DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL AHRI Data The performance standard AHRI/ASHRAE/ISO 13256-1 became effective January 1, 2000 and replaces ARI Standards 320, 325, and 330. This new standard has three major categories: Water Loop (comparable to ARI 320), Ground Water (ARI 325), and Ground Loop (ARI 330).
Page 6
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL AHRI Data Variable Speed ECM motor AHRI/ASHRAE/ISO 13256-1 English (IP) Units Ground Water Heat Pump Ground Loop Heat Pump Flow Rate Cooling Brine Heating Brine Cooling Heating Full Load 77°F Full Load 32°F EWT 59°F EWT 50°F Model...
Page 7
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL AHRI Data cont. Energy Star Compliance Table Energy Star Rating Criteria In order for water-source heat pumps to be Energy Star rated they must Tier 3 meet or exceed the minimum efficiency requirements listed below. Tier Model 3 represents the current minimum efficiency water source heat pumps Ground Water...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Dimensional Data Top Air Discharge LEFT RETURN RIGHT RETURN 1.9in [4.8cm] 1.9in [4.8cm] K J I D E H F FRONT 2ft [61cm] Primary Service Access RIGHT SIDE LEFT SIDE Electrical Return Connection Connections Discharge Connection...
Page 10
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Dimensional Data cont. Bottom Air Discharge RIGHT RETURN LEFT RETURN 1.70 (4.3 cm) LEFT SIDE RIGHT SIDE 1.90 (4.7 cm) FRONT 2ft [61cm] Primary Service Access LEFT BOTTOM DISCHARGE RIGHT BOTTOM DISCHARGE FLOOR FOOT PRINT FLOOR FOOT PRINT Electrical...
Page 11
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Dimensional Data cont. TOP VIEW 2.1in [5.4cm] MOUNT (2) HANGER BRACKETS AS SHOWN TO ALLOW ACCESS TO FILTER 2ft [61cm] Primary Service Access FRONT VIEW SIDE DISHCARGE VIEW END VIEW 1.9in [4.8cm] D E F G K J I...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Electrical Data Dual Capacity Unit with Variable Speed ECM Motor Blower Total Compressor Rated Voltage Pump Loop Motor Unit Circ Fuse/ Model Voltage Min/Max LRA* HACR 208-230/60/1 187/253 15.0 52.0 18.2 19.4 21.8 208-230/60/1...
Antifreeze solution is Propylene Glycol 20% by weight. Determine the corrected heating and cooling performance at 30°F and 90°F respectively as well as pressure drop at 30°F for a 5 Series 024-ECM. The corrected cooling capacity at 90°F would be: 22,900 MBtu/h x 0.969 = 22,190 MBtu/h The corrected heating capacity at 30°F would be: 18,900 MBtu/h x 0.913 = 17,255 MBtu/h...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Correction Factor Tables Air Flow Corrections (Dual Capacity Part Load) Airflow Cooling Heating cfm Per Ton % of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext of Clg 0.922 0.778...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Water Quality Material Copper 90/10 Cupronickel 316 Stainless Steel Acidity/Alkalinity 7 - 9 7 - 9 7 - 9 Calcium and (Total Hardness) (Total Hardness) (Total Hardness) Scaling Magnesium Carbonate less than 350 ppm less than 350 ppm less than 350 ppm Less than 0.5 ppm (rotten egg...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Operating Parameters Dual Capacity Models First Stage Operation Cooling -- No Hot Water Generation Entering Water Water Flow gpm/ Suction Pressure Discharge Pressure Water Temp Air Temp Drop °F Temp °F Superheat Subcooling psig...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Pressure Drop Dual Capacity Pressure Drop Pressure Drop (psi) Pressure Drop (psi) Model Model 30°F 50°F 70°F 90°F 110°F 30°F 50°F 70°F 90°F 110°F full load full load part load part load full load full load part load...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Operation Logic Data Table Heating Cooling Operation Logic Table STG1 STG2 STG3 EMERG Fan Only STG1 STG2 Fan Only Compressor Reversing Valve Staged Staged Aux Heat Acc Relay High High High High ECM Speed T-Stat Signal...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System Aurora ‘Base’ Control Aurora ‘Advanced’ Control The Aurora ‘Advanced’ The Aurora ‘Base’ Control Control expands on the (ABC) System is a complete capability of the Aurora residential and commercial ‘Base’...
