ADB Safegate CRE Installation Manual

Constant current regulator
Hide thumbs Also See for CRE:
Table of Contents

Advertisement

Quick Links

Constant Current Regulator
Type CRE
Installation Manual
6006, Rev. 2.1, 2024/07/16

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CRE and is the answer not in the manual?

Questions and answers

Summary of Contents for ADB Safegate CRE

  • Page 1 Constant Current Regulator Type CRE Installation Manual 6006, Rev. 2.1, 2024/07/16...
  • Page 3 Material Handling Precautions and Storage precautions that must be followed. ADB SAFEGATE reserves the right to examine goods upon which a claim is made. Said goods must be presented in the same condition as when the defect therein was discovered. ADB SAFEGATE furthers reserves the right to require the return of such goods to establish any claim.
  • Page 4 Use this equipment only as described in the manual. ADB SAFEGATE cannot be held responsible for injuries or damages resulting from non-standard, unintended uses of its equipment. The equipment is designed and intended only for the purpose described in the manual. Uses not described in the manual are considered unintended uses and may result in serious personal injury, death or property damage.
  • Page 5: Table Of Contents

    3.2 Transport and unpack the crate ..................................33 3.3 Transport Unpacked Equipment ..................................33 3.4 Storage ............................................35 4.0 Pre-Installation ..................................37 4.1 How to pre-install - general procedure ................................. 37 4.2 Prepare Substation ......................................... 37 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 6 6.7.2 EP00047 and EP00051 ..................................... 68 6.7.3 Multiwire/J-Bus connection scheme ..............................69 6.8 Interface PCB (PCB1702) (option CS) ................................72 A.0 SUPPORT ....................................77 A.1 ADB SAFEGATE Website ...................................... 78 A.2 Recycling ............................................ 78 A.2.1 ADB SAFEGATE Recycling ..................................78 Copyright ©...
  • Page 7 Figure 22: Printed Circuit Board (PCB) .................................... 66 Figure 23: Printed Circuit Board (PCB) .................................... 68 Figure 24: Multiwire and J-Bus connection ................................... 72 Figure 25: Printed Circuit Board (PCB) .................................... 72 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 8 Constant Current Regulator List of Figures viii Copyright © ADB Safegate, All Rights Reserved...
  • Page 9 Table 17: Factory set terminal assignments for remote control connections with multiwire dual J-Bus (Cable Set 4072.30.182) ..................................................70 Table 18: CS connectors ........................................73 Table 19: LEDs that indicate the logic functionality ..............................76 Table 20: LEDs that indicate the interface functionality ............................76 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 10 Constant Current Regulator List of Tables Copyright © ADB Safegate, All Rights Reserved...
  • Page 11: Safety

    1.0 Safety Introduction to Safety This section contains general safety instructions for installing and using ADB SAFEGATE equipment. Some safety instructions may not apply to the equipment in this manual. Task- and equipment-specific warnings are included in other sections of this manual where appropriate.
  • Page 12: Introduction To Safety

    Using this equipment in ways other than described in this manual may result in personal injury, death or property and equipment damage. Use this equipment only as described in this manual. Failure to follow this instruction can result in serious injury or equipment damage Copyright © ADB Safegate, All Rights Reserved...
  • Page 13: Material Handling Precautions: Storage

    Allow only qualified personnel to make repairs. Repair or replace the malfunctioning component according to instructions provided in its manual. Failure to follow these instructions can result in death or equipment damage 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 14: Material Handling Precautions, Esd

    • The tip of the soldering iron must be grounded. • Electronic modules and components must be stored and transported in conductive packing. Failure to follow this instruction can result in equipment damage Copyright © ADB Safegate, All Rights Reserved...
  • Page 15: Description

    Any other or additional use will not considered to be in conformity with the purpose. Do not operate the equipment outside the limits of the specifications or outside the specified ambient conditions. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 16: Working Principle

    The equipment converts the single phase input voltage line into a rectified current and voltage. The equipment then converts this DC current and voltage into a pure sine wave with a defined power rating. Copyright © ADB Safegate, All Rights Reserved...
  • Page 17: Layout Of The Equipment Cabinet

