ADB Safegate VIS User Manual

Constant current regulator
Table of Contents

Advertisement

Quick Links

Constant Current Regulator Type VIS
User Manual
UM-6007, Rev. 2.2, 2024/07/17

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VIS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ADB Safegate VIS

  • Page 1 Constant Current Regulator Type VIS User Manual UM-6007, Rev. 2.2, 2024/07/17...
  • Page 3 Material Handling Precautions and Storage precautions that must be followed. ADB SAFEGATE reserves the right to examine goods upon which a claim is made. Said goods must be presented in the same condition as when the defect therein was discovered. ADB SAFEGATE furthers reserves the right to require the return of such goods to establish any claim.
  • Page 4 Use this equipment only as described in the manual. ADB SAFEGATE cannot be held responsible for injuries or damages resulting from non-standard, unintended uses of its equipment. The equipment is designed and intended only for the purpose described in the manual. Uses not described in the manual are considered unintended uses and may result in serious personal injury, death or property damage.
  • Page 5: Table Of Contents

    3.2.5 CCR Errors ........................................34 3.2.6 Mains Voltage Errors ....................................35 3.2.7 Output ..........................................35 3.3 Output/Mains screen ......................................36 3.3.1 Output currents ......................................36 3.3.2 Off if overload ......................................37 UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 6 Constant Current Regulator Type VIS TABLE OF CONTENTS 3.3.3 Overcurrent ........................................37 3.3.4 Step Parameters ......................................37 3.3.5 Mains ..........................................37 3.4 Test screen ..........................................38 3.4.1 Brightness ........................................38 3.4.2 Ctrl Hardware Iprim ....................................38 3.4.3 Test JBUS ........................................38 3.5 Configuration screen ......................................
  • Page 7 8.4.1 Install the software to upload the firmware ..........................106 8.4.2 Change the SD Flash file paths ................................107 8.4.3 Check equipment parameters ................................107 8.4.4 Update the firmware ....................................108 UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 8 Constant Current Regulator Type VIS TABLE OF CONTENTS 8.4.5 Start the equipment after a firmware update ..........................108 9.0 PCB drawings and settings ............................... 111 9.1 CPU PCB (EPS479) ........................................ 111 9.1.1 LEDs ..........................................111 9.2 Power supply PCB (EPS480) ..................................... 112 9.2.1 LEDs ..........................................
  • Page 9 Figure 34: Printed Circuit Board (PCB) ..................................121 Figure 35: Printed Circuit Board (PCB) ..................................121 Figure 36: The small cabinet (A) and the big cabinet (B) ............................127 UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 10 Constant Current Regulator Type VIS List of Figures Copyright © ADB Safegate, All Rights Reserved...
  • Page 11 Table 30: Output specifications ....................................... 125 Table 31: Dimensions .......................................... 127 Table 32: Mass ............................................127 Table 33: Protection devices specifications ................................128 Table 34: Current values produced at each brightness step ..........................128 UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 12 Constant Current Regulator Type VIS List of Tables Table 35: Ambient conditions ......................................129 Table 36: Preventive spare parts - Main fuse ................................130 Table 37: Preventive spare parts - Main contactor ..............................130 Table 38: Preventive spare parts - Lightning arrestors ............................130 Table 39: Preventive spare parts - Overvoltage protection ..........................
  • Page 13 A.0 Safety Introduction to Safety This section contains general safety instructions for installing and using ADB SAFEGATE equipment. Some safety instructions may not apply to the equipment in this manual. Task- and equipment-specific warnings are included in other sections of this manual where appropriate.
  • Page 14 Constant Current Regulator Type VIS Copyright © ADB Safegate, All Rights Reserved...
  • Page 15 Material Handling Precautions and Storage precautions that must be followed. ADB SAFEGATE reserves the right to examine goods upon which a claim is made. Said goods must be presented in the same condition as when the defect therein was discovered. ADB SAFEGATE furthers reserves the right to require the return of such goods to establish any claim.
  • Page 16 Use this equipment only as described in the manual. ADB SAFEGATE cannot be held responsible for injuries or damages resulting from non-standard, unintended uses of its equipment. The equipment is designed and intended only for the purpose described in the manual. Uses not described in the manual are considered unintended uses and may result in serious personal injury, death or property damage.
  • Page 17 It is the responsibility of the company operating this equipment to ensure that its personnel meet these requirements. Always use required personal protective equipment (PPE) and follow safe electrical work practice. UM-6007, Rev. 2.2, 2024/07/17 xvii Copyright ADB Safegate, All Rights Reserved ©...
  • Page 18 Constant Current Regulator Type VIS A.0 Introduction to Safety CAUTION Unsafe Equipment Use This equipment may contain electrostatic devices, hazardous voltages and sharp edges on components • Read installation instructions in their entirety before starting installation. • Become familiar with the general safety instructions in this section of the manual before installing, operating, maintaining or repairing this equipment.
  • Page 19 Note To minimize the risk of errors, the ADB SAFEGATE Sales Representative will have information on which gasket goes with which base. This information is also provided in the product Data sheets, the User Manuals and the Spare Part Lists.
  • Page 20 Constant Current Regulator Type VIS A.0 Operation Safety CAUTION Improper Operation Do Not Operate this equipment other than as specified by the manufacturer • Only qualified personnel, physically capable of operating the equipment and with no impairments in their judgment or reaction times, should operate this equipment.
  • Page 21 Note To minimize the risk of errors, the ADB SAFEGATE Sales Representative will have information on which gasket goes with which base. This information is also provided in the product Data sheets, the User Manuals and the Spare Part Lists.
  • Page 22 Constant Current Regulator Type VIS xxii Copyright © ADB Safegate, All Rights Reserved...
  • Page 23: Description

