WaterFurnace TruClimate 300 Installation Manual

WaterFurnace TruClimate 300 Installation Manual

Formerly wc hybrex chiller commercial 60 hz water-cooled chiller with hybrex technology • r-410a refrigerant • 30-50 tons
Hide thumbs Also See for TruClimate 300:

Advertisement

Quick Links

Formerly WC HybrEx Chiller
Commercial 60 Hz
Water-Cooled Chiller with HybrEx Technology
• R-410A Refrigerant
• 30-50 Tons
Installation Information
Water Piping Connections
Electrical Data
Microprocessor Control
Startup Procedures
Preventive Maintenance
IM1910WW 01/22

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TruClimate 300 and is the answer not in the manual?

Questions and answers

Summary of Contents for WaterFurnace TruClimate 300

  • Page 1 Formerly WC HybrEx Chiller Commercial 60 Hz Water-Cooled Chiller with HybrEx Technology • R-410A Refrigerant • 30-50 Tons Installation Information Water Piping Connections Electrical Data Microprocessor Control Startup Procedures Preventive Maintenance IM1910WW 01/22...
  • Page 3: Table Of Contents

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Table of Contents General Installation Information ........... . 4 Nomenclature .
  • Page 4: General Installation Information

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller General Installation Information Safety Considerations Unit Location Installing and servicing air conditioning and heating Provide sufficient room to make water and electrical equipment can be hazardous due to system pressure and connections.
  • Page 5: Nomenclature

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Model Nomenclature WCXDM030A3AABS3S6GC100NSSS 17 - 19 24-26 Non-Standard Options Brand SSS – None W – WaterFurnace Future Option Model Type N – Not Applicable CX – Coax Chiller Cooling Only...
  • Page 6 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Single Point Disconnect Panel Nomenclature SPLD4030L410* Vintage * – Factory Use Only Model SP – Single Point Disconnect Panel Future Use 0 – Future Use...
  • Page 7 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Temperature Header Nomenclature Accessory Options Model N – None B – Bypass Header T – Temperature Header Revision 03 – Current Revision Pipe Diameter 6 – 6"...
  • Page 8: Unit And Accessory Nameplates

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Unit and Accessory Nameplates Unit Nameplate Model: S/N: Job #: Electrical Service Current (Amps) Minimum Circuit Amp (MCA) Unit Volts Frequency Min/Max Volts Phase Compressor (ea)
  • Page 9: The Wc Hybrex Chiller

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller The WC HybrEx Chiller The WC HybrEx Chiller is a cooling only scroll chiller utilizing R-410A refrigerant, brazed plate evaporator, electronic expansion valve and coax condenser. The unit is designed with intent of installing multiple units in parallel and creating a larger chiller system with a single point of control, single electrical power supply and single point water hookup.
  • Page 10: The Wc Hybrex Chiller Features

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller The WC HybrEx Chiller Features Unit Features Heavy gauge Heavy gauge insulated sheet insulated sheet metal cabinet metal cabinet Removable Removable to reduce noise to reduce noise...
  • Page 11 The WC HybrEx Chiller Features cont. The True "Modular" Concept Most modular chillers can be ganged together but once in place cannot be easily serviced or removed. Waterfurnace HybrEx modular chillers feature several industry fi rsts to provide a true modular chiller! Majority of servicing can be accomplished from front (control box) of unit.
  • Page 12 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller The WC HybrEx Chiller Features cont. Header Rack Full Access to evaporator with Minimum Disassembly Optional Factory Installed 40 Mesh Evaporator Optional Factory Installed 0.045perf...
  • Page 13: Physical Data

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Physical Data Fixed Speed VS Modular Fixed Speed VS Modular Model 050 Ton 050 Ton 030 Ton 030 Ton R-410A Refrigerant R-410A Number of Circuits 23.75 [10.7]...
  • Page 14: Electrical Data, Voltage Availability, Compressor Resistance

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Electrical Data Total Compressor* Rated Voltage Unit Circ Fuse/ Model Voltage Min/Max HACR 208-230/60/3 187/253 75.0 48.1 351.0 96.2 108.2 30Ton Fixed Speed 460/60/3 414/506 38.6...
  • Page 15: Dimensional Data

