi-Fi adapter on iOS smartphone (left) and Android smartphone (right) 3) If you are using a second-generation Wi-Fi adapter, you will be prompted for a password to connect to the inverter's Wi-Fi network.
  • Page 84 Figure 31 – Password of external Wi-Fi adapter Note: To ensure that the adapter is connected to the PC or smartphone during the configuration procedure, enable automatic reconnection of the AP_******* network. Figure 32 – Password entry prompt Note: the Access Point is not able to provide internet access; confirm to maintain the Wi-Fi connection, even if the internet is not available 83 / 131 User’s Manual 3PH 100-110KTL-V4...
  • Page 85 Figure 33 – Screen indicating that the Internet cannot be accessed 4) Open a browser (Google Chrome, Safari, Firefox) and enter the IP address 10.10.100.254 in the address bar at the top of the screen. In the box that appears, enter “admin” as both the Username and Password. Figure 34 –...
  • Page 86 5) The status screen will open, showing the logger information such as the serial number and firmware version. Check that the Inverter Information fields are filled in with the inverter information. The language of the page can be changed using the command in the top right-hand corner. Figure 35 –...
  • Page 87 Figure 36 – Screen for selecting the available wireless network (1) 8) Enter the password of the Wi-Fi network (Wi-Fi modem), clicking on Show Password to make sure it is correct; the password should not contain special characters (&, #, %) and spaces. Note: During this step, the system is not able to ensure that the password entered is the one actually requested by the modem, therefore please make sure you enter the correct password.
  • Page 88 Figure 37 – Screen for entering the password of the wireless network (2) 9) Click “Next” again without ticking any of the options relating to the system security. Figure 38 - Screen for setting the security options (3) 87 / 131 User’s Manual 3PH 100-110KTL-V4 Rev.
  • Page 89 10) Click “OK”. 11) At this point, if the configuration of the adapter is successful, the last configuration screen will Figure 39 – Final configuration screen (4) appear, and the telephone or PC will unpair from the inverter’s Wi-Fi network. 12) Manually close the web page with the Close key on the PC por remove it from the background of the telephone.
  • Page 90: Verification

    10.1.3. Verification Wait two minutes after configuring the adapter and then go back to the Wi-Fi network selection screen to verify that the AP_******* network is no longer present. The absence of the Wi-Fi network in the list will confirm the successful configuration of the Wi-Fi adapter. Figure 41 –...
  • Page 91 Figure 42 – Status screen 1) Initial status: Status of LEDs present on the adapter NET (left LED ): off COM (central LED): steady on READY (right LED): flashing on 2) Final status: Figure 43 - Initial status of LEDs NET (left LED): steady on COM (central LED): steady on READY (right LED): flashing on...
  • Page 92 If the NET LED does not light up or if the Remote Server A option in the Status page still shows “Not Figure 44 - Final status of LEDs Connected”, the configuration was not successful, i.e. the wrong router password was entered or the device was disconnected during connection.
  • Page 93: Troubleshooting

    10.1.4. Troubleshooting Status of LEDs present on the adapter 1) Irregular communication with inverter NET (left LED): steady on COM (central LED ): off READY (right LED): flashing on Figure 46 - Irregular communication status between inverter and Wi-Fi Check the Modbus address set on the inverter: Enter the main menu with the ESC key (first key on the left), go to System Info and press ENTER to enter the submenu.
  • Page 94 Restart the adapter: Press the reset button for 5 seconds and release After a few seconds, the LEDs will turn off and will start to flash quickly • The adapter will now be reset without having lost the configuration with the router •...
  • Page 95 a) Check that the 3G/LTE connection is active on your smartphone. Go to the Settings menu of the • Using an Android mobile phone as a modem the phone), operating system (the gear icon on the screen with a list of all the apps installed on select “Other”...
  • Page 96 Figure 50 - Configuration of an iOS smartphone as a hotspot router At this point, it is necessary to re-configure the Wi-Fi adapter using a PC or smartphone other than the one used as a modem. During this procedure, when asked to select the Wi-Fi network, choose the one activated by the smartphone and then enter the password associated with it (which can be changed from the personal hotspot settings).
  • Page 97: Ethernet Adapter

