Constant Current Regulator Type VIS User Manual UM-6007, Rev. 2.2, 2024/07/17...
Page 3
Material Handling Precautions and Storage precautions that must be followed. ADB SAFEGATE reserves the right to examine goods upon which a claim is made. Said goods must be presented in the same condition as when the defect therein was discovered. ADB SAFEGATE furthers reserves the right to require the return of such goods to establish any claim.
Page 4
Use this equipment only as described in the manual. ADB SAFEGATE cannot be held responsible for injuries or damages resulting from non-standard, unintended uses of its equipment. The equipment is designed and intended only for the purpose described in the manual. Uses not described in the manual are considered unintended uses and may result in serious personal injury, death or property damage.
Page 8
Constant Current Regulator Type VIS TABLE OF CONTENTS 8.4.5 Start the equipment after a firmware update ..........................108 9.0 PCB drawings and settings ............................... 111 9.1 CPU PCB (EPS479) ........................................ 111 9.1.1 LEDs ..........................................111 9.2 Power supply PCB (EPS480) ..................................... 112 9.2.1 LEDs ..........................................
Page 12
Constant Current Regulator Type VIS List of Tables Table 35: Ambient conditions ......................................129 Table 36: Preventive spare parts - Main fuse ................................130 Table 37: Preventive spare parts - Main contactor ..............................130 Table 38: Preventive spare parts - Lightning arrestors ............................130 Table 39: Preventive spare parts - Overvoltage protection ..........................
Page 13
A.0 Safety Introduction to Safety This section contains general safety instructions for installing and using ADB SAFEGATE equipment. Some safety instructions may not apply to the equipment in this manual. Task- and equipment-specific warnings are included in other sections of this manual where appropriate.
Page 15
Material Handling Precautions and Storage precautions that must be followed. ADB SAFEGATE reserves the right to examine goods upon which a claim is made. Said goods must be presented in the same condition as when the defect therein was discovered. ADB SAFEGATE furthers reserves the right to require the return of such goods to establish any claim.
Page 16
Use this equipment only as described in the manual. ADB SAFEGATE cannot be held responsible for injuries or damages resulting from non-standard, unintended uses of its equipment. The equipment is designed and intended only for the purpose described in the manual. Uses not described in the manual are considered unintended uses and may result in serious personal injury, death or property damage.
Page 18
Constant Current Regulator Type VIS A.0 Introduction to Safety CAUTION Unsafe Equipment Use This equipment may contain electrostatic devices, hazardous voltages and sharp edges on components • Read installation instructions in their entirety before starting installation. • Become familiar with the general safety instructions in this section of the manual before installing, operating, maintaining or repairing this equipment.
Page 19
Note To minimize the risk of errors, the ADB SAFEGATE Sales Representative will have information on which gasket goes with which base. This information is also provided in the product Data sheets, the User Manuals and the Spare Part Lists.
Page 20
Constant Current Regulator Type VIS A.0 Operation Safety CAUTION Improper Operation Do Not Operate this equipment other than as specified by the manufacturer • Only qualified personnel, physically capable of operating the equipment and with no impairments in their judgment or reaction times, should operate this equipment.
Page 21
Note To minimize the risk of errors, the ADB SAFEGATE Sales Representative will have information on which gasket goes with which base. This information is also provided in the product Data sheets, the User Manuals and the Spare Part Lists.
Constant Current Regulator Type VIS Description 1.2 Working Principle Line input. See Line input Precharge PCB. See Line input Diode bridge and sensing PCB.See IGBT power bridge Capacitor bank. See Capacitor bank IGBT module and IGBT PCB. See IGBT power bridge Output filter.
Constant Current Regulator Type VIS Description 1.3 Layout of the Equipment Cabinet 1.3.1 Outside - small cabinet: 2.5 to 15 kVA Ventilation grids Serial communication port Manual switch Remote control connector Series output connection. The illustration shows the SCO Output to Series Circuit...
