ICP DAS USA MDC-211-433 User Manual

ICP DAS USA MDC-211-433 User Manual

433mhz modbus data concentrator
Table of Contents

Advertisement

Quick Links

User Manual
Version 1.0 May 2024
MDC-211-433
(433MHz Modbus data concentrator)
ICP DAS, MDC-211-433 User Manual Version 1.0
Page 1
Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MDC-211-433 and is the answer not in the manual?

Questions and answers

Summary of Contents for ICP DAS USA MDC-211-433

  • Page 1 User Manual Version 1.0 May 2024 MDC-211-433 (433MHz Modbus data concentrator) ICP DAS, MDC-211-433 User Manual Version 1.0 Page 1 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 2 Contact us If you encounter any problems while operating this device, feel free to contact us via mail at: service@icpdas.com . ICP DAS, MDC-211-433 User Manual Version 1.0 Page 2 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 3: Table Of Contents

    Module Setting – Interface Setting ..............29 2.5.1.1. Wireless ......................29 2.5.1.2. Ethernet ......................31 2.5.1.3. Serial Port ....................... 32 2.6. Communication protocols and modes ............... 34 ICP DAS, MDC-211-433 User Manual Version 1.0 Page 3 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 4 Q1 - How many Modbus commands and register data can be defined at most in MDC-211-433? ..........................62 Q2 - How many data can the Modbus Master read back from the MDC-211-433 in one command? ..........................62 Q3 - How does the data address of the Modbus RTU device correspond to the address of the MDC-211-433? ....................
  • Page 5: Product Introduction

    1.1. Introduction  Functions The MDC-211-433 is a Modbus data concentrator developed by ICP DAS. It features Ethernet, 433MHz wireless communication, RS-232, and RS-485 communication interfaces, and can connect Modbus RTU devices to the Ethernet network. The MDC-211-433 sequentially reads data from Modbus RTU devices according to a user-defined command list and integrates the data from different Modbus RTU devices into a continuous address format.
  • Page 6  Advantages The MDC-211-433 Modbus Data Concentrator not only helps users manage local RS- 232/RS-485 Modbus RTU devices but also easily connects to remote and dispersed Modbus RTU devices through the 433MHz wireless network, even in environments where wiring is difficult.
  • Page 7: Features

    The MDC-211-433 offers a simple and user-friendly web interface. Users can configure the MDC-211-433 using a computer with internet access via a web browser. It also allows real-time monitoring to check for abnormalities in the connections of each Modbus RTU command and their update frequencies.
  • Page 8 Modbus RTU command settings, can also be configured in a *.csv file. By importing this file through the web interface, users can begin monitoring data from remote Modbus RTU devices.  ICP DAS, MDC-211-433 User Manual Version 1.0 Page 8 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 9: Specifications

    33 x 120 x 115 mm (W x L x H, not include antenna ) Installation DIN-Rail Environment Operating Temperature ‐25°C ~ +75°C Storage Temperature ‐30°C ~ +80°C Humidity 10~90% RH, non-condensing ICP DAS, MDC-211-433 User Manual Version 1.0 Page 9 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 10: Dimensions (Unit: Mm)

    1.4. Dimensions (Unit: mm) Front view Product photo Left view Antenna installation diagram Antenna installation diagram (0 degrees) (90 degrees) ICP DAS, MDC-211-433 User Manual Version 1.0 Page 10 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 11: Appearance And Configuration

    Short-circuit it to GND and power on to INIT enter initialization mode. Power,+10V~+30VDC P.GND Power ground. Frame ground. RS-232 RS-485 ICP DAS, MDC-211-433 User Manual Version 1.0 Page 11 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 12: Led Indicators And Status

    GND, but the Ethernet (1second) is not connected. The RF module failed to initialize. Yellow (abnormal state) No abnormality. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 12 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 13 Waiting to receive wireless data. RFPWR The RF module is powered on (RF power status) The RF module is powered off ICP DAS, MDC-211-433 User Manual Version 1.0 Page 13 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 14: Get Started

    The host computer can send Modbus TCP commands to read back together and speed up data collection. Subsequent chapters will be introduced in this mode. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 14 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 15: Initialization Mode

    INIT pin short-circuit to the GND pin, and then power on the module again to enter this mode. Name Factory default value 192.168.255.1 Mask 255.255.0.0 Gateway 192.168.0.1 Account admin (case-insensitive) Password admin (case-insensitive) ICP DAS, MDC-211-433 User Manual Version 1.0 Page 15 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 16: Firmware Update Mode

    (2) Adjust your computer's network domain to be the same as the module's factory default network domain, for example: 192.168.255.111, and use an Ethernet line to connect the computer and module. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 16 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 17 At this time, the module will execute the new firmware and restore the IP address that before updating the firmware to the setting. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 17 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 18: Setting Flow Chart