    10.2. Ethernet adapter 10.2.1. Installation Installation must be carried out for all inverters compatible with the adapter. However, the procedure is quicker easier there need open front cover inverter. Proper operation of the device requires the presence of a modem correctly connected to the network and in operation in order to achieve stable data transmission from the inverter to the server.
  • Page 98 3) Remove the ring nut and the waterproof cable gland from the adapter to allow the network cable to pass through; then insert the network cable network into the appropriate port on the inside of the adapter and tighten the ring nut and cable gland to ensure a stable connection. Figure 52 –...
  • Page 99: Verification

    5) Connect the other end of the network cable to the ETH output (or equivalent) of the modem or a suitable data transmission device. Figure 54 – Connecting the network cable to the modem 6) Switch on the inverter by following the procedure described in the manual. 7) Unlike Wi-Fi cards, the Ethernet adapter does not need to be configured and starts transmitting data shortly after the inverter is switched on.
  • Page 100 Figure 55 - Initial status of LEDs 2) Final status: NET (left LED): steady on COM (central LED): steady on SER (right LED): flashing on Figure 56 - Final status of LEDs 99 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev.
  • Page 101: Troubleshooting

    10.2.3. Troubleshooting Status of LEDs present on the adapter Irregular communication with inverter NET (left LED): steady on COM (central LED ): off SER (right LED): flashing on Figure 57 - Irregular communication status between the inverter and adapter Check the Modbus address set on the inverter: Enter the main menu with the ESC key (first key on the left), go to System Info and press ENTER to enter the submenu.
  • Page 102: Adapter

    10.3. 4G adapter The ZCS 4G adapters are sold with a virtual SIM integrated into the device with data traffic fee included for10 years, which is adequate for the proper transmission of data to monitor the inverter. In order to monitor the inverter, the RS485 communication address must be set to 01 directly from the display.
  • Page 103 2) Remove the cover for accessing the Wi-Fi/ GPRS connector on the bottom of the inverter by unscrewing the two cross-head screws (a), or by unscrewing the cover (b), depending on the inverter model, as shown in the figure. Figure 59 – Port of the 4G adapter 3) Insert the 4G adapter into the appropriate port, making sure to follow the direction of the connection and ensure correct contact between the two parts.
  • Page 104: Verification

    4) Switch on the inverter by following the procedure described in the manual. 5) Unlike Wi-Fi cards, the 4G adapter does not need to be configured and starts transmitting data shortly after the inverter is switched on. 10.3.2. Verification After installing the adapter, within the next 3 minutes check the status of the LEDs on the device to ensure that the device is configured correctly.
  • Page 105 Figure 62 - Final status of LEDs 1) Irregular communication with inverter Status of LEDs present on the adapter NET (left LED): on COM (central LED ): off SER (right LED): on Check the Modbus address set on the inverter: Figure 63 - Irregular communication status between inverter and adapter Enter the main menu with the ESC key (first key on the left), go to System Info and press ENTER to enter the submenu.
  • Page 106 2) Irregular communication with remote server: NET (left LED): flashing on COM (central LED): on SER (right LED): flashing on Figure 64 - Irregular communication status between the adapter and remote server Check that the 4G signal is present in the installation location (the adapter uses the Vodafone network for 4G transmission;...
  • Page 107: Datalogger

    10.4. Datalogger ZCS monitoring Product code Product photo Portal Possibility to send commands and monitoring monitoring to update the inverter remotely in case of technical support ZSM-WIFI ZSM-ETH ZSM-4G Datalogger 4-10 Inverters Datalogger up to 31 Inverters 10.4.1. Preliminary notes on how to configure the datalogger The AzzurroZCS inverters can be monitored via a datalogger connected to a Wi-Fi network present at the place of installation or via an ethernet cable connected to a modem.
  • Page 108 “Azzurro System” app or through the “www.zcsazzurroportal.com” website. All the Azzurro ZCS inverters can be monitored using the datalogger; different models or families of inverters can also be monitored. 107 / 131 User’s Manual 3PH 100-110KTL-V4...
  • Page 109: Electrical Connections And Configuration

