Description
Full height turnstile (with bicycle access)
MPT-333, MPT-353 and MPB-311
Control unit MGC
Doc. ID: 58170027EN
Version 03

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MPT-333 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Magnetic MPT-333

  • Page 1 Description Full height turnstile (with bicycle access) MPT-333, MPT-353 and MPB-311 Control unit MGC Doc. ID: 58170027EN Version 03...
  • Page 2 Control unit MGC MPT-333, MPT-353 and MPB-311 Original Operating Instructions This document is available as PDF in the Magnetic Autocontrol download area (www.magnetic-access.com). Authorisation is required for download. MAGNETIC AUTOCONTROL GMBH Grienmatt 20 D-79650 Schopfheim Germany Phone +49 7622 695 5 Fax +49 7622 695 802 info@magnetic-germany.com...
  • Page 3: Table Of Contents

    Control unit MGC MPT-333, MPT-353 and MPB-311 Contents Contents Notices on the document Purpose and contents of this description Separate operating instructions Symbols and illustrations used in this document 1.3.1 Warning notes and notes Target group 1.4.1 Personnel – activities and qualifications...
  • Page 4 Control unit MGC MPT-333, MPT-353 and MPB-311 Contents Symbols in the display 5.5.1 Control button functions 5.5.2 Further symbols Setting display contrast Protecting parameterisation from access Parameterising value Switching the "Service" mode on and off Description of menus and parameters "Information"...
  • Page 5 Control unit MGC MPT-333, MPT-353 and MPB-311 Contents Definitions and versions Definitions and versions MPT-333 Definitions and versions MPT-353 Definitions and versions MPB-311 Function description MPT-3x3 Function MPT-3x3 Function sequence MPT-3x3 Start-up and regular movement sequence MPT-3x3 8.3.1 De-energised state 8.3.2...
  • Page 6 Control unit MGC MPT-333, MPT-353 and MPB-311 Contents Corrective action 10.1 Safety in troubleshooting 10.2 Malfunctions pedestrian gate 10.3 Event, warning and error messages – definitions 10.4 Displaying and signalling messages 10.5 Procedure in case of a fault / message 10.6...
  • Page 7: Notices On The Document

    Control unit MGC MPT-333, MPT-353 and MPB-311 Notices on the document Notices on the document Purpose and contents of this description This document describes the control unit MGC from the programme versions listed below. Software number (Software #) and software version (SW version) are displayed in the menu "Module info".
  • Page 8: Symbols And Illustrations Used In This Document

    Control unit MGC MPT-333, MPT-353 and MPB-311 Notices on the document Symbols and illustrations used in this document 1.3.1 Warning notes and notes Warning notes are characterised by pictograms in these instructions. A warning note starts with a signal word that expresses the extent of the hazard.
  • Page 9: Target Group

    Control unit MGC MPT-333, MPT-353 and MPB-311 Notices on the document Target group 1.4.1 Personnel – activities and qualifications All work on the control unit may only be performed by technicians and qualified electricians with the following qualifications. Designation Qualification ›...
  • Page 10: Digital Inputs, Digital Outputs And Relay Outputs

    Control unit MGC MPT-333, MPT-353 and MPB-311 Digital inputs, digital outputs and relay outputs Digital inputs, digital outputs and relay outputs WARNING Improper wiring and parameterisation of the control unit! Improper wiring and parameterisation of the control unit can lead to undesired functions and thus to injuries.
  • Page 11 Control unit MGC MPT-333, MPT-353 and MPB-311 Digital inputs, digital outputs and relay outputs Function Description – Inputs that you assign this function "–" to are being deactivated. | Emergency open Emergency situation (closed-circuit principle) Connect fire brigade switches, emergency opening contacts, etc. to this input.
  • Page 12 Control unit MGC MPT-333, MPT-353 and MPB-311 Digital inputs, digital outputs and relay outputs Function Description Random check function Activate random check function, confirm hits As soon as +24 V DC are applied to this input, the random check function is activated.
  • Page 13 Control unit MGC MPT-333, MPT-353 and MPB-311 Digital inputs, digital outputs and relay outputs Function Description Sensor B1 (internal use) Connection proximity sensor B1 Sensor B1 is connected to this entry by default. The inductive proximity sensor is used to detect the end positions.
  • Page 14: Digital Outputs And Relay Outputs