    2.3.1 Outside - stackable cabinet 2.5 kVA Ventilation grids Serial communication port Manual switch Remote control connector Series output connection. The illustration shows the SCB. Output to Series Circuit Power supply connector 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 18: Inside - Stackable Cabinet 2.5 Kva

    IGBT-PCBs (EPS477) Diode bridge + sensing PCB (EPS476) CPU PCB (EPS479) Power supply PCB (EPS480) Remote control PCB (EPS495 or EP00047) Line filter Main transformer Output measure PCB (EPS442) Main contactor Main fuses Copyright © ADB Safegate, All Rights Reserved...
  • Page 19: Outside - Small Cabinet: 2.5 To 15 Kva

    Series output connection. The illustration shows the SCO Output to Series Circuit Ethernet connector Power supply cable entry 2.3.4 Inside - small cabinet: 2.5 to 15 kVA Note The illustrations show the 10 kVA cabinet. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 20 Diode bridge and sensing PCB (EPS476 / EPS507) Power supply PCB (EPS480) Input filter Remote control PCB (EPS495 or EP00047) Lightning arrestors Output measure PCB (EPS442) Input terminals Line filter Main transformer Power supply transformer Copyright © ADB Safegate, All Rights Reserved...
  • Page 21: Outside - Small Cabinet: 2.5 To 15 Kva With Cs (Option Cs)

    2.3.6 Inside - small cabinet: 2.5 to 15 kVA with CS (option CS) Note The illustration shows only the items of the CS. For all other items, see Inside - small cabinet: 2.5 to 15 kVA. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 22 Constant Current Regulator Description Interface PCB (PCB1702) Power supply convertors for multiwire remote control Input terminals Lightning arrestors CS PCB (PCB1619) Current sensors CS relays Connection terminals for the primary circuit Supports Copyright © ADB Safegate, All Rights Reserved...
  • Page 23: Outside - Big Cabinet 20 To 30 Kva

    2.3.7 Outside - big cabinet 20 to 30 kVA Ventilation grids Serial communication port Manual switch Remote control connector Series output connection. The illustration shows the SCO Output to Series Circuit Ethernet connector Power supply cable entry 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 24: Inside - Big Cabinet 20 To 30 Kva

    Sensing PCB (EPS476) Diode Bridge Main fuses Main contactor IGBT-PCBs (EPS496) IGBTs Sensing transformer Output filter Remote control PCB (EPS495 or EP00047) Lightning arrestors Output measure PCB (EPS442) Hall sensor Input terminals Main transformer Copyright © ADB Safegate, All Rights Reserved...
  • Page 25: Outside - Big Cabinet: 20 To 30 Kva With Cs (Option Cs)

    2.3.10 Inside - big cabinet: 20 to 30 kVA with CS (option CS) Note The illustration shows only the items of the CS. For all other items, see Inside - small cabinet: 2.5 to 15 kVA. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 26: Components

    Connection terminals for the primary circuit Supports 2.4 Components For the exact location and connectors see Layout of the Equipment Cabinet and the electrical scheme. You can find the electrical scheme attached on the outside of the equipment. Copyright © ADB Safegate, All Rights Reserved...
  • Page 27: Line Input

    ON or OFF position. Figure 5: Main fuses, all cabinets The main fuses disconnect the equipment from the mains power supply if the input current is above a given value. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 28: Figure 6: Main Contactor, Stackable Cabinet And Small Cabinet

    The resistors on the precharge PCB limit the current for the precharge of the capacitor bank. Figure 8: Sensing transformer, all cabinets The sensing transformer measures the input voltage level of the line input. Figure 9: Power supply transformer, all cabinets Copyright © ADB Safegate, All Rights Reserved...
  • Page 29: Input Filter

    Figure 11: Input filter, 15 kVA small cabinet and big cabinet The input filter is a 12.5 kHz filter that blocks the noise the equipment produces from the line input at a different frequency than the line filter. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 30: Igbt Power Bridge