Constant Current Regulator Type VIS Description 1.4.1 Line input Figure 4: Input terminal, all cabinets The input terminal connects the power input cables to the equipment. Figure 5: Line filter, all cabinets The line filter blocks the noise the equipment generates to the line input and filters out voltage pulses from the input voltage.
Constant Current Regulator Type VIS Description The main contactor allows the power supply PCB to automatically interrupt the power. Figure 11: Precharge contactor, small cabinet The precharge contactor allows a smooth charge of the capacitors on the capacitor bank. Figure 12: Precharge contactor, big cabinet The precharge contactor allows a smooth charge of the capacitors on the capacitor bank.
Constant Current Regulator Type VIS Description The power supply transformer: • Measures the input voltage level between phases L2 and L3. • Provides the correct current and voltage to power all the electronic components such as PCBs and to power the fans (for 15 to 30kVA equipment).
Constant Current Regulator Type VIS Description 1.4.3 Capacitor bank The capacitor bank smoothens the DC current and voltage to make a constant DC current and voltage. Figure 21: Capacitor bank, small cabinet Figure 22: Capacitor bank, big cabinet 1.4.4 Hall sensor, big cabinet Figure 23: Hall sensor, big cabinet The Hall sensor measures the current between the IGBT and the output filter.
Constant Current Regulator Type VIS Description 1.4.7 Output measure PCB (EPS422), all cabinets The output measure PCB measures the output voltage and current and sends these measurements to the CPU PCB. The EFD (See Earth Fault Detection (EFD) ) and LFD (See...
1.4.10 Remote control PCB (EPS495 or EP00047), all cabinets Note Until 2022, the VIS was delivered with the EPS495 board as the remote control PCB. Since 2022, the VIS has been delivered with the EP00047, and the EP00051 as an add-on board when Multiwire is required. The functionalities of these boards are equivalent in most cases, with the exception of the most demanding recent ALCMS systems with a redundant bus.
Constant Current Regulator Type VIS Description 1.4.11 Power supply PCB (EPS480), all cabinets The power supply PCB provides the power supply for: • All electronic components such as PCBs of the equipment • The fans (for 15 to 30 kVA equipments) •...
1.5.1 Remote control Note Until 2022, the VIS was delivered with the EPS495 board as the remote control PCB. Since 2022, the VIS has been delivered with the EP00047, and the EP00051 as an add-on board when Multiwire is required. The functionalities of these boards are equivalent in most cases, with the exception of the most demanding recent ALCMS systems with a redundant bus.
Constant Current Regulator Type VIS Description 1.5.3 Series Connector Box (SCB), all cabinets The SCB connects the equipment to the series circuit with two medium voltage cables of the primary circuit. The SCB does not allow the short circuit connection.
Constant Current Regulator Type VIS Description of the HMI Table 1: Display description: Main screen (Continued) Name Description True RMS output current Shows the true RMS output current in A Highest brightness step Shows the time that the equipment operates at the maximum brightness step in h...
Constant Current Regulator Type VIS Description of the HMI For an overview of alarm texts and messages, see Alarm texts and messages on the HMI 2.6 Maintenance menu A password is required to access the maintenance menu. Table 6: General function buttons...
Page 50
Constant Current Regulator Type VIS Description of the HMI Alarm text / message Possible cause GATE H FAULT There is a problem with the H-bridge (IGBT). On the HMI, a message shows “IGBT KO: xxx x” IGBT KO: ... Both IGBTs are broken...
Page 51
There is a problem with the mains frequency detection x PIC COMMUNICATION ERROR A faulty communication with the measurement PCB PRE-CHARGE CONTACTOR ON The pre-charge contactor is broken (VIS only) PRE-CHARGE CONTACTOR OFF The pre-charge contactor is broken (VIS only) SCO / DOOR OPENED...
When you activate the configuration tool, you transfer all control of the equipment to the configuration software tool. In this situation, remote or local control of the equipment is not possible. To update the software version, contact ADB Safegate. 3.1 Description of screens and menus...
Constant Current Regulator Type VIS Description of the configuration software tool You can adjust the values in the yellow areas (A). You cannot adjust values in the orange areas (B). White selection boxes: if the box is marked, the item applies (C).