    Control unit MGC MPT-333, MPT-353 and MPB-311 Digital inputs, digital outputs and relay outputs Digital outputs and relay outputs Definition of "entry" and "exit": ä Page 62, chapter 7. By parameterising the outputs, you assign certain functions to the outputs.
  • Page 15 Control unit MGC MPT-333, MPT-353 and MPB-311 Digital inputs, digital outputs and relay outputs Function Description – Outputs that you assign this function "–" to are deactivated. | Error When the control unit recognises any safety-relevant error or error, the output with this function is deactivated (closed-circuit principle).
  • Page 16 Control unit MGC MPT-333, MPT-353 and MPB-311 Digital inputs, digital outputs and relay outputs Function Description Obstacle detection This function is only available for MPB-311. Obstacle detection during opening or closing of the bicycle door. As soon as an obstacle is detected during movement, this output is activated.
  • Page 17: Plug-In Modules Mfm01, Dm02 And Em01

    Control unit MGC MPT-333, MPT-353 and MPB-311 Digital inputs, digital outputs and relay outputs Plug-in modules MFM01, DM02 and EM01 The MGC control unit is equipped with 5 slots for plug-in modules. The function is permanently assigned via the slot number.
  • Page 18 Control unit MGC MPT-333, MPT-353 and MPB-311 Digital inputs, digital outputs and relay outputs Slot assignment and function MPB-311 Slot Terminal LED plug-in Function number plug-in module module Loop detector module DM02 – – – MFM01: Magnets for locking Magnet RL1...
  • Page 19: Parameterising Mpt-333, Mpt-353 And Mpb-311

    Parameterisation directly at the control unit The turnstile MPT-333 and the turnstile with bicycle access MPB-311 are equipped with a control unit. The control unit is mounted in the support beam and is accessible when the cover of the support beam is dismounted.
  • Page 20: Parameterisation Via The "Mgc.connect" Programme

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising MPT-333, MPT-353 and MPB-311 Parameterisation via the "MGC.Connect" programme The programme "MGC.Connect" is available on the Magnetic website in the download centre. You can also download the programme with the programme for the Service Module SM01 "SM-Downloader".
  • Page 21 Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising MPT-333, MPT-353 and MPB-311 If the connection could not established, the connection settings may have been changed. 1. Open the "Configuration" window. To do so, click the " " button in the header of the MGC.Connect programme.
  • Page 22: Connection Via Ethernet Module Em01

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising MPT-333, MPT-353 and MPB-311 3.2.2 Connection via Ethernet module EM01 Further information on the Ethernet module: Technical Manual "Ethernet Module" (Doc.ID: 5815,0001). For pedestrian gates with the option "Ethernet module EM01", the Ethernet module is installed ex works.
  • Page 23: Description Of The "Mgc.connect" Programme

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of the "MGC.Connect" programme Description of the "MGC.Connect" programme Overview Fig. 4: Exemplary view "MGC.Connect" Button to open the "Configuration" window Button to disconnect or connect the connection Status display of the pedestrian gate...
  • Page 24: Changing The Menu Language For Mgc.connect

    In the "Closed" position the value is 0°. When turning to the left, the value is negative. When turning to the right, the value is positive. Fig. 5: Status display, here as an example MPT-333 with status "OK" Display of symbols: ä Page 25, Table 10 Display of the current status of the output functions "GED red exit"...
  • Page 25 Control unit MGC MPT-333, MPT-353 and MPB-311 Description of the "MGC.Connect" programme Fig. 6: Examples of event displays Example of an event of the type WARNING Confirm pending messages and update display Example of an event of the type ERROR Information on WARNING and ERROR: ä...
  • Page 26: Passage Control" Tab

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of the "MGC.Connect" programme "Passage control" tab Use the "Passage control" tab to test the behaviour of the pedestrian gate. Fig. 7: "Passage control" tab The view offers the following options. Information about the input functions: ä Page 10, chapter 2.1.
  • Page 27: Settings" Tab

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of the "MGC.Connect" programme Button / Description parameters Hold-open time Display of the current hold-open time still available. If several validations are pending, the total hold-open time is not displayed. The hold-open time is counted down again from the set value with each validation.
  • Page 28 Control unit MGC MPT-333, MPT-353 and MPB-311 Description of the "MGC.Connect" programme "General" section Parameter Description Hold-open time "Hold-open time" parameter: ä Page 42 Permanent open "Permanent open" parameter: ä Page 43 Vend count "Vend count" menu: ä Page 44 Interlock "Interlock"...
  • Page 29: Service" Tab