    In the stackable cabinet and the small cabinet, the sensing PCB and the diode bridge are combined into one part. Figure 13: Sensing PCB (EPS476), big cabinet The sensing PCB measures the AC input line and controls the diode bridge. Copyright © ADB Safegate, All Rights Reserved...
  • Page 31: Figure 14: Diode Bridge, Big Cabinet

    The system uses four IGBTs connected as an H-bridge to make an AC-signal. Figure 16: IGBT PCB (EPS477 /EPS496 /EPS 478), all cabinets The IGBT PCB measures the output signal from the IGBT H-bridge. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 32: Output Filter

    Figure 18: Output filter, 15 kVA small cabinet and big cabinet The output filter is a Pulse Width Modulation (PWM) filter that builds the pure sine wave signal that comes from the H-bridge. Copyright © ADB Safegate, All Rights Reserved...
  • Page 33 The output measure PCB measures the output voltage and current and sends these measurements to the CPU PCB. The EFD (See Earth Fault Detection (EFD) ) and LFD (See Lamp Fault Detection (LFD)) logic is also located on the output measure PCB. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 34: Power Output

    2.4.5.2 Remote control PCB (EPS495 or EP00047), all cabinets Note Until 2022, the CRE was delivered with the EPS495 board as the remote control PCB. Since 2022, the CRE has been delivered with the EP00047, and the EP00051 as an add-on board when Multiwire is required. The functionalities of these boards are equivalent in most cases, with the exception of the most demanding recent ALCMS systems with a redundant bus.
  • Page 35 2.4.5.4 Lamp Fault Detection (LFD) The equipment analyses the output current and the voltage pattern to calculate, on a linear load, the number of open circuited lamps, in compliance with IEC 61822:2009. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 36: Options

    2.5.1 Remote control Note Until 2022, the CRE was delivered with the EPS495 board as the remote control PCB. Since 2022, the CRE has been delivered with the EP00047, and the EP00051 as an add-on board when Multiwire is required. The functionalities of these boards are equivalent in most cases, with the exception of the most demanding recent ALCMS systems with a redundant bus.
  • Page 37: Circuit Selector (Cs)

    A varistor is a surge protection device that is connected directly across the AC output. 2.5.5 Interface PCB (PCB1702) (option CS) Note This item is installed on the CS when the CS option is chosen. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 38: Cs Pcb (Pcb1619) (Option Cs)

    Note This item is installed on the CS when the CS option is chosen. The HMI SIN BCB provides the indication of the state of the different series circuits (selected or not selected). Copyright © ADB Safegate, All Rights Reserved...
  • Page 39: Remote Control Sin Pcb (Pcb1694) (Option Cs)

    2.5.9 CS relay (option CS) Note This item is installed on the CS when the CS option is chosen. The CS relays switch on or off its designated series circuit. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 40: Current Sensor (Option Cs)

    The SCO acts as an output disconnection device between the equipment and the series circuit. The SCO also isolates the series circuit from the equipment during maintenance or testing operations. The cover is locked with a key to prevent unauthorized access. Copyright © ADB Safegate, All Rights Reserved...
  • Page 41: Rolling Castors

    You can operate the equipment with the HMI. 2.7 HMI of an equipment with CS (option CS) You can operate the equipment with the HMI. 2.8 Nameplate Each equipment has a standard nameplate: 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 42 Constant Current Regulator Description Copyright © ADB Safegate, All Rights Reserved...
  • Page 43: Inspection, Transportation And Storage

    Use the correct type of eye bolt. Suppliers of eye bolts provide data on configurations and maximum allowed load for different types of eye bolts. Use a rotation eye bolt to cover all applications with the same type of eye bolt. Note Contact ADB Safegate for the correct eye bolt type. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 44 3. Carefully move the equipment to the applicable location. Transport - small and big cabinet with wheels Push the equipment to the applicable location. WARNING Make sure that the ground surface is flat and horizontal. Copyright © ADB Safegate, All Rights Reserved...
  • Page 45: Storage