    Any other or additional use will not considered to be in conformity with the purpose. Do not operate the equipment outside the limits of the specifications or outside the specified ambient conditions. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 24: Working Principle

    Constant Current Regulator Type VIS Description 1.2 Working Principle Line input. See Line input Precharge PCB. See Line input Diode bridge and sensing PCB.See IGBT power bridge Capacitor bank. See Capacitor bank IGBT module and IGBT PCB. See IGBT power bridge Output filter.
  • Page 25 Main feedback loop The output measure PCB sends the measured output to the CPU PCB. Depending on the output, the CPU PCB automatically generates a signal to adjust the regulation. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 26: Layout Of The Equipment Cabinet

    Constant Current Regulator Type VIS Description 1.3 Layout of the Equipment Cabinet 1.3.1 Outside - small cabinet: 2.5 to 15 kVA Ventilation grids Serial communication port Manual switch Remote control connector Series output connection. The illustration shows the SCO Output to Series Circuit...
  • Page 27: Inside - Small Cabinet: 2.5 To 15 Kva

    Power supply PCB (EPS480) Output filter Remote control PCB (EPS495) Lightning arrestors Output measure PCB (EPS422) Input terminals Line filter Main transformer Capacitator bank Power supply transformer Sensing transformer UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 28: Outside - Big Cabinet 20 To 30 Kva

    Constant Current Regulator Type VIS Description 1.3.3 Outside - big cabinet 20 to 30 kVA Ventilation grids Serial communication port Manual switch Remote control connector Series output connection. The illustration shows the SCO Output to Series Circuit Ethernet connector Power supply cable entry Copyright ©...
  • Page 29: Inside - Big Cabinet 20 To 30 Kva

    For the exact location and connectors see Layout of the Equipment Cabinet and the electrical scheme. You can find the electrical scheme attached on the outside of the equipment. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 30: Line Input

    Constant Current Regulator Type VIS Description 1.4.1 Line input Figure 4: Input terminal, all cabinets The input terminal connects the power input cables to the equipment. Figure 5: Line filter, all cabinets The line filter blocks the noise the equipment generates to the line input and filters out voltage pulses from the input voltage.
  • Page 31: Figure 7: Main Fuses, Small Cabinet

    The main fuses disconnect the equipment from the mains power supply if the input current is above a given value. Figure 9: Main contactor, small cabinet The main contactor allows the power supply PCB to automatically interrupt the power. Figure 10: Main contactor, big cabinet UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 32: Figure 11: Precharge Contactor, Small Cabinet

    Constant Current Regulator Type VIS Description The main contactor allows the power supply PCB to automatically interrupt the power. Figure 11: Precharge contactor, small cabinet The precharge contactor allows a smooth charge of the capacitors on the capacitor bank. Figure 12: Precharge contactor, big cabinet The precharge contactor allows a smooth charge of the capacitors on the capacitor bank.
  • Page 33: Figure 15: Power Supply Transformer, All Cabinets

    The sensing transformer measures the difference in the input voltage level between phases L1 and L2. Figure 15: Power supply transformer, all cabinets UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 34: Igbt Power Bridge

    Constant Current Regulator Type VIS Description The power supply transformer: • Measures the input voltage level between phases L2 and L3. • Provides the correct current and voltage to power all the electronic components such as PCBs and to power the fans (for 15 to 30kVA equipment).
  • Page 35: Figure 18: Diode Bridge, Big Cabinet

    The system uses four IGBTs connected as an H-bridge to make an AC-signal. Figure 20: IGBT PCB (EPS477 /EPS496 /EPS 478), all cabinets The IGBT PCB measures the output signal from the IGBT H-bridge. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 36: Capacitor Bank

    Constant Current Regulator Type VIS Description 1.4.3 Capacitor bank The capacitor bank smoothens the DC current and voltage to make a constant DC current and voltage. Figure 21: Capacitor bank, small cabinet Figure 22: Capacitor bank, big cabinet 1.4.4 Hall sensor, big cabinet Figure 23: Hall sensor, big cabinet The Hall sensor measures the current between the IGBT and the output filter.
  • Page 37: Output Filter

    The output filter is a Pulse Width Modulation (PWM) filter that builds the pure sine wave signal that comes from the H-bridge. 1.4.6 Main transformer, all cabinets The main transformer converts the pure sine wave to the correct output voltage and current. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 38: Output Measure Pcb (Eps422), All Cabinets

    Constant Current Regulator Type VIS Description 1.4.7 Output measure PCB (EPS422), all cabinets The output measure PCB measures the output voltage and current and sends these measurements to the CPU PCB. The EFD (See Earth Fault Detection (EFD) ) and LFD (See...
  • Page 39: Remote Control Pcb (Eps495 Or Ep00047), All Cabinets

    1.4.10 Remote control PCB (EPS495 or EP00047), all cabinets Note Until 2022, the VIS was delivered with the EPS495 board as the remote control PCB. Since 2022, the VIS has been delivered with the EP00047, and the EP00051 as an add-on board when Multiwire is required. The functionalities of these boards are equivalent in most cases, with the exception of the most demanding recent ALCMS systems with a redundant bus.
  • Page 40: Power Supply Pcb (Eps480), All Cabinets

    Constant Current Regulator Type VIS Description 1.4.11 Power supply PCB (EPS480), all cabinets The power supply PCB provides the power supply for: • All electronic components such as PCBs of the equipment • The fans (for 15 to 30 kVA equipments) •...
  • Page 41: Options