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of the "MGC.Connect" programme "Service" tab The "Service" tab displays the configured exit direction and the locking. For the turnstile, you can adjust the exit direction and locking. In both cases, conversion work is required on the pedestrian gate.
  • Page 30 Control unit MGC MPT-333, MPT-353 and MPB-311 Description of the "MGC.Connect" programme Button / Description parameters Invert Magnet RL1 This parameter is used to specify the switching signal for the Magnet RL1 for locking. Options (display) › [ X ]: Invert magnet RL1 (locked when de-energised): The checkbox is activated.
  • Page 31: Parameterising The Control Unit

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit Parameterising the control unit Changing menu language The default setting in the MGC control unit is the menu language "English". Change the menu language as follows: The operational view is displayed.
  • Page 32 Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit 4. Select the "System" menu with the two middle buttons « », « ». Main menu Settings In-/Outputs Service System Fig. 13: "Main menu – System" view 5. Confirm selection with the right control button « ». The following view is displayed.
  • Page 33 Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit 8. Use the right button « » to select the new menu language. Your selection is marked with the symbol « ». Language German English French Fig. 17: "Language – German, step 2" view 9.
  • Page 34: Entering Password

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit Entering password You need to enter a password in the following cases: › You would like to change parameters in the control unit and the password protection was activated.
  • Page 35: Control Unit Elements

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit 6. Use the right button « » to select the fourth digit of the password. The following view is displayed: Password Fig. 22: "Enter fourth digit of the password" view 7.
  • Page 36: Displays Of The Control Unit

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit Displays of the control unit FlowMotion MPT333 – – – – Fig. 24: Example "Operational view" Pedestrian gate type, here MPT-333 electromotive Status display, here ready for operation Angle of rotation, here 0 Current function of the right control button, here accessing menu "Main menu"...
  • Page 37: Symbols In The Display

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit Symbols in the display 5.5.1 Control button functions The control unit is equipped with 4 control buttons. The function of the control buttons change depending on the current view in the display. The current functions are shown in the display.
  • Page 38: Further Symbols

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit 5.5.2 Further symbols Symbols Description Wrong password entered. Access denied. Reset values to factory settings. To do this, you must enter the password "0000". The next validation is blocked by the random check function.
  • Page 39: Protecting Parameterisation From Access

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit Protecting parameterisation from access You can apply the access to the main menu with password protection. ä Page 54, chapter 6.4.2. Parameterising value Example: Change hold-open time The operational view is displayed.
  • Page 40: Switching The "Service" Mode On And Off

    Control unit MGC MPT-333, MPT-353 and MPB-311 Parameterising the control unit Switching the "Service" mode on and off IMPORTANT! In service mode, all validations from the control unit inputs and via Ethernet are ignored. Switching the "Service" mode on Switch the "Service" switch for the "Service" mode. The LED lights red. The display backlighting flashes.
  • Page 41: Description Of Menus And Parameters

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters Description of menus and parameters "Information" menu Accessing and navigating The operational view is displayed. ä Page 31, Fig. 10. 1. Press left button « ». 2. Use the left button « » to scroll within the menu.
  • Page 42: Settings" Menu

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters "Settings" menu 6.2.1 Hold-open time Operational view > Main menu > Settings > Hold-open time Parameter Description Hold-open time Set the hold-open time. The hold-open time is started by a validation by a control device, such as a card reader.
  • Page 43: Permanent Open

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters 6.2.3 Permanent open Operational view > Main menu > Settings > Permanent open Parameter Description Permanent open You use this parameter to specify whether and after what time the permanent open is activated for a permanent signal at the "Open entry"...
  • Page 44: Vend Count

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters 6.2.5 Vend count Operational view > Main menu > Settings > Vend count Parameter Description Entry Shows the current counter for validations for the passages in zone controlled direction.
  • Page 45 Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters Operational view > Main menu > Settings > Signalling Parameter Description GED mode entry Set the behaviour of the optional GEDs. Options › Off: The display is dark.
  • Page 46: Random Check Function

