Motor lead pigtail splice fir 5/8 kv non-shielded and shielded cables ribbon or wire and unishield cables, cable size range, feeder 8 awg-500 kcmil, motor lead 10 awg-500 kcmil, copper conductors (12 pages)
Motor lead pigtail splice for 1000 volts (or less) cables with one-hole lugs (4 pages)
Summary of Contents for 3M 7600-T-3RJS Series
Page 1
Rubber 3/C Cabinet Mount Termination Kit With High-K Stress Relief For 3-Conductor Copper Tape Shield Cables with or without Ground Wires 7600-T-3RJS Series Instructions IEEE Std. No. 48 Class 1 Termination F CAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment.
Page 5
Temporary Vinyl Tape Band Ground Wire Copper Tape Shield Figure 1 2.0 Attach Metallic Shield Grounding Braids 2.1 Cut supplied tinned copper grounding braid into three equal 2’ (610 mm) lengths. Expand each braid end for a ② distance of 2" (51 mm) ( Figure 2).
Page 6
2.2 Attach shield ground braids: A. Position each expanded ground braid end over phase shielding as shown in Figure 3. B. Using bands of Scotch Vinyl Electrical Tape, secure upper braid end to copper tape shielding 8" Super 33+ ® ™...
Page 7
3.0 Install Silicone Rubber Rejacketing Sleeves 3.1 From the chart below, determine the correct [A] dimension (Figure 5) for the termination product being installed. Kit Number Dimension [A] 7620-T-95-3-RJS 6.75” (171 mm) 7621-T-95-3-RJS 7623-T-95-3-RJS 5.50” (140 mm) 7624-T-95-3-RJS 7625-T-95-3-RJS 7621-T-110-3-RJS 7622-T-110-3-RJS 8.5”...
Page 8
3.5 Guide one rejacketing sleeve assembly over each cable phase leg (Figure 7). Push sleeve assembly from above. Continuously guide the free end maintaining sleeve-to-cable-core alignment. Figure 7 3.6 Slide rejacketing sleeve until inner polyester braid is within 2" (51 mm) of desired final location (near cable entrance gland).
Page 10
Start taping 0.75" (19 mm) over rejacketing sleeve, extend 0.25" (6 mm) over cable metallic shield and return to starting point. Note: Do not fully cover the Copper Tape Shield or 3M™ EMI Copper Foil Shielding Tape 1181 Strips. BE SURE TO LEAVE PART OF THE COPPER TAPE SHIELD EXPOSED.
Page 11
2. Use only aluminum oxide abrasive; grit 120 or finer. 3. Be careful not to reduce the cable insulation diameter below that allowed by the kit. (e.) Thoroughly clean primary insulation and lug barrel area using a solvent wipe from supplied 3M Cable ™...
Page 12
INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the 3M product.
Need help?
Do you have a question about the 7600-T-3RJS Series and is the answer not in the manual?