Constant Current Regulator Type VIS Description of the configuration software tool 3.2.4 Regulation Errors Possible cause Alarm type CCR switched OFF for OVERCURRENT • • The output current is more than Imax +5% The equipment automatically switches for minimum 4s •...
Constant Current Regulator Type VIS Description of the configuration software tool 3.3 Output/Mains screen Description Output screen part See items B to F Output currents Off if overload Imax Shows the maximum output current Overcurrent Overcurrent Off if overload Off if overload...
Constant Current Regulator Type VIS Description of the configuration software tool 3.4 Test screen Description Read To read the actual Analogue Data parameters (AD0 to AD7) from the selected equipment Brightness Brightness Ctrl Hardware Iprim Ctrl Hardware Iprim Switch on JBUS...
To read the actual configuration parameters from the selected data line Open Circuit Do not use these parameters. There is a risk of damage to the equipment. Only ADB Safegate service engineers are allowed to use these parameters Regulation Rate...
Constant Current Regulator Type VIS Description of the configuration software tool 3.5.3 SN/YearCode Item Description YearCode/SN To change the production year and the serial number Change To activate the value and to send it to the equipment 3.5.4 Maintenance Password...
Constant Current Regulator Type VIS Description of the configuration software tool 3.7 Diag/Dsp/BUS screen Description Slave errors Slave Errors Rem Reset Rem Reset Dsp parameters Dsp Parameters Imp Test Imp Test Hours_Meter Hours_Meter Bus Parameters • Arbiter: To set the signal source for remote control. To set a priority for different systems. If you set this parameter to disabled, remote control is not possible.
Constant Current Regulator Type VIS Description of the configuration software tool 3.7.5 Hours_Meter Item Description Total Shows the total time that the equipment is set to ‘on’ in h Max Br. Shows the time that the equipment operates at the maximum brightness step in h...
Page 70
Constant Current Regulator Type VIS Install and operate the configuration software tool Connect the serial cable, if applicable 1. Switch OFF the equipment. See Switch OFF the equipment. 2. Connect the extension cable to the dongle (A) and to the serial communication port of the PC (B).
Constant Current Regulator Type VIS Install and operate the configuration software tool 4.3 Monitor the data of an equipment Select the equipment 1. Select the slave number of the equipment you want to monitor. 2. Push the OK button. Start monitoring 1.
Constant Current Regulator Type VIS Commissioning Measure 1. Measure the input voltage on the input terminals (A). Use a True RMS Multimeter. 2. Examine if the voltage is in accordance with: • The nameplate of the equipment. • Local regulations.
Constant Current Regulator Type VIS Commissioning 5.1.6 Measure the output current in short circuit Connect AC True RMS multimeter (SCB) • Connect the current clamp of an AC True RMS multimeter (B) to the short-circuited cable (A). Connect AC True RMS multimeter (SCO) •...
Constant Current Regulator Type VIS Commissioning 5.1.10 Measure resistance of series circuit Measure the resistance: measure on the ends of the series cable (A). Use a multimeter (B), in accordance with local regulations. 5.1.11 Measure insulation resistance of series circuit 1.
Constant Current Regulator Type VIS Commissioning Check brilliancy level 1. Examine if all light fittings have the same brilliancy level. Go to the runway area to make a visual inspection. 2. Examine all the brightness steps separately. Go through the whole procedure for each brightness step.
Constant Current Regulator Type VIS Commissioning Examine or adjust the input and output signals function assigned to terminals 1. Push the → or ← buttons until the HMI shows the multiwire configuration. 2. Check and adjust the signals if necessary. See Maintenance menu.
Constant Current Regulator Type VIS Operation 6.2 Switch OFF the equipment 1. On the HMI, push the Local button. The screen now shows the state LOCAL. 2. Push the OFF button. The equipment goes to the mode OFF. 3. Switch OFF the power supply. See Switch OFF the power supply.