    Remove the oxidation layer from the electrical contact before connection, if necessary. NOTICE For long term storage, it is recommended to keep the equipment in a dry (<60% humidity) and moderate temperature area (15−30°C ambient temperature). 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 46 Constant Current Regulator Inspection, Transportation and Storage Copyright © ADB Safegate, All Rights Reserved...
  • Page 47: Pre-Installation

    5. Install an external fuse. See External fuse. 6. Make sure that the circuit breakers are of the correct type. See Circuit breakers. 7. Install the separate disconnection devices. See Disconnection devices. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 48: Provide Heat Dissipation

    Equipment [kVA] Heat dissipation [W] 1200 1400 1750 1800 Make sure that the heat dissipation efficiency is better than 90% for an equipment less than 30kVA and at least 92% for a 30kVA equipment. Copyright © ADB Safegate, All Rights Reserved...
  • Page 49: Ventilation

    External fuse Install the external fuse in the distribution panel with at least one rating higher than the manual switch (see Protection Devices) for fuses type gG or aM. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 50: Prepare Lightning Protection

    Disconnection devices 4.3 Prepare lightning protection 1. Examine the need for additional lightning protection. 2. If you need additional lightning protection, contact ADB Safegate to supply lightning diverters in accordance with IEC 61822. 4.4 Install power supply 1. Install a power supply for each equipment.
  • Page 51: Plan Cables To Remote Control Interface

    Make sure that you plan power supply and earthing cables that comply with table 3-B in IEC 6095-1 latest edition. 4.5.1 Plan cables to remote control interface WARNING Only earth the remote control cable at one end, preferably at the equipment side. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 52: Table 2: Recommended Multiwire Cables

    Table 4: Wire sections for J-Bus cables Cable type Number of wires Diameter [mm] JE-LiYCY (with armouring type R, B, Q or Z) 2 or 3 pairs twisted TWAVB 4 or 6 x 0.8mm (0 V wire) Copyright © ADB Safegate, All Rights Reserved...
  • Page 53 Ethernet cables (option) Use an FTP CAT 5e patchcable to limit the electromagnetic interference. You can use also a higher cable standard. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 54 Constant Current Regulator Pre-Installation Copyright © ADB Safegate, All Rights Reserved...
  • Page 55: Installation

    For each equipment there is a power supply cable available For each equipment there is a remote control cable available For each equipment there is a series circuit cable available 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 56: Required Tools And Equipment

    2. Examine if the inner side of the equipment is not damaged. 3. Examine the transformers for displacement or bending. 4. If you see damage, displacement or bending, tell the carrier immediately. Copyright © ADB Safegate, All Rights Reserved...
  • Page 57: Switch Off The Power Supply

    5.3 Switch OFF the power supply 1. Set the manual switch (A) to the OFF position. 2. Open the main switch on the main distribution board. 3. Disconnect the equipment from the series circuit. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 58: Remove Lower Rear Panel, Big And Small Cabinet

    3. Carefully remove the panel (B). CAUTION Do not damage cables and/or connectors. 4. Disconnect the green/yellow earthing wires. The wires have a fast-on connector. Figure 20: Disconnect wires Copyright © ADB Safegate, All Rights Reserved...
  • Page 59: Install Additional Earthing, Stackable Cabinet

    Earth the cabinet correctly. The equipment can create ground return currents up to 3.5 mA. Also when the equipment is not connected to the load, the equipment can create lethal ground currents. 2. Connect the earthing wire to the earthing network of the substation. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 60: Connect Power Input Supply, Stackable Cabinet

    2. Examine if the numbers on the connector correspond with the numbers on the input connector on the equipment. 3. Install the connector to the equipment. 4. Close the clamps of the connector. Copyright © ADB Safegate, All Rights Reserved...
  • Page 61: Connect Power Input Supply, Big And Small Cabinet

    Phase Neutral 380-400 Phase Phase 3. Connect the earthing wire to the terminal (D). Connect - 2 Connect the earthing wire to the earthing network (A) of the substation. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 62: Connect Power Input Supply, Big And Small Cabinet With Cs (Option)