    •Confirm Modbus communication status. Confirm •Confirm the correspondence between the Modbus RTU device and the internal communication register of the MDC module. status ICP DAS, MDC-211-433 User Manual Version 1.0 Page 18 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 19: Preparatory Work

    3. RS-232: Please connect the three-wire RS-232 to the module. 4. Ethernet: Please connect the module’s LAN and computer through a network cable (or through an Ethernet Switch/Hub). ICP DAS, MDC-211-433 User Manual Version 1.0 Page 19 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 20: Modify Ip Address

    The following describes the steps to use eSearch Utility to search for modules and modify network parameters: Step 1 Click [Search Server] to search for modules. Step 2 After selecting [MDC-211-433] with the mouse, click the [Configuration (UDP)] button. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 20 Copyright ©...
  • Page 21 After completion, click the [OK] button to modify the network parameters. Step 4 Click [Search Server] again to search the module and confirm whether the network parameters have been modified successfully. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 21 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 22: Login Web Page

    (Note) It is recommended to use IE11 / Chrome / Firefox as a browser with a resolution of 800 x 600 or above. Name Factory default value Account admin (case-insensitive) Password admin (case-insensitive) ICP DAS, MDC-211-433 User Manual Version 1.0 Page 22 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 23 Save button, you will be prompted again to refresh the web page and click Log in with new account and password. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 23 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 24 Information, Module Setting, I/O Information and Other Information, as shown below. The subsequent chapters will introduce the parameters in each tab in order. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 24 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 25: System Information

    The default value is 180 seconds. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 25 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 26 If the communication has been interrupted, the time will start to count down to 0 and the connection will be automatically disconnected. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 26 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 27: Account Management

    English or symbols with a maximum length of 12 characters. Enter the new password again, which must be the same as Retype New Password the new password. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 27 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 28: Time Setting

    User-defined time The date and time set by the user will be written to the module after clicking the Save button. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 28 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 29: Communication Interface

    2.5. Communication interface MDC-211-433 provides a Wireless, Ethernet, RS-232 and RS-485 communication interface. The relevant parameters and settings of these communication interfaces in the Module Setting tab will be introduced later. 2.5.1. Module Setting – Interface Setting The Module Setting tab contains three sections: Interface Setting, Protocol Setting and Other.
  • Page 30 (Note) The three wireless parameters including RF Channel, Group ID and RF Rate must be the same as other 433MHz modules to enable communication. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 30 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 31: Ethernet

    Gateway The module’s communication gateway address, the default value is 192.168.0.1. Web Server Port Fixed 80. Modbus TCP Port Fixed 502. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 31 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 32: Serial Port

    (or byte) of the data. Confirm whether new characters are received. If no new characters are received after this waiting time and it ICP DAS, MDC-211-433 User Manual Version 1.0 Page 32 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 33 3.5 characters, the interval between characters only needs to exceed 3.5 milliseconds, the module will determine that the data has been received and then start parsing the data. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 33 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 34: Communication Protocols And Modes

    2.6. Communication protocols and modes MDC-211-433 supports Modbus RTU or Modbus TCP communication protocols according to the communication interface. The communication interfaces that support Modbus RTU are Wireless, RS-232 and RS-485, and the communication interface that supports Modbus TCP is Ethernet.
  • Page 35: Module Setting - Protocol Setting

    1 second. In addition, if you want to give up the modification, you can click the Cancel button and leave the modification page. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 35 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 36 (Note 1) The wireless timeout time is related to the wireless communication baud rate (RF Rate) and data length. Please refer to the table below for recommended values. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 36 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 37 128 bytes 2 bytes (bps) timeout (ms) timeout (ms) 57600 38400 19200 9600 1500 4800 3000 2400 6000 1200 12000 23000 ICP DAS, MDC-211-433 User Manual Version 1.0 Page 37 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 38: Set The External Slave Device To Be Polled By The Master Station

    Modify the icon of the polling command. After clicking, the web page will pop up the Slave Device Configurations window. Delete all polling command icons for this slave station. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 38 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 39 The starting address to be read by Modbus, Base 0 is used here, the value Start addr. range is 0~65535, and the default value is 0. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 39 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 40 Delete all polling command icons for this slave station. Add icons for command content, and up to 250 commands can be added. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 40 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 41: Set The Module Slave Station Number

    Parameter name Description ID (Dec) Slave station number, the value range is 1~255, and the default value is 1. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 41 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 42: The Data Corresponding Address And Polling Status Of The Slave Device

    I/O channel status of the external slave device. The relevant parameters of these functions in the I/O Information tab will be introduced later. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 42 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 43: I/O Information - Internal Register