    1.5.1 Remote control Note Until 2022, the VIS was delivered with the EPS495 board as the remote control PCB. Since 2022, the VIS has been delivered with the EP00047, and the EP00051 as an add-on board when Multiwire is required. The functionalities of these boards are equivalent in most cases, with the exception of the most demanding recent ALCMS systems with a redundant bus.
  • Page 42: Series Connector Box (Scb), All Cabinets

    Constant Current Regulator Type VIS Description 1.5.3 Series Connector Box (SCB), all cabinets The SCB connects the equipment to the series circuit with two medium voltage cables of the primary circuit. The SCB does not allow the short circuit connection.
  • Page 43: Nameplate

    1.7 Nameplate Each equipment has a standard nameplate: UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 44 Constant Current Regulator Type VIS Description Copyright © ADB Safegate, All Rights Reserved...
  • Page 45: Description Of The Hmi

    Field circuit Shows the name of the field circuit that the equipment delivers power to True RMS output voltage Shows the true RMS output voltage in kV UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 46: Description Of General Functions

    Constant Current Regulator Type VIS Description of the HMI Table 1: Display description: Main screen (Continued) Name Description True RMS output current Shows the true RMS output current in A Highest brightness step Shows the time that the equipment operates at the maximum brightness step in h...
  • Page 47: Main Menu

    Table 5: Buttons Button Description RESET To reset the alarm: See also Alarms FORWARD To show the previous alarm in the list: See also Alarm texts and messages on the HMI UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 48: Maintenance Menu

    Constant Current Regulator Type VIS Description of the HMI For an overview of alarm texts and messages, see Alarm texts and messages on the HMI 2.6 Maintenance menu A password is required to access the maintenance menu. Table 6: General function buttons...
  • Page 49: Alarm Texts And Messages On The Hmi

    The resistance to earth is less than level 1 (20 MOhm default value) EFD LEVEL 2 FAULT The resistance to earth is less than level 2 (2 MOhm default value) UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 50 Constant Current Regulator Type VIS Description of the HMI Alarm text / message Possible cause GATE H FAULT There is a problem with the H-bridge (IGBT). On the HMI, a message shows “IGBT KO: xxx x” IGBT KO: ... Both IGBTs are broken...
  • Page 51 There is a problem with the mains frequency detection x PIC COMMUNICATION ERROR A faulty communication with the measurement PCB PRE-CHARGE CONTACTOR ON The pre-charge contactor is broken (VIS only) PRE-CHARGE CONTACTOR OFF The pre-charge contactor is broken (VIS only) SCO / DOOR OPENED...
  • Page 52 Constant Current Regulator Type VIS Description of the HMI Copyright © ADB Safegate, All Rights Reserved...
  • Page 53: Description Of The Configuration Software Tool

    When you activate the configuration tool, you transfer all control of the equipment to the configuration software tool. In this situation, remote or local control of the equipment is not possible. To update the software version, contact ADB Safegate. 3.1 Description of screens and menus...
  • Page 54: Ccr Status Screen

    Constant Current Regulator Type VIS Description of the configuration software tool You can adjust the values in the yellow areas (A). You cannot adjust values in the orange areas (B). White selection boxes: if the box is marked, the item applies (C).
  • Page 55: Ccr Status

    The LFD reference calibration is not done or is not successful Error in LFD Removed Lamps Calibration The LFD removed lamps calibration is not done or is not successful UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 56: Regulation Errors

    Constant Current Regulator Type VIS Description of the configuration software tool 3.2.4 Regulation Errors Possible cause Alarm type CCR switched OFF for OVERCURRENT • • The output current is more than Imax +5% The equipment automatically switches for minimum 4s •...
  • Page 57: Mains Voltage Errors

    The red light on the equipment goes on 3.2.7 Output Item Description I_out Shows the output current V_out Shows the output voltage P_out Shows the output power V_in Shows the input voltage Shows the PWM UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 58: Output/Mains Screen

    Constant Current Regulator Type VIS Description of the configuration software tool 3.3 Output/Mains screen Description Output screen part See items B to F Output currents Off if overload Imax Shows the maximum output current Overcurrent Overcurrent Off if overload Off if overload...
  • Page 59: Off If Overload

    Frequency_In Shows the supply voltage frequency Change To activate the values and to send them to the equipment Read To read the actual Mains parameters from the selected equipment UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 60: Test Screen

    Constant Current Regulator Type VIS Description of the configuration software tool 3.4 Test screen Description Read To read the actual Analogue Data parameters (AD0 to AD7) from the selected equipment Brightness Brightness Ctrl Hardware Iprim Ctrl Hardware Iprim Switch on JBUS...
  • Page 61: Configuration Screen

    To read the actual configuration parameters from the selected data line Open Circuit Do not use these parameters. There is a risk of damage to the equipment. Only ADB Safegate service engineers are allowed to use these parameters Regulation Rate...
  • Page 62: Sn/Yearcode

    Constant Current Regulator Type VIS Description of the configuration software tool 3.5.3 SN/YearCode Item Description YearCode/SN To change the production year and the serial number Change To activate the value and to send it to the equipment 3.5.4 Maintenance Password...
  • Page 63: Efd Enable

    To adjust the minimum time span after the error before the equipment gives the VA Drop 1 or Drop 2 alarm Change To activate the value and to send it to the equipment UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 64: Diag/Dsp/Bus Screen

    Constant Current Regulator Type VIS Description of the configuration software tool 3.7 Diag/Dsp/BUS screen Description Slave errors Slave Errors Rem Reset Rem Reset Dsp parameters Dsp Parameters Imp Test Imp Test Hours_Meter Hours_Meter Bus Parameters • Arbiter: To set the signal source for remote control. To set a priority for different systems. If you set this parameter to disabled, remote control is not possible.
  • Page 65: Rem Reset