    10.4.2. Electrical connections and configuration All the Azzurro ZCS inverters have at least one RS485 connection point. The connections can be made via the green terminal block or via the RJ45 plug inside the inverter. Use positive and negative conductors. There is no need to use a conductor for the GND. This applies to both the terminal block and the plug.
  • Page 110 Figure 68 – Tightening the network cable to the RS485 terminal block For 3PH HYD5000-HYD20000-ZSS three-phase hybrid inverters, use only one positive and one negative of Figure 69 – Connecting the serial line via the RS485 terminal block and via the RJ45 plug those shown in the figure below.
  • Page 111 For 3000-6000 TLM-V3, 3PH 100-110KTL-V4 photovoltaic inverters and HYD 3PH 5000-20000 ZSS three-phase hybrid inverters, use only one positive and one negative of those shown in the figure below. Figure 6 – Connecting the serial line via the communication connector for 1PH 3000- 6000 TLM-V3 inverters For 1PH HYD3000-HYD6000-ZSS-HP single-phase hybrid inverters, use only one positive and one negative of those shown in the figure below Figure 7 –...
  • Page 112 c. Position the dip switches of the last inverter of the daisy chain as shown in the figure below for activating the 120 Ohm resistor and closing the communication chain. If there are no switches, physically connect a 120 Ohm resistor to terminate the bus. Figure 81 –...
  • Page 113: Zsm-Datalog-04 And Zsm-Datalog-10 Devices

    10.4.3. ZSM-DATALOG-04 AND ZSM-DATALOG-10 DEVICES The initial status of the LEDs on the datalogger will be: POWER steady on 485 steady on • LINK off • STATUS steady on • • 10.4.4. WI-FI CONFIGURATION To configure the datalogger via Wi-Fi, please refer to the chapter on monitoring systems, as the configuration is similar to that of any type of Wi-Fi adapter.
  • Page 114 Figure 84 - Wi-Fi network search on iOS smartphone (left) and Android (right) Note: Disconnect from any Wi-Fi networks to which you are connected by removing automatic access. Figure 85 - Disabling automatic reconnection to a network Connect to a Wi-Fi network generated by the datalogger (i.e. AP_*******, where ******* indicates the serial number of the datalogger shown on the label of the device), which operates as an Access Point.
  • Page 115 Figure 86 - Password entry prompt Note: the Access Point is not able to provide internet access; confirm to maintain the Wi-Fi connection, even if internet is not available. Figure 87 - Screen showing that the Internet cannot be accessed Open a browser (Google Chrome, Safari, Firefox) and enter the IP address 10.10.100.254 in the address bar at the top of the screen.
  • Page 116 Figure 88 - Screen for logging into the web server to configure the datalogger The status screen will open, showing the datalogger information such as serial number and firmware version. Check that the fields relating to the Inverter Information are filled in with the information of all the inverters connected.
  • Page 117 Click on the Wizard setup button in the left-hand column. Now click on the Start button to start the configuration wizard. Figure 90 – Screen for starting (1) the Setup Wizard Check the “Cable Connection” option and then click “Next.” Figure 90 - Network cable connection selection screen Make sure that the “Enable”...
  • Page 118 router, then click Next. Figure 91 – Screen for automatically obtaining the IP address (5) Click on Next without making any changes. Figure 92 - Screen for setting the security options (6) 117 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev.
  • Page 119 Complete the configuration procedure by clicking OK, as shown in the following screen. Figure 93 – Final configuration screen (7) If the configuration procedure is successful, the following screen will appear. If this screen does not appear, try refreshing the browser page. The screen will prompt you to manually close the page;...
  • Page 120: Checking That The Datalogger Has Been Configured Correctly