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters 6.2.7 Random check function IMPORTANT! For certain applications, it makes sense to invert the input assigned with the "Random check function" via the "Invert Inputs/Outputs" menu. The MGC control unit is equipped with the "Random check function" option. This function allows random bag and identity control of persons.
  • Page 47 Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters Operational view > Main menu > Settings > Random check function Parameter Description Options (continued) Mode › (Continued) Random: You can set the random probability using the "Hit range" and "Count of hits"...
  • Page 48 Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters Operational view > Main menu > Settings > Random check function Parameter Description Delete validation Use the "Delete validation" parameter to specify whether the validation is to be deleted automatically in the event of a random hit. Validations are only deleted if the option "Entry"...
  • Page 49: Sensor Bicycle Door

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters 6.2.8 Sensor bicycle door Operational view > Main menu > Settings > Sensor bicycle door Parameter Description Sensor bicycle door This parameter is only available for MPB-311. Select sensor / button for bicycle detection.
  • Page 50: Inverted In-/Outputs

    Description of menus and parameters 6.3.3 Inverted In-/Outputs This menu is only intended for MAGNETIC's service and only accessible with a password. This menu allows you to invert individual inputs and outputs and with it the assigned functions. Customer-side additional relays for signal inversion are therefore not required.
  • Page 51: Service" Menu

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters "Service" menu 6.4.1 Gate HW IMPORTANT! As standard, the turnstile is delivered with the "locking (rotating freely when de-energised)" configuration. If you want a different configuration, convert the locking and adjust the parameters "Invert magnet RL1"...
  • Page 52 Operational view > Main menu > Service > Gate HW Parameter Description Exit direction MPT-333 and MPT-311: Unless otherwise ordered, the turnstile is delivered for the "Entrance side right" design. The control unit is parameterised accordingly. MPT-333: ä Page 62, chapter 7.1 MPB-311: ä...
  • Page 53 Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters Installation version Magnets and Settings MGC The following installation versions are possible for the magnets RL1 and RL2. The settings for the parameters "Invert RL1" and "Invert RL2" depend on the installation version.
  • Page 54: Further Parameters

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters 6.4.2 Further parameters Operational view > Main menu > Service Parameter Description Cycles Display of complete passage procedures. Lifetime Displays the operating hours counter. The operating hours counter records the time, during which the pedestrian gate is supplied with electrical power.
  • Page 55: Passage Counter" Menu

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters "Passage counter" menu Operational view > Main menu > Passage counter Parameter Description From entry Display for the number of completed passages in zone controlled direction. If necessary, the value can be changed.
  • Page 56: Menu "Detector 1 (A-B)

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters Menu "Detector 1 (A-B)" The menu is only relevant for MPB-311. The assignment of the induction loops is fixed: › Induction loop A: Entry (passage from the zone not controlled (ZNC) to the zone controlled (ZC)) ›...
  • Page 57: Check The Working Frequency Of The Induction Loops

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters Operational view > Main Menu > Detector 1 (A-B) > Frequency settings Parameter Description Freq. A Displays the currently measured frequency for induction loop A Freq. B Displays the currently measured frequency for induction loop B Freq.
  • Page 58: Reconciling And Setting The Operating Frequency Of The Induction Loop

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters 6.8.2 Reconciling and setting the operating frequency of the induction loop Operating frequency requirements The operating frequency must fulfil following requirements: › When driving over the induction loop with a bicycle, a significant frequency increase must be measurable.
  • Page 59 Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters The operational view is displayed. ä Page 36, Fig. 24. 1. Press the right button « ». √ The "Main Menu" menu is displayed. 2. Select the menu "Freq. shift". Path: Main menu > Detector 1 (A-B) >...
  • Page 60: Factory Settings" Menu

    Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters "Factory settings" menu IMPORTANT! The parameters of the control unit are stored in the three memory areas "Default settings", "Factory settings" and "User settings". The default settings are identical to the factory settings in these operating instructions.
  • Page 61 Control unit MGC MPT-333, MPT-353 and MPB-311 Description of menus and parameters 6. Press the right button « ». √ The safety prompt "Save changes?" appears. › If the changes are to be saved, press the right button « ». The current settings are reset to factory settings.
  • Page 62: Definitions And Versions

    Control unit MGC MPT-333, MPT-353 and MPB-311 Definitions and versions Definitions and versions Definitions and versions MPT-333 Left and right › Left: The passage is to the left of the centre pillar. › Right: The passage is to the right of the centre pillar.
  • Page 63 Control unit MGC MPT-333, MPT-353 and MPB-311 Definitions and versions Version "Entrance side left" Entry Exit Fig. 31: Version "Entrance side left", Fig. 32: Version "Entrance side left", here MPT-x3x 3x120° – view here MPT-x3x 3x120° – view from the zone not controlled...
  • Page 64: Definitions And Versions Mpt-353