    1. Connect the input supply cables to the terminals (A) and (B). Input [V] 208-230 Phase Neutral 380-400 Phase Phase 2. Connect the earthing wire to the terminal (C). Connect - 2 Connect the earthing wire to the earthing network (A) of the substation. Copyright © ADB Safegate, All Rights Reserved...
  • Page 63: Connect Output To Series Circuit

    ø Y: less than or equal to 18 mm • B: screened cables • X: 16 mm • ø Y: less than or equal to 18 mm • U: 11 mm • Z: 77 mm 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 64: Connect Output To Series Circuit With Sco

    5. Install the series circuit cables. 6. Tighten the screws (B), (D) and (E). Finish Install the box panel. 5.10.2 Connect Output to Series Circuit with SCO Remove cover Remove the cover (A) of the SCO. Copyright © ADB Safegate, All Rights Reserved...
  • Page 65 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 66: Connect Output To Series Circuit (Option Cs)

    The number of terminals available for series circuit connections depends on your order. CAUTION Make sure you connect all terminals. If you do not want to use all terminals, put the free terminals into short-circuit. Copyright © ADB Safegate, All Rights Reserved...
  • Page 67 7. Connection to series circuit (the number on the label refers to the series circuit, OUT if there is only one series circuit The label is located in front of the terminals. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 68: Connect Remote Control Cables

    6. Install the protection plate and the screws. 5.11 Connect Remote Control Cables Connect multiwire or J-Bus (option) Note If the terminal blocks are not located on the correct sides, the remote control does not work. Copyright © ADB Safegate, All Rights Reserved...
  • Page 69 3. Examine if the numbers on the connector correspond with the numbers on the female side on the receiver of the remote connector. 4. Install the connector to the equipment. 5. Close the clamps of the connector. Connect ethernet cable(s) (option) Install the connector(s) to the ethernet connection(s). 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 70: Install Lower Rear Panel

    CS). To connect the individual wires to the WAGO connectors, use the specific tool delivered with the equipment. 5.12 Install Lower Rear Panel Connect the earthing wire and install the lower rear panel. See Remove lower rear panel, big and small cabinet. Copyright © ADB Safegate, All Rights Reserved...
  • Page 71: Technical Data

    1.5 kV , 2.8 kJ CRE 7.5 1.13 2.2 kV , 4.2 kJ CRE 10 1.50 2.2 kV , 4.2 kJ CRE 15 2.30 3.0 kV , 5.6 kJ 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 72: Applicable Standards

    From -20 up to +55 °C Altitude From 0 (sea level) up to 1000 meter Relative humidity From 10% up to 95% RH without condensation Notes For IEC conformity to -40 °C an optional modification is required. Copyright © ADB Safegate, All Rights Reserved...
  • Page 73: Dimensions And Mass

    1200 x 800 x 1500 1200x800x 1500 1200 x 800 x 1500 1200 x 800 x 1500 1200 x 800 x 1850 1200 x 800 x 1850 1200 x 800 x 1850 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 74: Substation Layout

    Between the rear of the machine and the wall, X Approximately 500 Between two machines (side by side) or between another machine, Y Minimum 150 If necessary, the distances can be increased for maintenance purposes. Copyright © ADB Safegate, All Rights Reserved...
  • Page 75: Protection Devices

    6.7 Remote Control PCB Note Until 2022, the CRE was delivered with the EPS495 board as the remote control PCB. Since 2022, the CRE has been delivered with the EP00047, and the EP00051 as an add-on board when Multiwire is required. The functionalities of these boards are equivalent in most cases, with the exception of the most demanding recent ALCMS systems with a redundant bus.
  • Page 76: Eps495 (1597.00.300)

    RX serial channel 2 termination resistance position 1-3 and position 2-4 ethernet channel 1: enable 1 3 5 2 4 6 position 3-5 and position 4-6 serial channel 1: enable 1 3 5 2 4 6 Copyright © ADB Safegate, All Rights Reserved...
  • Page 77: Table 15: Remote Control Pcb Jumper Settings

