EPH Controls RFC V2 Installation And Operation Manual page 22

Rf cylinder thermostat with boost button
Table of Contents

Advertisement

P0 2 Hysteresis
This menu allows the installer to change the hysteresis of the
thermostat when the temperature is rising and falling.
If HOn is set to 5˚C, this will allow a temperature drop of 5˚C below
the target temperature, before the thermostat turns on again.
If HOFF is set to 0.0˚C, this will allow the temperature to rise 0˚C
above the target temperature before the thermostat turns o .
To access this setting press and hold
seconds. 'P01' will appear on the screen.
Rotate
clockwise until 'P02 & HOn' appears on the screen.
Press
to select. Use
to con rm. 'HOFF' appears on the screen. Use
Press
select the 'HOFF' temperature, press
be saved and the user will be returned to the previous screen.
Press
to return to normal operation.
Boost
20
HOn 5°C HOFF 0.0°C
&
to select the 'HOn' temperature,
to con rm. The settings will
RFC
V2
together for 5
Boost
to

Advertisement

Table of Contents
loading