    Control unit MGC MPT-333, MPT-353 and MPB-311 Definitions and versions Definitions and versions MPT-353 Left and Right › Left: The passage is to the left of the centre pillar. › Right: The passage is to the right of the centre pillar.
  • Page 65 Control unit MGC MPT-333, MPT-353 and MPB-311 Definitions and versions Fig. 34: View from zone controlled (ZC), here MPT-x5x 3x120° If both control units are supplied with the configuration "Entrance side right", as seen from the zone controlled, the right turnstile is an exit and the left turnstile...
  • Page 66: Definitions And Versions Mpb-311

    Control unit MGC MPT-333, MPT-353 and MPB-311 Definitions and versions Definitions and versions MPB-311 Left and right › Left: The person passage is to the left of the centre pillar. › Right: The person passage is to the right of the centre pillar.
  • Page 67 Control unit MGC MPT-333, MPT-353 and MPB-311 Definitions and versions Version "Entrance side right" (MPB-311B) Entry Fig. 35: Version "Entrance side right" - view from the zone not controlled (ZNC), the entrance is to the right of the centre pillar Exit Fig.
  • Page 68 Control unit MGC MPT-333, MPT-353 and MPB-311 Definitions and versions Version "Entrance side left" (MPB-311B) Entry Fig. 37: Version "Entrance side left" - view from the zone not controlled (ZNC), the entrance is to the left of the centre pillar Exit Fig.
  • Page 69: Function Description Mpt-3X3

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPT-3x3 Function description MPT-3x3 Function MPT-3x3 The MPT turnstile is used to control pedestrians in outdoor areas with relatively high safety requirements. The turnstile can be operated either in one direction or in both directions.
  • Page 70: Function Sequence Mpt-3X3

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPT-3x3 Function sequence MPT-3x3 Start The control unit receives a validation. Passage is possible. The hold-open time starts to expire. Has the centre pillar been turned? Has the hold-open time expired?
  • Page 71: Start-Up And Regular Movement Sequence Mpt-3X3

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPT-3x3 Start-up and regular movement sequence MPT-3x3 8.3.1 De-energised state The turnstile is available in the following configurations: › Locking rotating freely when de-energised › Locking locked when de-energised If no details were given in the order, the configuration "Locking rotating freely when de-energised"...
  • Page 72: Operating Modes Mpt-3X3

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPT-3x3 Operating modes MPT-3x3 8.4.1 Pulse operation in both directions The two inputs "Open entry" and "Open exit" are used to clear passage in the corresponding direction for one passage each. The pulse must be present between 0.2 and 1 sec.
  • Page 73: Permanent Open In Both Directions

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPT-3x3 8.4.3 Permanent open in both directions Prerequisite: For the parameter "Permanent open" either the option "After 3 s" or "After 10 s" has been selected. "Permanent open" parameter: ä Page 43 If a permanent signal is present at the two "Open entry"...
  • Page 74: Function Description Mpb-311

    Function description MPB-311 Function MPB-311 The MAGNETIC pedestrian gate MPB is made of a turnstile and a bicycle access. The pedestrian gate controls access of persons from a zone not controlled to a zone controlled. The separate bicycle access makes it possible to take along a bicycle into the zone controlled.
  • Page 75 Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPB-311 The turnstile is controlled by the MGC control unit. The bicycle door of the bicycle access is controlled via the MBC-110 control unit. The communication between the two control units is realised via the connection unit RIO44. The MGC control unit is used for the customer's control.
  • Page 76: Function Sequence Mpb-311

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPB-311 Function sequence MPB-311 Start The control unit receives a validation. Passage is possible. Is the The hold-open time opening loop starts to expire. occupied? Has the centre pillar The bicycle door is opened.
  • Page 77: Start-Up And Regular Movement Sequence Mpb-311

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPB-311 Start-up and regular movement sequence MPB-311 9.3.1 De-energised state Turnstile The turnstile is available in the following configurations: › Locking rotating freely when de-energised › Locking locked when de-energised If no details were given in the order, the configuration "Locking rotating freely when de-energised"...
  • Page 78: Start-Up Routine (Reference Run)