Page 24
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System Service Device Description Aurora 'Advanced' Allows setup, monitoring and troubleshooting of any Aurora Control. For Service NOTE: Although the ABC has basic compatibility with all Aurora, new product features (Ver.
Page 25
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System Aurora ‘Base’ Control Field Selectable Options via Hardware DIP Switch (SW1) – Test/Configuration Button (See SW1 Operation Table) Test Mode The control is placed in the test mode by holding the push button switch SW1 for 2 - 5 seconds.
Page 26
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System Cycle with Blower - The accessory relay will cycle with Lockout – when locked out, the blower will operate the blower output. continuously in “G” speed, and PSC blower motor output will remain on.
Page 27
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System Over/Under Voltage Shutdown - An over/under voltage Cooling Operation condition exists when the control voltage is outside the In all cooling operations, the reversing valve directly tracks range of 18 VAC to 30 VAC. If the over/under voltage the O input.
Page 28
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System cycle. Since compressor hot gas temperature is dependent Aurora ‘Advanced’ Control Features Control Features on loop temperature in cooling mode, loop temperatures may The Aurora ‘Advanced’ be too low to allow proper heating of water. The control will Control system expands on monitor water and refrigerant temperatures to determine if the capability of the Aurora...
Page 29
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System Aurora ‘Base’ Control LED Displays ASB Sensor Board These three LEDs display the status, configuration, and Refrigerant Leak Detection fault codes for the control. These can also be read in plain The Aurora control system uses the ASB control board to English via the Aurora AID Tool.
Page 30
REQUIRES WaterFurnace dealer login The AID Tool will allow configuration of this input for the action credentials SCC is for WaterFurnace dealer technicians ONLY and includes: • No Action •...
Page 31
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System Home Automation 1 - E23 HA1 Dual Capacity Power Adjustment With a closed dry contact signal, this input will cause an alarm Voltage and Alert Code 23 to indicate on the stat or flash on ABC. The AID Model Unit Capacity Tool will allow configuration of this input between the following...
Page 32
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System The Aurora Unitary Protocol Converter (UPC) Aurora Control The Aurora UPC is implemented with is an integrated solution and communicates w/UPC BACnet the Aurora Base Controller (ABC) heat directly with the Aurora Heat Pump Controls pump control into our latest water and allows access/control of a variety of internal...
Page 33
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System Aurora ‘Advanced’ Control LED Displays These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool. Status LED (LED3, Green) Description of Operation Fault LED, Green...
Page 34
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System entire length of the appropriate delay to be recognized as a Aurora now expands the Fault/Alarms in to several groups. fault. This fault will be ignored for the initial 2 minutes of the Faults are system critical faults to the heat pump and will compressor run time.
Page 35
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Control System E82, ASB Sensor Problem - The gas sensor has lost communi- Aurora Alarm Codes cation with the ASB board or has an internal error. These alarms are planned to alert the homeowner and the ser- vice personnel but will NOT effect system operation and are E97, Invalid System Configuration - ABC has not been config- for information only.
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Refrigerant Circuit Guideline Head Suction Compressor Air Temp. Water Temp. Symptom Superheat Subcooling Pressure Pressure Amp Draw Differential Differential Under Charged System High (Possible Leak) Over Charged System High High High Normal High Normal/Low...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Electrical Information 208 Volt Operation General All 208/230 units are factory wired for 230 volt operation. For Be sure the available power is the same voltage and phase 208 volt operation, the red and blue transformer wires must as that shown on the unit serial plate.
Page 38
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Electrical Information Figure 13A: Figure 13B: Wire access (control box open) Wire access (control box closed) Ground Fastener Wire Insert must be installed for Location proper unit ground Figure 13C: Line Voltage 208-230/60/1 control box T1 T2 (018) (036-072)
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Electrical Information cont. Figure 14: Pump Wiring 208-230/60/1 Wire Nuts Optional External Variable Speed Loop Pump 208-230/60/1 External Loop Pump(s) 208-230/60/1 1/2 hp Max Electronic Thermostat Installation Position the thermostat subbase against the wall so that Figure 21: Thermostat Wiring (Y1 Style Signals) it is level and the thermostat wires protrude through the middle of the subbase.
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Electrical Information - Flow Centers Fixed Speed Flow Center The pump(s) will be connected to the terminals on PB1 in the unit electrical box as shown in Figure 15. The pumps will automatically be cycled as required by the unit or by a signal from another unit sharing the flow center (See Figures 5 and 6).