    To carry out a test on the LEDs of the keyboard on the HMI. The LED adjacent to the DB9 connector comes on Change To activate the value and to send it to the equipment UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 66: Hours_Meter

    Constant Current Regulator Type VIS Description of the configuration software tool 3.7.5 Hours_Meter Item Description Total Shows the total time that the equipment is set to ‘on’ in h Max Br. Shows the time that the equipment operates at the maximum brightness step in h...
  • Page 67: Log Screen

    3.10 Test JBus screen Description Start Test To start the test Stop To stop the test No. of slaves Shows the number of slaves Reg. start No. of reg UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 68 Constant Current Regulator Type VIS Description of the configuration software tool Copyright © ADB Safegate, All Rights Reserved...
  • Page 69: Install And Operate The Configuration Software Tool

    2. Push the OPTIONS button to go to the Options menu. 3. Push the SLVNUM button to show the slave number. 4. Note the slave number. You will need it for reference later. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 70 Constant Current Regulator Type VIS Install and operate the configuration software tool Connect the serial cable, if applicable 1. Switch OFF the equipment. See Switch OFF the equipment. 2. Connect the extension cable to the dongle (A) and to the serial communication port of the PC (B).
  • Page 71 If the settings are correct, the yellow OK button is enabled and the bottom bar shows the message 'Port opened'. • If the settings are not correct, the bottom bar shows an error message. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 72: Monitor The Data Of An Equipment

    Constant Current Regulator Type VIS Install and operate the configuration software tool 4.3 Monitor the data of an equipment Select the equipment 1. Select the slave number of the equipment you want to monitor. 2. Push the OK button. Start monitoring 1.
  • Page 73: Commissioning

    3. Set the manual switch to the ON position. 4. On the HMI, push the Local button. The screen now shows the state LOCAL. 5. Push the OFF button. The equipment goes to the mode OFF. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 74: Measure Output Current In Short-Circuit

    Constant Current Regulator Type VIS Commissioning Measure 1. Measure the input voltage on the input terminals (A). Use a True RMS Multimeter. 2. Examine if the voltage is in accordance with: • The nameplate of the equipment. • Local regulations.
  • Page 75: Put Sco In Short Circuit

    2. With the separate piece of output cable (B), short-circuit the output terminals (A). 3. Install the box panel. 5.1.5 Put SCO in short circuit Set the SCO to mode C. See Operation mode UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 76: Measure The Output Current In Short Circuit

    Constant Current Regulator Type VIS Commissioning 5.1.6 Measure the output current in short circuit Connect AC True RMS multimeter (SCB) • Connect the current clamp of an AC True RMS multimeter (B) to the short-circuited cable (A). Connect AC True RMS multimeter (SCO) •...
  • Page 77: Prepare With Scb

    1. Open the lock (A). 2. Remove the cover (B). Use the handle. Remove series circuit cables • Completely remove the series circuit cables, also the shielding, if applicable. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 78: Measure Resistance Of Series Circuit

    Constant Current Regulator Type VIS Commissioning 5.1.10 Measure resistance of series circuit Measure the resistance: measure on the ends of the series cable (A). Use a multimeter (B), in accordance with local regulations. 5.1.11 Measure insulation resistance of series circuit 1.
  • Page 79: Complete The Measurement

    4. Compare the output current reading on the HMI with the reading on the True RMS Multimeter. 5. Examine if the output current readings are in accordance with local regulations. If not, do not continue. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 80: Calibrate Lamp Fault Detection (Lfd)

    Constant Current Regulator Type VIS Commissioning Check brilliancy level 1. Examine if all light fittings have the same brilliancy level. Go to the runway area to make a visual inspection. 2. Examine all the brightness steps separately. Go through the whole procedure for each brightness step.
  • Page 81: Remote Control Configuration: Multiwire (Option)

    4. Push the → or ← buttons until the HMI shows the remote control mode. 5. Make sure that the remote control mode is ‘MULTIWIRE’. 6. If necessary, adjust the remote control mode. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 82: Remote Control Configuration: J-Bus (Option)

    Constant Current Regulator Type VIS Commissioning Examine or adjust the input and output signals function assigned to terminals 1. Push the → or ← buttons until the HMI shows the multiwire configuration. 2. Check and adjust the signals if necessary. See Maintenance menu.
  • Page 83: Operation

    2. If the UI shows that the equipment is in the state OFF, push the ON button. The HMI shows the state ON. 3. To switch between Local and Remote mode, see Switch between local and remote mode. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 84: Switch Off The Equipment

    Constant Current Regulator Type VIS Operation 6.2 Switch OFF the equipment 1. On the HMI, push the Local button. The screen now shows the state LOCAL. 2. Push the OFF button. The equipment goes to the mode OFF. 3. Switch OFF the power supply. See Switch OFF the power supply.
  • Page 85: Select Brightness Step

    The HMI only shows information about errors that the equipment can detect. The equipment does not detect all possible errors. You have to observe if the equipment operates correctly. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 86: Use Series Cutout (Sco)

    Constant Current Regulator Type VIS Operation Local mode An alarm occurs, the equipment switches OFF automatically. • If you need to switch off the power supply to remove the cause of the alarm: The equipment starts to produce the same output current that was valid before the equipment was switched OFF.
  • Page 87: Adjust Operation Mode

    When the cover is closed, the micro switch is activated. When the cover is open, the microcircuit is deactivated and the equipment shuts down. 6.8.2 Adjust operation mode Remove the cover 1. Open the lock (A). 2. Remove the cover (B). Use the handle. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 88: Operation Mode