Constant Current Regulator Type VIS Operation Local mode An alarm occurs, the equipment switches OFF automatically. • If you need to switch off the power supply to remove the cause of the alarm: The equipment starts to produce the same output current that was valid before the equipment was switched OFF.
Constant Current Regulator Type VIS Operation Set operation mode 1. Install the cover (B). See the cover placement in Operation mode. 2. Close the lock (A). 6.9 Operation mode A series circuit with non-linear loads can be unstable. If the system is unstable, follow the procedure below.
Constant Current Regulator Type VIS Troubleshooting 7.2.1 Fault: Equipment does not turn ON Table 9: Equipment does not turn ON Problem Possible cause Possible solution No display indications A problem with the power supply on the • Examine the transformer on the diode bridge diode bridge PCB •...
Constant Current Regulator Type VIS Troubleshooting 7.2.3 Fault: Equipment turns ON but suddenly de-energizes Table 11: Equipment turns ON but suddenly de-energizes Problem Possible cause Solution (See) After you press the ON button, The input AC line delivers less than 360...
Page 94
Constant Current Regulator Type VIS Troubleshooting If the voltage you measure with the LFD module connected is already 330 V DC, the cable leakage resistance is approximately 10 MOhm. In this case, the discharge time is approximately 5 seconds for a cable capacitance of 1 pF.
Constant Current Regulator Type VIS Maintenance CAUTION While you carry out maintenance: • Do not drop screws or nuts inside the equipment cabinet. Collect loose nuts and screws immediately. • To identify all cables you disconnect, label the cables. •...
Constant Current Regulator Type VIS Maintenance Install 1. Install the new CPU PCB. 2. Install the fasteners. 3. Connect all the wires. CAUTION Connect the keyboard cable with the green side down. Update the firmware 1. Update the firmware. See Firmware update.
Constant Current Regulator Type VIS Maintenance 8.2.4 Diode bridge and sensing PCB (EPS 497) replacement, big cabinet For parts, see Parts list. • Diode bridge + sensing PCB Prepare 1. Remove the lower front panel. See Remove panels. 2. Remove the precharge PCB. See Precharge PCB (EPS546) replacement, small cabinet.
Constant Current Regulator Type VIS Maintenance 8.2.7 IGBT PCB (EPS477 / EPS 478) replacement, small cabinet For parts, see Parts list. • IGBT PCB Note The IGBT PCB, IGBT module, and the diode bridge and sensing PCB together are the IGBT power bridge. If one component breaks, replace the entire IGBT power bridge.
Constant Current Regulator Type VIS Maintenance Remove the spring from the IGBT • Make sure that spring number 7 (A) of the IGBT is removed. Once a spring has been removed, it cannot be reinstalled. Install CAUTION When you tighten the fasteners, only apply force vertically. Use an alien key screwdriver or an allen key handle instead of a socket wrench or a ratchet.
Constant Current Regulator Type VIS Maintenance Install 1 1. Wipe clean the heat sink below the IGBT (A). 2. Apply an even layer of conductive paste on the rear of the IGBT (the side that touches the heat sink). 3. Tighten the fasteners (B) crosswise. Apply a torque of 4 Nm.
Constant Current Regulator Type VIS Maintenance 8.2.13 Main contactor replacement For parts, see Remove panels. • Main contactor WARNING Make sure that you switched OFF the power to the equipment. See Switch OFF the power supply. WARNING Make sure that you switched OFF the external disconnection device to remove all power to the equipment.
Page 110
Constant Current Regulator Type VIS Maintenance Remove panel • Remove the lower front panel. See Remove panels. Disconnect 1. Loosen the screws (A). 2. Disconnect the wires (B). 3. Remove the manual switch (C). Use a screwdriver as a lever to release the manual switch from the rail (D).
Page 112
Constant Current Regulator Type VIS Maintenance Remove 1. Disconnect the wires (A). 2. Remove the fasteners (B). 3. Remove the output filter plate (C). Disconnect 1. Disconnect the fasteners (A). 2. Remove the output filter plate (C) from the back plate (B).