Page 41
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Electrical Information - Flow Centers cont. Variable Speed Flow Center Single Pump Variable Speed Flow Center If a variable speed single pump flow center is used, the flow center will come with two red and one green wires for the high voltage wiring.
Page 42
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Electrical Information - Flow Centers cont. Variable Speed Flow Center cont. Two Pump Variable Speed Flow Center If a variable speed two pump flow center is used, the flow center will come with four red and two green wires for the high voltage wiring.
5 Series Units Envision Units Electromechanical Units Auxiliary Heat ® GeoLink Supply Polyethylene w/ LOOP 5 Series Unit #1 5 Series Unit #1 5 Series Unit #1 ® Armaflex Unit Supply with AXB Board with AXB Board with AXB Board...
Page 44
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Open Loop Ground Water Systems Variable Speed Pump Setup Figure 9b: Open Loop Solenoid Valve Connection Option When using a variable speed pump flow center (FCV1- Typical slow operating external 24V water solenoid valve GL or FCV2-GL) the use of an AID Tool will be necessary (type V100FPT) wiring.
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Reference Calculations Heating Calculations: Cooling Calculations: LWT = EWT - LWT = EWT + GPM x 500* GPM x 500* NOTE: * When using water. Legend Abbreviations and Definitions EWT = Entering Water Temperature HWR = Hot Water Return EER = Energy Efficiency Ratio (TC/kW) HWS = Hot Water Supply...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Preventative Maintenance Proper maintenance is very important to obtain optimum Condensate Drain performance and longevity for the heat pump system. It is In areas where airborne bacteria produce a slime in the best to establish a periodic maintenance schedule with the drain pan, it may be necessary to treat chemically to installer so the heat pump system can be checked regularly.
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Troubleshooting Aurora Control System Refrigerant Systems To maintain sealed circuit integrity, do not install service NOTE: Refer to the Aurora Base Control Application and gauges unless unit operation appears abnormal. Compare Troubleshooting Guide and the Instruction Guide: Aurora the change in temperature on the air side as well as the Interface and Diagnostics (AID) Tool for additional information.
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Aurora Interface Diagnostic (AID) Tool Aurora Input-Output Diagnostics LED Displays Slow Flash = 1 second on and 1 second off Troubleshooting the Aurora logic board Fast Flash = 100 ms on and 100 ms off can be accomplished using nothing more Flash Code = 100 ms on and 400 ms off with a 2 second pause than a couple of jumper wires and a volt...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Troubleshooting Checklist • Return air temperature may be below 50°F. Block off air coil Equipment will not start or operate temporarily to improve flow of refrigerant through the system. Air • Follow the troubleshooting flow charts to find root cause. below 50°F cannot be tolerated on a continuing basis.
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Steps 1) General Check Other items to check when troubleshooting a water flow lockout • If any new device was installed, or any wiring was changed, are superheat, water flow through the coaxial heat exchanger and check the connections to ensure the wiring is correct, and all the antifreeze composition.
Page 52
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Steps cont. No Lockout Output – Measure the voltage output between 4) Other Faults P1-1 and C. The reading should be 24 VDC or a pulsed 24 VDC ECM Motor Will Not Start dependent on the selection of SW2-7.
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL CONTROL BOARD FLOW CHARTS...
Page 54
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts Use the following flow charts to aid in troubleshooting the control board. Compressor Will Not Start Without AID Tool Compressor will not start Count the number of Is LED3 (green) lit Is LED1 (red) flashes and compare to...
Page 55
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. Put control into test Check 24VAC Check 24VAC Check for correct Check Compressor mode, and wait 1 between CC and across contactor...
Page 56
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. Compressor Will Not Start With AID Tool Compressor will not start Check current fault. Connect the AID Is the control in Correct fault and try to Tool Lockout? restart.
Page 57
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. Check 24VAC Check 24VAC Check for correct Check Compressor In “System between CC and across contactor voltage on T1 and wiring, winding...
Page 58
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. ECM Blower Will Not Start Without AID Tool Blower will not start Check for correct voltage Remove P1 and place a Put control into test Is LED3 (green) Lit between orange and jumper between R and...
Page 59
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. There is a problem Does the blower with the thermostat or start thermostat wiring Check 24VAC Is the DC voltage on P13-1...
Page 60
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. ECM Blower Will Not Start With AID Tool Blower will not start Check for correct voltage Connect AID Tool. Put control in test Is LED3 (green) Lit between orange and Remove P1 and put a mode and wait 1...