    Constant Current Regulator Type VIS Operation Set operation mode 1. Install the cover (B). See the cover placement in Operation mode. 2. Close the lock (A). 6.9 Operation mode A series circuit with non-linear loads can be unstable. If the system is unstable, follow the procedure below.
  • Page 89: Troubleshooting

    ‘open’ position • wires are not interrupted or damaged. 7.2 Troubleshooting guide Note For a list of errors, see CCR status screen. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 90: Fault: Equipment Does Not Turn On

    Constant Current Regulator Type VIS Troubleshooting 7.2.1 Fault: Equipment does not turn ON Table 9: Equipment does not turn ON Problem Possible cause Possible solution No display indications A problem with the power supply on the • Examine the transformer on the diode bridge diode bridge PCB •...
  • Page 91: Fault: Equipment Does Not Go To The On State

    Replace the diode bridge PCB if necessary Diode bridge and sensing PCB (EPS540 / EPS 541) replacement, small cabinet Diode bridge and sensing PCB (EPS 497) replacement, big cabinet UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 92: Fault: Equipment Turns On But Suddenly De-Energizes

    Constant Current Regulator Type VIS Troubleshooting 7.2.3 Fault: Equipment turns ON but suddenly de-energizes Table 11: Equipment turns ON but suddenly de-energizes Problem Possible cause Solution (See) After you press the ON button, The input AC line delivers less than 360...
  • Page 93: Checks And Measurements

    400 V DC to 147 V DC. If the cable capacitance is 1 pF, the measured voltage decreases from 400 V DC to 147 V DC (=0.37x400) in approximately 10 seconds. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 94 Constant Current Regulator Type VIS Troubleshooting If the voltage you measure with the LFD module connected is already 330 V DC, the cable leakage resistance is approximately 10 MOhm. In this case, the discharge time is approximately 5 seconds for a cable capacitance of 1 pF.
  • Page 95: Maintenance

    Make sure you switch OFF the power to the equipment. See Switch OFF the power supply. • Make sure you switch OFF the manual switch to remove all power to the equipment. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 96: Required Tools

    Constant Current Regulator Type VIS Maintenance CAUTION While you carry out maintenance: • Do not drop screws or nuts inside the equipment cabinet. Collect loose nuts and screws immediately. • To identify all cables you disconnect, label the cables. •...
  • Page 97: Cpu Pcb (Eps479) Replacement

    Remove panel • Remove the front panel. See Remove panels. Disconnect 1. Disconnect the connectors and the wires (A). 2. Remove the fasteners (B). 3. Remove the CPU PCB (C). UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 98: Diode Bridge And Sensing Pcb (Eps540 / Eps 541) Replacement, Small Cabinet

    Constant Current Regulator Type VIS Maintenance Install 1. Install the new CPU PCB. 2. Install the fasteners. 3. Connect all the wires. CAUTION Connect the keyboard cable with the green side down. Update the firmware 1. Update the firmware. See Firmware update.
  • Page 99 6. Tighten the fasteners (B). Apply a torque of 2 Nm. 7. Install the precharge PCB. See Precharge PCB (EPS546) replacement, small cabinet. 8. Install the front panel. See Remove panels. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 100: Diode Bridge And Sensing Pcb (Eps 497) Replacement, Big Cabinet

    Constant Current Regulator Type VIS Maintenance 8.2.4 Diode bridge and sensing PCB (EPS 497) replacement, big cabinet For parts, see Parts list. • Diode bridge + sensing PCB Prepare 1. Remove the lower front panel. See Remove panels. 2. Remove the precharge PCB. See Precharge PCB (EPS546) replacement, small cabinet.
  • Page 101: Display And Keyboard Replacement

    2. To replace, push, turn counterclockwise and remove the fuse (A). If only one fuse is broken, replace only the broken fuse. 3. Install the new fuse. 4. Install the lower front panel. See Remove panels. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 102: Igbt Pcb (Eps477 / Eps 478) Replacement, Small Cabinet

    Constant Current Regulator Type VIS Maintenance 8.2.7 IGBT PCB (EPS477 / EPS 478) replacement, small cabinet For parts, see Parts list. • IGBT PCB Note The IGBT PCB, IGBT module, and the diode bridge and sensing PCB together are the IGBT power bridge. If one component breaks, replace the entire IGBT power bridge.
  • Page 103: Igbt Pcb (Eps496) Replacement, Big Cabinet

    Remove the lower front panel. See Remove panels. Remove 1. Disconnect the wires (A). 2. Remove the fasteners (B). 3. Remove the capacitors (C). 4. Remove the fasteners (D). 5. Remove the IGBT PCB. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 104: Igbt Replacement, Small Cabinet

    Constant Current Regulator Type VIS Maintenance Remove the spring from the IGBT • Make sure that spring number 7 (A) of the IGBT is removed. Once a spring has been removed, it cannot be reinstalled. Install CAUTION When you tighten the fasteners, only apply force vertically. Use an alien key screwdriver or an allen key handle instead of a socket wrench or a ratchet.
  • Page 105 3. Remove the IGBT PCB. See IGBT PCB (EPS477 / EPS 478) replacement, small cabinet. Remove 2 1. Disconnect the wire (A). 2. Remove the fasteners (B). 3. Remove the IGBT (C). UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 106: Igbt Replacement, Big Cabinet

    Constant Current Regulator Type VIS Maintenance Install 1 1. Wipe clean the heat sink below the IGBT (A). 2. Apply an even layer of conductive paste on the rear of the IGBT (the side that touches the heat sink). 3. Tighten the fasteners (B) crosswise. Apply a torque of 4 Nm.
  • Page 107: Line Filter Replacement