Constant Current Regulator Type VIS Maintenance 8.2.18 Output measure PCB (EPS442) replacement Parts: see Parts list. • Output measure PCB Remove panels 1. Remove the upper rear panel. See Remove panels. 2. Remove the screws (A). 3. Remove the box panel (B).
Page 116
Constant Current Regulator Type VIS Maintenance Remove panel • Remove the lower front panel. See Remove panels. Disconnect 1. Loosen the screws (A). 2. Disconnect the wires (B). 3. Remove the precharge contactor (C). Use a screwdriver as a lever to release the manual switch from the rail (D).
Constant Current Regulator Type VIS Maintenance 4. Remove the fasteners (D). 5. Remove the electrical wires. Install 1. Connect all the wires. 2. Tighten the fasteners (A). Apply a torque of 4 Nm. 3. Install the new precharge PCB. 4. Install the lower front panel. See Generic panels.
Constant Current Regulator Type VIS Maintenance Install 1. Install the new SCB. 2. Put the series circuit cables through the stress-relief clamps. 3. Tighten the screws of the stress-relief clamps. 4. Install all the wires and connectors. 5. Install the box panel.
Page 122
Constant Current Regulator Type VIS Maintenance Connect the micro switch 1. Disconnect the cables to the micro switch (A). 2. Connect the cables to the micro switch (A) in the new SCO. Install 1. Install the new SCO. 2. Install the bolts (D).
Constant Current Regulator Type VIS Maintenance 8.3.1 Remove the display / keyboard panel of the small cabinet Disconnect HMI 1. Remove the front panel. See Generic panels. 2. Disconnect the wires (A) to the HMI from the CPU PCB (B).
Constant Current Regulator Type VIS Maintenance CAUTION Take care not to damage cables and connectors. 8.3.3 Top panel (small cabinet) Disconnect HMI 1. Remove the front panel. See Generic panels 2. Disconnect the wires (A) to the HMI from the CPU PCB (B).
Constant Current Regulator Type VIS Maintenance 3. Do a check on the equipment parameters. See Check equipment parameters. 4. Update the firmware. See Update the firmware. 5. Start the equipment after a firmware update. See Start the equipment after a firmware update.
4. Push the Read button to show the firmware details. 5. Make sure that the equipment parameters below match those of the filename of the required firmware version: • Single Phase (CRE) or Tri-phase (VIS) • Input Voltage: 230V range or 400V range •...
Constant Current Regulator Type VIS Maintenance 8.4.4 Update the firmware Prepare the equipment 1. Remove the lower front panel. See Generic panels 2. Remove the watch-dog jumper from the CPU PCB (EPS479). See CPU PCB (EPS479). 3. Connect the firmware update dongle (A) between the PC and the equipment.
Constant Current Regulator Type VIS PCB drawings and settings 9.2 Power supply PCB (EPS480) Figure 29: Printed Circuit Board (PCB) 9.2.1 LEDs Table 15: Power supply PCB LED functions Color Function Green The voltage for the fans, if applicable is +24 V DC (generated on the PCB)
9.3 Remote Control PCB Note Until 2022, the VIS was delivered with the EPS495 board as the remote control PCB. Since 2022, the VIS has been delivered with the EP00047, and the EP00051 as an add-on board when Multiwire is required. The functionalities of these boards are equivalent in most cases, with the exception of the most demanding recent ALCMS systems with a redundant bus.
Page 136
Constant Current Regulator Type VIS PCB drawings and settings Table 18: Remote control PCB jumper settings (Continued) Jumper Position Function position 1-3 and position 2-4 ethernet channel 1: enable 1 3 5 2 4 6 position 3-5 and position 4-6...
Constant Current Regulator Type VIS PCB drawings and settings 9.3.3 Multiwire/J-Bus connection scheme Note The table shows the standard remote control configuration for the signals. If you want another configuration, contact ADB Safegate. Table 19: Factory set terminal assignments for remote control connections with multiwire and single J-Bus (Cable Set 4072.30.XXX)
Page 140
Constant Current Regulator Type VIS PCB drawings and settings Table 20: Factory set terminal assignments for remote control connections with multiwire dual J-Bus (Cable Set 4072.30.182) (Continued) Function Terminal number on 32-pole Relay number on Remote Control PCB (unless connector...