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPB-311 9.3.3 Start-up routine (reference run) After the start, the turnstile is immediately ready for operation. Bicycle door After switching on, the bicycle door automatically performs a reference run (homing). During the reference run, the bicycle door is turned by approx. 90° in both directions and the respective end stop is searched for in that direction.
  • Page 79: Pulse Operation In One Direction, Permanent Open In The Other Direction

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPB-311 9.4.2 Pulse operation in one direction, permanent open in the other direction Prerequisite: For the parameter "Permanent open" either the option "After 3 s" or "After 10 s" has been selected. "Permanent open"...
  • Page 80: Induction Loops / Buttons

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPB-311 9.5.1 Induction loops / buttons Induction loops are used to detect the bicycle. These are laid in the area of the bicycle door and connected to the loop detector module DM02.
  • Page 81: Laser Scanners

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPB-311 After opening the bicycle door, the safety loop must be occupied within approx. 3 seconds. If the safety loop is not occupied, the bicycle door is closed again. If there is no passage during the hold open time at the turnstile and there are no further validations for the current passage direction, the bicycle door is closed.
  • Page 82: Buttons

    Control unit MGC MPT-333, MPT-353 and MPB-311 Function description MPB-311 9.5.3 Buttons If you select for parameter "Sensor bicycle door" the option "Button", connect the button to the inputs with the functions "Sensor / button entry" and "Sensor / button exit".
  • Page 83: Corrective Action

    Control unit MGC MPT-333, MPT-353 and MPB-311 Corrective action Corrective action 10.1 Safety in troubleshooting Qualification of personnel › Technician › Qualified electrician ä Page 9, chapter 1.4.1. Personal protective equipment Wear the following personal protective equipment: › Work clothes ›...
  • Page 84: Malfunctions Pedestrian Gate

    Control unit MGC MPT-333, MPT-353 and MPB-311 Corrective action 10.2 Malfunctions pedestrian gate Malfunction: Display is difficult or impossible to read. Possible cause Corrective action Removal by Display contact set too light or Correct display contact. Technician dark. ä Page 38, chapter 5.6.
  • Page 85: Displaying And Signalling Messages

    Control unit MGC MPT-333, MPT-353 and MPB-311 Corrective action Error messages "ERROR" Faults that cannot be reset by the control unit are displayed as errors. The pedestrian gate is put out of service. IMPORTANT! With some messages, the control unit tries to reset the cause of the message.
  • Page 86: Procedure In Case Of A Fault / Message

    Control unit MGC MPT-333, MPT-353 and MPB-311 Corrective action 10.5 Procedure in case of a fault / message IMPORTANT! Faults of the types WARNING and ERROR may only be corrected by a trained technician or a trained qualified electrician. Required qualification: ä Page 9, chapter 1.4.1.
  • Page 87: Event, Warning And Error Messages (Troubleshooting)

    Control unit MGC MPT-333, MPT-353 and MPB-311 Corrective action 10.6 Event, warning and error messages (troubleshooting) 10.6.1 Event, warning and error messages – Logic control (control unit) Number Designation Possible cause Corrective action 3120 Mains power failure Short-term power failure Check supply voltage and detected.
  • Page 88: Event, Warning And Error Messages - Detector

    Control unit MGC MPT-333, MPT-353 and MPB-311 Corrective action Number Designation Possible cause Corrective action › FF25 Bicycle door: Fault/Error Bicycle door is not Check whether there functioning perfectly. is an error on the MBC WARNING or MMC for the bicycle (MPB-311 only) door.
  • Page 89: Event, Warning And Error Messages - All Modules

    Control unit MGC MPT-333, MPT-353 and MPB-311 Corrective action 10.6.3 Event, warning and error messages – All modules Number Designation Possible cause Corrective action 6010 Watchdog reset SW error If required, contact Service. WARNING 8110 Bus fault Warning If required, contact Service.
  • Page 90: Bicycle Door Troubleshooting - Mbc-110 And Mmc-120 (Mpb-311 Only)

    Control unit MGC MPT-333, MPT-353 and MPB-311 Bicycle door troubleshooting – MBC-110 and MMC-120 (MPB-311 only) Bicycle door troubleshooting – MBC-110 and MMC-120 (MPB-311 only) 11.1 Bicycle door faults Fault: The bicycle door moves too slowly. Possible cause Corrective action Removal by Motor is overheated.
  • Page 91: Faults On Control Unit Mbc-110