    5. Remove the line filter (C). 6. Install the new line filter. 7. Install the wires. 8. Install the lower rear panel. See Remove panels. 9. Install the side panels. See Remove panels. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 108: Main Contactor Replacement

    Constant Current Regulator Type VIS Maintenance 8.2.13 Main contactor replacement For parts, see Remove panels. • Main contactor WARNING Make sure that you switched OFF the power to the equipment. See Switch OFF the power supply. WARNING Make sure that you switched OFF the external disconnection device to remove all power to the equipment.
  • Page 109: Main Fuses Replacement

    Make sure you switch OFF the power to the equipment. See Switch OFF the power supply. Note Make sure you switch OFF the external disconnection device to remove al power to the equipment. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 110 Constant Current Regulator Type VIS Maintenance Remove panel • Remove the lower front panel. See Remove panels. Disconnect 1. Loosen the screws (A). 2. Disconnect the wires (B). 3. Remove the manual switch (C). Use a screwdriver as a lever to release the manual switch from the rail (D).
  • Page 111: Output Filter Replacement, Small Cabinet

    For equipments up to 7.5 kVA, the output filter is not installed on a plate, but directly on the housing. In this case, replace all individiual filter parts. Remove panel • Remove the side panels. See Remove panels. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 112 Constant Current Regulator Type VIS Maintenance Remove 1. Disconnect the wires (A). 2. Remove the fasteners (B). 3. Remove the output filter plate (C). Disconnect 1. Disconnect the fasteners (A). 2. Remove the output filter plate (C) from the back plate (B).
  • Page 113: Output Filter Replacement, Big Cabinet

    1. Install the new output filter plate. 2. Install the wires. 3. Tighten the fasteners (A). Apply a torque of 6 Nm. 4. Install the side panels. See Remove panels. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 114: Output Measure Pcb (Eps442) Replacement

    Constant Current Regulator Type VIS Maintenance 8.2.18 Output measure PCB (EPS442) replacement Parts: see Parts list. • Output measure PCB Remove panels 1. Remove the upper rear panel. See Remove panels. 2. Remove the screws (A). 3. Remove the box panel (B).
  • Page 115: Power Supply Pcb (Eps480) Replacement

    8.2.20 Precharge contactor replacement For parts, see Remove panels. • Precharge contactor WARNING Make sure you have switched OFF power to the equipment. See Switch OFF the power supply. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 116 Constant Current Regulator Type VIS Maintenance Remove panel • Remove the lower front panel. See Remove panels. Disconnect 1. Loosen the screws (A). 2. Disconnect the wires (B). 3. Remove the precharge contactor (C). Use a screwdriver as a lever to release the manual switch from the rail (D).
  • Page 117: Precharge Pcb (Eps546) Replacement, Small Cabinet

    Remove panel • Remove the lower front panel. See Generic panels. Remove 1. Disconnect the connector (A). 2. Remove the fasteners (B). 3. Carefully remove the precharge PCB (C). UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 118: Remote Control Pcb (Eps495 Or Ep00051) Replacement

    Constant Current Regulator Type VIS Maintenance 4. Remove the fasteners (D). 5. Remove the electrical wires. Install 1. Connect all the wires. 2. Tighten the fasteners (A). Apply a torque of 4 Nm. 3. Install the new precharge PCB. 4. Install the lower front panel. See Generic panels.
  • Page 119: Series Connection Box (Scb) Replacement (Option)

    1. Loosen the screws (A). 2. Disconnect the series circuit cables (B). 3. Disconnect the wires and connectors (C). 4. Loosen the screws (D). 5. Carefully remove the SCB (E). UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 120: Series Cutout (Sco) Replacement (Option)

    Constant Current Regulator Type VIS Maintenance Install 1. Install the new SCB. 2. Put the series circuit cables through the stress-relief clamps. 3. Tighten the screws of the stress-relief clamps. 4. Install all the wires and connectors. 5. Install the box panel.
  • Page 121 4. Loosen the screws (B1). 5. Disconnect the output cables (B). 6. Loosen the screw (C1) 7. Disconnect the earthing wire (C). 8. Remove the bolts (D). 9. Remove the SCO. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 122 Constant Current Regulator Type VIS Maintenance Connect the micro switch 1. Disconnect the cables to the micro switch (A). 2. Connect the cables to the micro switch (A) in the new SCO. Install 1. Install the new SCO. 2. Install the bolts (D).
  • Page 123: Remove Panels

    Do not change or lock the panel switches. A panel switch sees if a panel is installed or not. Note The panels differ in size and number of screws. The illustrations below show the principle. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 124: Remove The Display / Keyboard Panel Of The Small Cabinet

    Constant Current Regulator Type VIS Maintenance 8.3.1 Remove the display / keyboard panel of the small cabinet Disconnect HMI 1. Remove the front panel. See Generic panels. 2. Disconnect the wires (A) to the HMI from the CPU PCB (B).
  • Page 125: Remove The Display / Keyboard Panel Of The Big Cabinet

    2. Disconnect the wires (A) to the HMI from the CPU PCB (B). 3. Disconnect the earthing wire (C). Remove panel 1. Remove the screws (A). 2. Carefully remove the panel (B). UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 126: Top Panel (Small Cabinet)

    Constant Current Regulator Type VIS Maintenance CAUTION Take care not to damage cables and connectors. 8.3.3 Top panel (small cabinet) Disconnect HMI 1. Remove the front panel. See Generic panels 2. Disconnect the wires (A) to the HMI from the CPU PCB (B).
  • Page 127: Generic Panels