Constant Current Regulator Type VIS PCB drawings and settings 9.4.1 LEDs EPS477 for 2s Semix Table 21: IGBT PCB LED functions Color Function LDX1 The voltage for the high side IGBT, generated on the PCB, is +18 V DC. LDX2 The voltage for the high side IGBT, generated on the PCB, is -5 V DC.
Constant Current Regulator Type VIS PCB drawings and settings 9.7 Test parameters 9.7.1 Analog channels Table 25: Analog channels Channel Description Value range Temperature 17000 - 32000 Temperature 27000 - 32000 I bridge 100 - 2000 V bridge 0 - 30000 V in ±31000...
Constant Current Regulator Type VIS Technical Data Table 30: Output specifications (Continued) Type Rated output power RMS output voltage at 6.6 A Insulated test on Output overvoltage protection [kW] RMS output current [kV] output [kV] 25kApk VIS 20 3.00 4.5 kV , 8.4 kJ...
Constant Current Regulator Type VIS Technical Data 10.4 Protection devices Table 33: Protection devices specifications Equipment type Equipment Main fuse rating [A] Manual switch type C rating [A] Maximum line input current [A] [kVA] voltage [V] 380 to 400 11.7 17.6...
For IEC conformity to -40 °C an optional modification is required. 10.7 Parts list WARNING Use only original ADB Safegate spare parts. If you use other spare parts, the specific module or the equipment may be damaged. This can also put personnel in danger. Note The parts list may be subject to change without prior notice.
6351.88.060 ISOLAT.M6 0.6kV 6126.12.485 Semix 341D16s 6351.88.030 Table 44: Preventive spare parts - CPU PCB Description Part number Quantity per order EPS479/5 CRE/VIS CPU pcb:CS00179 1597.00.000 rev.1.1 EPS479/15 CRE/VIS 1597.00.010 CPU pcb:CS00179 rev1.1 EPS479/30 CRE/VIS 1597.00.020 CPU pcb:CS00179 rev1.1 UM-6007, Rev. 2.2, 2024/07/17...
Constant Current Regulator Type VIS Technical Data Table 45: Preventive spare parts - Output measure PCB Description Part number Quantity per order EPS442/2.5 CRE/VIS 1597.00.100 out.meas.board CS0039 rev.2.2 EPS442/5 CRE/VIS out.meas.board 1597.00.110 CS0039 rev.2.2 EPS442/7.5 CRE/VIS 1597.00.120 out.meas.board CS0039 rev.2.2 EPS442/10 CRE/VIS 1597.00.130...
Constant Current Regulator Type VIS Technical Data Table 52: Preventive spare parts - Display and keyboard Description Part number Quantity per order Description Part number CCR KEYBOARD BOX 4072.30.630 ASSY. TRIPHASE 10.9 Corrective spare parts Item Table Manual switch Table 53...
Constant Current Regulator Type VIS Technical Data Table 59: Corrective spare parts - Main transformer Description Part number Quantity per order Transf.400Vac out:24V ref:524108 6300.03.430 Transf.100VA 400V/24V- 6300.03.400 94VA/24V-6VA Transf.200VA 400V/24V- 6300.03.410 6VA/24V-194VA Table 60: Corrective spare parts - Fan connector cable...
Our experienced engineers are available for support and service at all times, 24 hour/7 days a week. They are part of a dynamic organization making sure the entire ADB SAFEGATE is committed to minimal disturbance for airport operations. ADB SAFEGATE Support Technical Support –...
A.2.1.1 Local Authority Recycling The disposal of ADB SAFEGATE products is to be made at an applicable collection point for the recycling of electrical and electronic equipment. The correct disposal of equipment prevents any potential negative consequences for the environment and human health, which could otherwise be caused by inappropriate waste handling.