    Control unit MGC MPT-333, MPT-353 and MPB-311 Bicycle door troubleshooting – MBC-110 and MMC-120 (MPB-311 only) Fault: Display such as, e.g., gate end display does not work. Possible cause Corrective action Removal by Incorrect connection of the Check wiring and connection of Qualified electrician or technician Barrier End Display.
  • Page 92: Mbc-110 - Example Of Error Code Display

    Control unit MGC MPT-333, MPT-353 and MPB-311 Bicycle door troubleshooting – MBC-110 and MMC-120 (MPB-311 only) DIP switch Locking Locking rotating freely when de- locked when de-energised energised S1.7 S2.7 Table 40: DIP switch setting S1.7 and S2.7 on MBC-110 11.2.2...
  • Page 93: Mbc-110 - Possible Error Codes

    Control unit MGC MPT-333, MPT-353 and MPB-311 Bicycle door troubleshooting – MBC-110 and MMC-120 (MPB-311 only) 11.2.3 MBC-110 – possible error codes Error code Fault description Automatic reset Strike detection with runtime monitoring Emergency entrance is activated Wrong direction Wrong direction, high security...
  • Page 94: Faults On Control Unit Mmc-120

    Control unit MGC MPT-333, MPT-353 and MPB-311 Bicycle door troubleshooting – MBC-110 and MMC-120 (MPB-311 only) 11.3 Faults on control unit MMC-120 The following faults may only be repaired by qualified electricians. Description Possible cause / corrective action Green LED is No power supply Check power supply.
  • Page 95: Menu Structure

    – – – – Error, Warning, Main menu Event Inputs Settings Outputs In-/Outputs Modul info Service System Passage counter Information Detector 1 (A-B) Factory settings Fig. 42: "Information" and "Main menu" menu, operational view on example MPT-333 1) only with MPB-311...
  • Page 96 Control unit MGC MPT-333, MPT-353 and MPB-311 Menu structure Main menu Settings Hold-open time Close delay In-/Outputs Permanent open Service Interlock System Vend count Input Output Passage counter Max pulse count Max pulse w/o passage Information Signalling Buzzer/Siren Detector 1 (A-B)
  • Page 97 Control unit MGC MPT-333, MPT-353 and MPB-311 Menu structure Main menu Settings In-/Outputs Inputs Digital inputs 1 – 8 Outputs Digital outputs 1 – 4 Relay outputs 1 – 6 Service Gate HW Invert Magnet RL1 Invert Magnet RL2 Exit direction...
  • Page 98 Control unit MGC MPT-333, MPT-353 and MPB-311 Menu structure Main menu Settings In-/Outputs Service System Passage counter Information Detector 1 (A-B) Recalibration Mode A Factory settings Mode B Sensitivity A Sensitivity B Frequency settings Freq. A Freq. B Special function Freq.
  • Page 99: Index

    Control unit MGC MPT-333, MPT-353 and MPB-311 Index Index Entry Definition .......... 62, 66 Menu Vend count ........44 Symbole Error ............15 | Emergency open ........11 Error messages ........41, 85 | Error ............15 Ethernet module EM01 ....... 22 | Over-climb detection ........
  • Page 100 Control unit MGC MPT-333, MPT-353 and MPB-311 Index Inhibit opening ..........11 Normally open..See Rotating freely when Inhibit sensor entry ........12 de-energised Inhibit sensor exit ........12 Notice Inputs ............ 10, 41 Illustration ..........8 Factory setting ........10 Interlock ............
  • Page 101 Control unit MGC MPT-333, MPT-353 and MPB-311 Index Random check function ....... 46 Random hit ..........16 X20-EN ............55 Ref val. A ............57 Ref val. B ............57 Relay outputs......... 10, 14 ZC (zone controlled) ..... 62, 63, 65, 67, 68 Reset ............
  • Page 102 Control unit MGC MPT-333, MPT-353 and MPB-311...
  • Page 103 Control unit MGC MPT-333, MPT-353 and MPB-311...
  • Page 104 MAGNETIC AUTOCONTROL GMBH Sales partner Grienmatt 20 D-79650 Schopfheim Germany Phone +49 7622 695 5 Fax +49 7622 695 802 info@magnetic-germany.com www.magnetic-access.com F10044755...

This manual is also suitable for:

Mpt-353Mpb-311

Table of Contents