    2: RS485 configuration position 1-2 serial channel 2: RS422 configuration (not used) position 2-3 serial channel 2: RS485 configuration position 1-2 serial channel 2: RS422 configuration (not used) 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 78: Ep00047 And Ep00051

    120 Ohm 120 Ohm CAN (1-2) Boot-GND (2-3) RS485_2_TX+ (1-2) RS485_1_TX+ 120 Ohm 120 Ohm RS485_2_RX+ RS485_1_RX+ RS485_2_RX+ (4w:2-3, RS485_1_RX+ 2w:1-2) (4w:2-3) RS485_2_RX- (4w:2-3) J38 RS485_1_RX- (4w:2-3) RS485_2 (3-5, 4-6) RS485_1 (3-5, 4-6) Copyright © ADB Safegate, All Rights Reserved...
  • Page 79: Multiwire/J-Bus Connection Scheme

    Feedback signals (configurable via HMI): the values below are default values, for configuration options (for the options, see the table that follows) Disable local/remote (relay 7 for both J5.7 (NC relay) connections) J5.8 (NO relay) 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 80: Table 17: Factory Set Terminal Assignments For Remote Control Connections With Multiwire Dual J-Bus (Cable Set 4072.30.182)

    J1.8 V-OUT 48V J8.1 GND 48V J8.2 Feedback signals (fixed) GND - FB J8.3 GND - FB J8.4 Step 1 - FB J5.1 Step 2 - FB J5.2 Step 3 - FB J5.3 Copyright © ADB Safegate, All Rights Reserved...
  • Page 81 J-Bus interface (fixed) RS485 Bus B GND DB92.3 RS485 Bus B- DB92.1 RS485 Data B+ DB92.2 RS485 Bus A GND DB9.3 RS485 Data A - DB9.2 RS485 Data A + DB9.1 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 82: Interface Pcb (Pcb1702) (Option Cs)

    +48 V DC I Rel com Remote control PCB - feedback signals Relays 24 V DC power supply J-Bus RS485 connection J-Bus RS485 interface 6.8 Interface PCB (PCB1702) (option CS) Figure 25: Printed Circuit Board (PCB) RJ45 Copyright © ADB Safegate, All Rights Reserved...
  • Page 83: Table 18: Cs Connectors

    Equipment ON control can happen only happen through an external signal (no jumper J10 and no resistor R116 wired) or by a brightness selection (if jumper J10 is installed or resistor R116 is wired). 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 84 Feedback circuit 5 CS6FB Feedback circuit 6 CS7FB Feedback circuit 7 CS8FB Feedback circuit 8 CSE-FLT Feedback CS fault CSESP1CS6FB Feedback CS, spare 1 CSESP2CS5FB Feedback CS, spare 2 CSESP3CS4FB Feedback CS, spare 3 Copyright © ADB Safegate, All Rights Reserved...
  • Page 85 The voltage source (floating in regard to earth in this equipment) can be used to give a voltage feedback signal if the positive or negative pole is connected to CF. 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...
  • Page 86: Table 19: Leds That Indicate The Logic Functionality

    LED to CRE LOCREM. The LED is ON if there the equipment is in local mode LED to CRE REQCON. The LED is ON if the CS requests to switch on the equipment LED CSEFLT. The LED is ON if the circuit selector is faulty (CSE-FAULT) LED SP_UC1.
  • Page 87: Support

    Our experienced engineers are available for support and service at all times, 24 hour/7 days a week. They are part of a dynamic organization making sure the entire ADB SAFEGATE is committed to minimal disturbance for airport operations. ADB SAFEGATE Support Technical Support –...
  • Page 88: Adb Safegate Website

    A.2.1.1 Local Authority Recycling The disposal of ADB SAFEGATE products is to be made at an applicable collection point for the recycling of electrical and electronic equipment. The correct disposal of equipment prevents any potential negative consequences for the environment and human health, which could otherwise be caused by inappropriate waste handling.
  • Page 89 6006, Rev. 2.1, 2024/07/16 Copyright ADB Safegate, All Rights Reserved ©...