    1. Install the software to upload the firmware. See Install the software to upload the firmware. 2. Change the SD flash file paths, if necessary. See Change the SD Flash file paths. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 128: Install The Software To Upload The Firmware

    Constant Current Regulator Type VIS Maintenance 3. Do a check on the equipment parameters. See Check equipment parameters. 4. Update the firmware. See Update the firmware. 5. Start the equipment after a firmware update. See Start the equipment after a firmware update.
  • Page 129: Change The Sd Flash File Paths

    4. Push the Read button to show the firmware details. 5. Make sure that the equipment parameters below match those of the filename of the required firmware version: • Single Phase (CRE) or Tri-phase (VIS) • Input Voltage: 230V range or 400V range •...
  • Page 130: Update The Firmware

    Constant Current Regulator Type VIS Maintenance 8.4.4 Update the firmware Prepare the equipment 1. Remove the lower front panel. See Generic panels 2. Remove the watch-dog jumper from the CPU PCB (EPS479). See CPU PCB (EPS479). 3. Connect the firmware update dongle (A) between the PC and the equipment.
  • Page 131 2. Make sure that the manual switch is in the OFF position. See Switch OFF the power supply. 3. Disconnect the firmware update dongle. 4. Install the lower front panel. See Generic panels. 5. Switch ON the equipment. See Operation. UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 132 Constant Current Regulator Type VIS Maintenance Copyright © ADB Safegate, All Rights Reserved...
  • Page 133: Pcb Drawings And Settings

    The voltage for the power supply on the PCB is +3.3 V DC (generated on the PCB) Green The voltage for the powers supply on the PCB is +1.8 V DC (generated on the PCB) UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 134: Power Supply Pcb (Eps480)

    Constant Current Regulator Type VIS PCB drawings and settings 9.2 Power supply PCB (EPS480) Figure 29: Printed Circuit Board (PCB) 9.2.1 LEDs Table 15: Power supply PCB LED functions Color Function Green The voltage for the fans, if applicable is +24 V DC (generated on the PCB)
  • Page 135: Remote Control Pcb

    9.3 Remote Control PCB Note Until 2022, the VIS was delivered with the EPS495 board as the remote control PCB. Since 2022, the VIS has been delivered with the EP00047, and the EP00051 as an add-on board when Multiwire is required. The functionalities of these boards are equivalent in most cases, with the exception of the most demanding recent ALCMS systems with a redundant bus.
  • Page 136 Constant Current Regulator Type VIS PCB drawings and settings Table 18: Remote control PCB jumper settings (Continued) Jumper Position Function position 1-3 and position 2-4 ethernet channel 1: enable 1 3 5 2 4 6 position 3-5 and position 4-6...
  • Page 137: Ep00047 And Ep00051

    120 Ohm CAN (1-2) Boot-GND (2-3) RS485_2_TX+ (1-2) RS485_1_TX+ 120 Ohm 120 Ohm RS485_2_RX+ RS485_1_RX+ RS485_2_RX+ (4w:2-3, RS485_1_RX+ 2w:1-2) (4w:2-3) RS485_2_RX- (4w:2-3) J38 RS485_1_RX- (4w:2-3) RS485_2 (3-5, 4-6) RS485_1 (3-5, 4-6) UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 138: Multiwire/J-Bus Connection Scheme

    Constant Current Regulator Type VIS PCB drawings and settings 9.3.3 Multiwire/J-Bus connection scheme Note The table shows the standard remote control configuration for the signals. If you want another configuration, contact ADB Safegate. Table 19: Factory set terminal assignments for remote control connections with multiwire and single J-Bus (Cable Set 4072.30.XXX)
  • Page 139: Table 20: Factory Set Terminal Assignments For Remote Control Connections With Multiwire Dual J-Bus (Cable Set 4072.30.182)

    ON - CMD J1.6 CCR OFF from HVCS - CMD J1.7 J1.8 V-OUT 48V J8.1 GND 48V J8.2 Feedback signals (fixed) GND - FB J8.3 GND - FB J8.4 UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 140 Constant Current Regulator Type VIS PCB drawings and settings Table 20: Factory set terminal assignments for remote control connections with multiwire dual J-Bus (Cable Set 4072.30.182) (Continued) Function Terminal number on 32-pole Relay number on Remote Control PCB (unless connector...
  • Page 141: Igbt Pcb (Eps477 / Eps 496)

    Remote control PCB - feedback signals Relays 24 V DC power supply J-Bus RS485 connection J-Bus RS485 interface 9.4 IGBT PCB (EPS477 / EPS 496) Figure 33: Printed Circuit Board (PCB) EPS477 for2s Semix UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 142: Leds Eps477 For 2S Semix

    Constant Current Regulator Type VIS PCB drawings and settings 9.4.1 LEDs EPS477 for 2s Semix Table 21: IGBT PCB LED functions Color Function LDX1 The voltage for the high side IGBT, generated on the PCB, is +18 V DC. LDX2 The voltage for the high side IGBT, generated on the PCB, is -5 V DC.
  • Page 143: Output Measure Pcb (Eps442)

    LDX3 The voltage from the 50 kHz power supply on the PCB is +18 V DC LDX4 The nominal voltage for the IGTBT bridge bus is 560 V DC UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 144: Test Parameters

    Constant Current Regulator Type VIS PCB drawings and settings 9.7 Test parameters 9.7.1 Analog channels Table 25: Analog channels Channel Description Value range Temperature 17000 - 32000 Temperature 27000 - 32000 I bridge 100 - 2000 V bridge 0 - 30000 V in ±31000...
  • Page 145: External Output