    0~4294967295. (Note) Modbus commands can be used to read the polling time. Please refer to the Modbus Table in Section 2.10. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 43 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 44 The CRC 16 check code of the slave station responding to this command is incorrect, indicating that the communication process may be subject to abnormal interference. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 44 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 45 MDC address has been reassigned and is different from the original one. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 45 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 46 ICP DAS, MDC-211-433 User Manual Version 1.0 Page 46 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 47: I/O Information - I/O Channel Status

    IO status information will be displayed on the right. Each parameter is explained in the table below. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 47 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 48 Analog Output Setting window will pop up. After entering the value and clicking the OK button, the module will write the AO value to the external slave. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 48 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 49: Wireless Signal Strength

    -84 ~ -72 120 ~ 159 -71 ~ -53 160 ~ 199 -52 ~ -35 200 ~ 255 -34 ~ -9 ICP DAS, MDC-211-433 User Manual Version 1.0 Page 49 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 50: Import, Export And Restore Default Values Of Parameters

    CSV file when using the module for the first time, who can export this file from the module first. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 50 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 51 In addition, each parameter is separated by ",", and the mark "*" indicates that this parameter is enabled, and the mark "-" indicates that this parameter is not enabled. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 51 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 52: Wireless Section

    The subnet mask of the module. The default value is 255.255.0.0. Gateway The module’s communication gateway address, the default value is 192.168.0.1. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 52 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 53: Serialport Section

    3.5 characters, the interval between characters only needs to exceed 3.5 milliseconds, the module will determine that the data has been received, and then start parsing the data. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 53 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 54: Modbus Section

    If the slave station does not respond after this time, it will be judged as a timeout. The ICP DAS, MDC-211-433 User Manual Version 1.0 Page 54 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 55 128 bytes 2 bytes (bps) timeout (ms) timeout (ms) 57600 38400 19200 9600 1500 4800 3000 2400 6000 1200 12000 23000 ICP DAS, MDC-211-433 User Manual Version 1.0 Page 55 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 56: Modbusslavedevice Section

    The number of data to be read by Modbus, the value range is 1~64, and RegCount the default value is 4. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 56 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 57: Default/Reboot

    It means the account/password to log in to the module web page. Account/Password (Note) Checking this option will restore the account/password to admin. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 57 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 58: Modbus Table

    0~255, where the value 0 means that this correspond to a maximum of address is not used. 250 commands. [Low byte] ICP DAS, MDC-211-433 User Manual Version 1.0 Page 58 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 59 R, W Uint32 0xFFFFFFF Wireless polling time Min。 Value 0xFFFFFFFF: Not used or to be 49865 (0x2689) (Low word, 0xHiLo) updated. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 59 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 60 RS-485 polling time Now。 (Note) Writing 0 clears the Wireless 49875 (0x2693) (Low word, 0xHiLo) polling time Max, Now and Min. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 60 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 61 Modbus TCP connection Value range: 0~65535, unit: second. 49900 (0xC2EC) 3, 6 R, W Uint16 timeout time. Value 0: Restore default value. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 61 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 62: Faq (Questions And Answers)

    MDC-211-433? A1: Up to 250 Modbus commands can be defined, and each command can set up to 64 register addresses. MDC-211-433 has four data tables of DI/DO/AI/AO. Each data table can store up to 9600 temporary register data.
  • Page 63: Address Of The Mdc-211-433

    RS-485 Modbus RTU RFU-433 M-7026 Wireless Modbus RTU Modbus TCP RS-485 Modbus RTU Ethernet M-7017 I-7520 RS-232 Modbus RTU M-7024 RS-485 ICP DAS, MDC-211-433 User Manual Version 1.0 Page 63 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 64: Q4 - How To Control The Output Channel Of Modbus Rtu Device

    Modbus command code 06 (0x06) or 16 (0x10) to write to addresses 40004~40007. Modbus RTU Modbus TCP RS-485 Ethernet M-7024 MDC-211-433 (ID: 6) (ID: 1) ICP DAS, MDC-211-433 User Manual Version 1.0 Page 64 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 65 Modbus TCP [B5 FE 00 00 00 0F] 00 04 00 04 08 00 01 00 02 00 0A 00 0B ICP DAS, MDC-211-433 User Manual Version 1.0 Page 65 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...
  • Page 66: Q5 - How To Read The Connection Status Of Each Command Through Modbus

    A6: Please refer to the operation and update steps in Section 2.1.3, first let the module into firmware update mode, and then use the software tool (Windows version) to update the firmware through Ethernet. ICP DAS, MDC-211-433 User Manual Version 1.0 Page 66 Copyright © 2024 ICP DAS Co., Ltd. All Rights Reserved...