Page 61
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. Put control into test Check 24VAC Check 24VAC Check for correct Check Compressor mode, and wait 1 between CC and across contactor...
Page 62
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. Loop Pump Will Not Start Variable Speed Pump Loop Pump will not start Check pump wiring to Is AXB LED1 Is AXB LED1 AXB. Check (Green) Flashing flashing fast? communication wiring...
Page 63
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. 2. When measuring 240VAC actual value may be between 190 and 250 VAC. Check 240 VAC Did the loop pump Is voltage on VS PMP...
Page 64
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. Loop Pump Will Not Start Non Variable Speed Pump Loop Pump will not start Check pump wiring to Is AXB LED1 Is AXB LED1 AXB. Check (Green) Flashing flashing fast? communication wiring...
Page 65
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Troubleshooting Flow Charts cont. Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. 2. When measuring 240VAC actual value may be between 190 and 250 VAC. Check for 240 VAC Check 240 VAC Did the loop pump...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Communicating Thermostat Troubleshooting Guide TPCC32U01*, TPCM32U03A* and TPCM32U04A* (*GSR, GSM, E, YRK) Thermostat not communicating Wire non- Are you using a communicating 8 Is this a variable communicating wire thermostat speed unit? thermostat? to P1 terminal on the ABC board...
Page 67
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Communicating Thermostat Troubleshooting Guide cont. Are all Remove what is applicable not needed or add devices present what is needed. Is Issue resolved on Configure the thermostat Aurora System communicating? screen TPCM32U03A*/TPCM32U04A* Thermostat P7 on ABC Board...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Signals To Check for 24VAC between R and C a signal and the contactor is not pulled in, check voltage across the contactor coil. If you have voltage across the contractor coil, replace the contactor.
Page 69
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Signals cont. To Check Operation of the Accessory Relay Put gauges on the unit to monitor high/low pressure. Place a jumper between “R” and “CC” as shown. This will bypass the safety circuit and the compressor will run whether the board is calling for it or not.
Page 70
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Control Board Signals cont. To Check the Condensate Sensor To Check the ECM Blower Motor Enable Signal 24 VAC VOLTS VOLTS OHMS With the AID Tool go to the “Thermostat Inputs” Menu under “Diagnostics”...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Jumping the Control Board Stage 1 Heating Stage 2 Heating With the AID Tool go to the “Thermostat Inputs” Menu under With the AID Tool go to the “Thermostat Inputs” Menu under “Diagnostics”...
Page 72
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Jumping the Control Board cont. Emergency Heat Stage 1 Cooling With the AID Tool go to the “Thermostat Inputs” Menu under With the AID Tool go to the “Thermostat Inputs” Menu under “Diagnostics”...
Page 73
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Jumping the Control Board cont. Reheat Mode With the AID Tool go to the “Thermostat Inputs” Menu under “Diagnostics” and over-ride the “DH” input to ON. If an AID Tool is not available remove the P1 connector to disconnect the thermostat from the board.
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Water Side Analysis: Heat of Extraction/Rejection By determining the amount of heat extracted or rejected, the ∆P = 40 psi – 34.2 psi service technician can better judge the performance of the unit and ∆P = 5.8 psi verify whether or not the unit performance is acceptable.
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Superheat/Subcooling Checking Superheat in the Heating Mode Superheat = Suction line temperature minus suction saturation temperature Digital Thermometer Suction COIL Comp Expansion Coax Discharge Valve Hot Water Generator Checking Superheat in the Cooling Mode Superheat = Suction line temperature minus suction saturation temperature Digital...
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Troubleshooting...
Page 77
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Troubleshooting cont. Startup/ roubleshooting Form Controls Info: Dealer: ABC Version: Phone #: Date: AXB Version: IZ2 Version: Problem: T-Stat Version: Model #: Installed Sensors: Serial #: COOLING CYCLE ANALYSIS SAT °F °F Unit Amp Draw: Loop:...
Page 78
DUAL CAPACITY PACKAGED HEAT PUMP OPERATING AND MAINTENANCE MANUAL Troubleshooting cont. Single Speed/Dual Capacity Startup/Troubleshooting Form 1. Job Information Model # Job Name: Loop: Open / Closed Serial # Install Date: Hot Water Generator: Y / N 2. Flow Rate in gpm SOURCE COAX LOAD COAX (Water-to-Water) HEATING...