    10.4.6. Checking that the datalogger has been configured correctly Wait two minutes after completing the configuration of the device. First of all, check that the LINK LED on the device is on and steady. Enter the IP address 10.10.100.254 again, and the login credentials (“admin” for both username and Figure 95 –...
  • Page 121 Figure 96 – Main status screen and checking of correct configuration If the Remote Server A item in the Status page is still “Unpingable”, the configuration was not successful, i.e. Figure 97 - main status screen and checking of correct configuration the incorrect router password was entered or the device was disconnected during connection.
  • Page 122 Close the web page and enter the Status page again. At this point, the configuration procedure can be repeated again. Figure 98 – Reset Screen 121 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev. 1.1 of 15/03/2021 - Application: GID...
  • Page 123: Zsm-Rms001/M200 And Zsm-Rms001/M1000 Devices

    10.4.7. ZSM-RMS001/M200 and ZSM-RMS001/M1000 Devices 10.4.7.1. Mechanical description and Datalogger interface Mechanical Dimensions: 127mm x 134 x 52 mm Protection rating: IP20 The usable ports are indicated below. LAN cable connection port RS485 cable connection port Battery pack Power supply connection port connection port Figure 99: Datalogger rear panel...
  • Page 124: Connecting The Datalogger To The Inverters

    10.4.7.2. Connecting the Datalogger to the inverters A serial communication via RS485 cable is provided for connecting to the inverters. The GND cable does not need to be connected to the inverters. Follow the connections as shown in the table below.
  • Page 125: Connecting The Lm2-485 Pro Cell Irradiance And Temperature Sensor To The Datalogger

    10.4.7.5. Connecting the LM2-485 PRO cell irradiance and temperature sensor to the datalogger For proper installation, make sure to connect the sensor signal cable and the power cable. In particular, the sensor of the signal cables must be connected in a daisy chain configuration to the remaining devices on the RS485 bus, as shown in the table below.
  • Page 126: Configuring The Datalogger

    10.4.8. Configuring the Datalogger Connect to the website dlconfig.it and login by entering the temporary credentials: Username = admin and Password = admin. In the screen that opens, enter the serial number(S/N) of the datalogger to be configured and click “SEARCH”.
  • Page 127 If a meter is one of the devices connected to the Datalogger, select the type of Meter/Datalogger communication interface and the relative communication protocol. Once this operation has been completed, update the new configuration by clicking “Confirm,” which will allow you to register the devices associated with the datalogger. 126 / 131 User’s Manual 3PH 100-110KTL-V4 Rev.
  • Page 128: Configuring The Datalogger On The Zcs Azzurro Portal

    From this moment, the datalogger is correctly configured (all devices must be in the “saved” status) and therefore a new installation can be created on the ZCS Azzurro portal for associating the datalogger and the devices connected to it. 10.4.8.1.
  • Page 129: Network Configuration

    Once the “location” of the field has been entered, click “Calculate Location Information” to allow the system to obtain the latitude, longitude and time zone of the installation. Click “Confirm” to complete the configuration of the field. You only need to wait a few minutes to view the data flow on the ZCS Azzurro portal.
  • Page 130: Local Monitoring

    To complete the operation, click “Apply” (see arrow). 10.4.9. Local monitoring The datalogger makes it possible to obtain an additional monitoring system (local monitoring), which can be used locally on a web page (therefore, also without an internet connection) and accessed from any device present in the same local network as the datalogger.
  • Page 131: Features Of Local Monitoring

    10.4.9.2. Features of local monitoring After installation and configuration, local monitoring makes it possible to monitor the fundamental parameters of the photovoltaic system, even without an internet connection, from any device connected to the same local network. In particular, it is possible to monitor the power and energy of the inverters and the storage systems over the last 7 days.
  • Page 132: Warranty Terms And Conditions

    11. Warranty terms and conditions To view the Warranty Terms and Conditions” offered by ZCS Azzurro, please refer to the documentation inside the product box and on the website www.zcsazzurro.com. 131 / 131 User’s Manual 3PH 100-110KTL-V4 Rev. 1.2 14/11/2023 Identification: MD-AL-GI-00 Rev.