    Description Div_I Number of divisions of output current Div_V Number of divisions of output voltage Number of divisions of EFD Phase Phase displacement between V and I (x 1000) UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 146 Constant Current Regulator Type VIS PCB drawings and settings Copyright © ADB Safegate, All Rights Reserved...
  • Page 147: Technical Data

    1.5 kV , 2.8 kJ VIS 7.5 1.13 2.2 kV , 4.2 kJ VIS 10 1.50 2.2 kV , 4.2 kJ VIS 15 2.30 3.0 kV , 5.6 kJ UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 148: Applicable Standards

    Constant Current Regulator Type VIS Technical Data Table 30: Output specifications (Continued) Type Rated output power RMS output voltage at 6.6 A Insulated test on Output overvoltage protection [kW] RMS output current [kV] output [kV] 25kApk VIS 20 3.00 4.5 kV , 8.4 kJ...
  • Page 149: Dimensions And Mass

    1200 x 800 x 1500 1200 x 800 x 1500 1200 x 800 x 1500 1200 x 800 x 1850 1200 x 800 x 1850 1200 x 800 x 1850 UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 150: Protection Devices

    Constant Current Regulator Type VIS Technical Data 10.4 Protection devices Table 33: Protection devices specifications Equipment type Equipment Main fuse rating [A] Manual switch type C rating [A] Maximum line input current [A] [kVA] voltage [V] 380 to 400 11.7 17.6...
  • Page 151: Ambient Conditions

    For IEC conformity to -40 °C an optional modification is required. 10.7 Parts list WARNING Use only original ADB Safegate spare parts. If you use other spare parts, the specific module or the equipment may be damaged. This can also put personnel in danger. Note The parts list may be subject to change without prior notice.
  • Page 152: Table 36: Preventive Spare Parts - Main Fuse

    Constant Current Regulator Type VIS Technical Data Item Table Safety switches Table 41 Table 42 IGBT bridge Table 43 Micro control PCB Table 44 Output measure PCB Table 45 Power supply PCB Table 46 Remote control PCB Table 47 Diode bridge PCB...
  • Page 153: Table 40: Preventive Spare Parts - Capacitors

    6351.88.060 ISOLAT.M6 0.6kV 6126.12.485 Semix 341D16s 6351.88.030 Table 44: Preventive spare parts - CPU PCB Description Part number Quantity per order EPS479/5 CRE/VIS CPU pcb:CS00179 1597.00.000 rev.1.1 EPS479/15 CRE/VIS 1597.00.010 CPU pcb:CS00179 rev1.1 EPS479/30 CRE/VIS 1597.00.020 CPU pcb:CS00179 rev1.1 UM-6007, Rev. 2.2, 2024/07/17...
  • Page 154: Table 45: Preventive Spare Parts - Output Measure Pcb

    Constant Current Regulator Type VIS Technical Data Table 45: Preventive spare parts - Output measure PCB Description Part number Quantity per order EPS442/2.5 CRE/VIS 1597.00.100 out.meas.board CS0039 rev.2.2 EPS442/5 CRE/VIS out.meas.board 1597.00.110 CS0039 rev.2.2 EPS442/7.5 CRE/VIS 1597.00.120 out.meas.board CS0039 rev.2.2 EPS442/10 CRE/VIS 1597.00.130...
  • Page 155: Table 48: Preventive Spare Parts - Diode Bridge And Sensing Pcbt

    30KVA PCB CS00176 rev.2.0 (sensing, without diode bridge) Table 49: Preventive spare parts - IGBT PCB Description Part number Quantity per order EPS477 CRE/VIS 2.5/ 15KVA PCB 1597.00.510 CS00177 rev.1.1 (IGBT driver) EPS478 CRE/VIS 2.5/ 15KVA PCB 1597.00.520 CS00178 rev.1.0 EPS496 CRE/VIS 20/ 30KVA PCB 1597.00.530...
  • Page 156: Corrective Spare Parts

    Constant Current Regulator Type VIS Technical Data Table 52: Preventive spare parts - Display and keyboard Description Part number Quantity per order Description Part number CCR KEYBOARD BOX 4072.30.630 ASSY. TRIPHASE 10.9 Corrective spare parts Item Table Manual switch Table 53...
  • Page 157: Table 55: Corrective Spare Parts - Line Filter

    CAP. AYUX- 6322.60.210 HR222M400DC LBK Int. 2200uF/400V M12 Table 58: Corrective spare parts - Precharge resistors Description Part number Quantity per order Resistor 15K/10W a filo smaltata 6310.60.200 EPS:529 UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 158: Table 59: Corrective Spare Parts - Main Transformer

    Constant Current Regulator Type VIS Technical Data Table 59: Corrective spare parts - Main transformer Description Part number Quantity per order Transf.400Vac out:24V ref:524108 6300.03.430 Transf.100VA 400V/24V- 6300.03.400 94VA/24V-6VA Transf.200VA 400V/24V- 6300.03.410 6VA/24V-194VA Table 60: Corrective spare parts - Fan connector cable...
  • Page 159: Support

    Our experienced engineers are available for support and service at all times, 24 hour/7 days a week. They are part of a dynamic organization making sure the entire ADB SAFEGATE is committed to minimal disturbance for airport operations. ADB SAFEGATE Support Technical Support –...
  • Page 160: Adb Safegate Website

    A.2.1.1 Local Authority Recycling The disposal of ADB SAFEGATE products is to be made at an applicable collection point for the recycling of electrical and electronic equipment. The correct disposal of equipment prevents any potential negative consequences for the environment and human health, which could otherwise be caused by inappropriate waste handling.
  • Page 161 UM-6007, Rev. 2.2, 2024/07/17 Copyright ADB Safegate, All Rights Reserved ©...

This manual is also suitable for:

Cre

Table of Contents