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Dimensional Data - 30 Ton Single Module Power Inlet 2" 7" 4" 28" 11" CHILLED WATER OUTLET CHILLED WATER 10.50" INLET 10.50" CONDENSER WATER OUTLET 72"...
  • Page 16 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Dimensional Data - 30 Ton Bank of Units REQUIRED TEMPERATURE HEADER LEFT OR RIGHT CONFIGURATION 9" 8" OPTIONAL SINGLE POINT PANEL RIGHT INSTALLATION SHOWN 55"...
  • Page 17 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Dimensional Data - 50 Ton Single Module WCXDM050 TON DIMENSIONAL DATA Power Inlet 2.00 7.00 3.54 33.00 10.50 CHILLED WATER OUTLET CHILLED WATER 10.50 INLET 10.50...
  • Page 18 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Dimensional Data - 50 Ton Single Module Service Clearance SERVICE CLEARANCE 30.00 15.57 40.00 20.00...
  • Page 19 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Dimensional Data - 50 Ton Bank of Units 5" OPTIONAL STRAINER REQUIRED TEMPERATURE HEADER LEFT OR RIGHT CONFIGURATION 9" 64" OPTIONAL 1626 SINGLE POINT PANEL (RIGHT...
  • Page 20 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Dimensional Data - Temperature Header TEMPERATURE WEATHER SCH 40 CARBON STEEL PIPE WATER TEMP SENSOR TYPE II WATER PRESSURE CUT GROOVE SENSOR (OPTIONAL) PER VIC 25.01 REV J 1/2"...
  • Page 21 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Dimensional Data - Strainer PLUGGED ACCESSORY PORTS 16.0 ANSI 125 FLANGE 2.5" GROOVE PIPE FITTING 2.5" GROOVE PIPE FITTING 6.5 INCH CLEARANCE REQUIRED FOR BASKET REMOVAL DRAIN/BLOW-OFF PLUG Strainer Specifi...
  • Page 22 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Dimensional Data - Service Requirements...
  • Page 23: Pressure Drop

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Pressure Drop - Unit...
  • Page 24 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Strainer Pressure Drop (New Basket)
  • Page 25: Operating Limits

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Operating Limits The operational limits of the chiller are presented based on leaving water temperature for the condenser and evaporator (See Leaving Water Temperature Operational Maps).
  • Page 26: Leaving Water Temperature Operational Maps

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Leaving Water Temperature Operational Maps...
  • Page 27: Hpc And Mop Entering Water Temperature Limits

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller HPC and MOP Entering Water Temperature Limits Minimum Flow During Head Pressure Control (HPC) and Maximum Evaporator Pressure Control (MOP). During HPC and MOP operation, the valves are modulated to keep the compressor running within the operation limits. Dur- ing the modulation, the valve can close to 40%.
  • Page 28: Chiller Components

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Components Chiller Components Flow Switch The following section summarizes the major component All chillers come standard with used in the system. All major components are shown in a 30 a fl...
  • Page 29: Detailed Component Callouts

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Detailed Component Callouts - Cabinet Removed Compressor Brazed Plate Evaporator Coax Condenser Isolation valve Motorized Isolation valve Isolation valve Motorized Isolation valve Filter Drier Electronic...
  • Page 30 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Detailed Component Callouts - Full Assembly EP19-012IMF5 6IN Grooved Headers VFD VENT OPENING Unit Power Feed Warning Label Unit Serial Plate Removable High Volt Panel...
  • Page 31: Electrical System And Controls

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Electrical System and Controls Unit Fuses General (Fused Disconnect Only) Detailed overview of high volt panel, low volt panel and the controls platform is provided in this section. The Hybrid UL Class J fuses.
  • Page 32 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Electrical System and Controls cont. High Voltage Panels Overview VARIABLE SPEED DRIVE POWER BLOCKS (OPTIONAL FUSED OR NON-FUSED DISCONNECT) UNIT GROUND OPTIONAL INTERFACE (PRIMARY UNIT ONLY)
  • Page 33: Aurora Hydrolink2 Chiller Control System

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Aurora HydroLink2 Chiller Control System HydroLink2 Controller HybrEx Supervisory Controller The HybrEx Supervisory Controller is a Niagara4 control that functions as a master control communicating to each HydroLink2 unit controller.
  • Page 34 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller HydroLink2 Aurora Chiller Controls cont. Operation Description Other Modes of Operation Power Up - The unit will not operate until all the inputs and Emergency Shutdown - Four (4) seconds after a valid ES input or communicated signal, P2-7 is present, all control safety controls are checked for normal conditions.
  • Page 35 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller HydroLink2 Aurora Chiller Controls cont. HybrEx Supervisory Controller in BAS The HydroLink2 Aurora is programmed using the powerful Niagara language.. This will allow for a BAS to integrate and...
  • Page 36 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller HydroLink2 Aurora Chiller Controls cont. Fault, Configuration and Status Codes Fault Reset/ Fault Flash Lockout Fault Condition Summary Code Remove Code * Normal - No Faults...
  • Page 37 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller HydroLink2 Aurora Chiller Controls cont. Field Relay 7 and 8 – This shows the state of the Field Relay 7 Other User Defined Field I/O and 8 on AXB A and B (labeled K6).
  • Page 38 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Aurora HydroLink2 Chiller Control System cont. Chiller Sys Interface Ethernet Switch Primary HL2 HybrEx Supervisory Controller Controller BACnet Secondary HL2 Secondary HL2 Controller Controller Secondary...
  • Page 39 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Aurora HydroLink2 Chiller Control System cont. Control Panel Overview Quick Disconnect Harness to High Volt Panel AXB-A AXB-B Quick Disconnect Harness to Unit Sensors ABC - B...
  • Page 40: Wiring Schematics

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Wiring Schematics Fixed Speed High Voltage - 30 Ton...
  • Page 41 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Wiring Schematics cont. Variable Speed High Voltage - 30 Ton...
  • Page 42 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Wiring Schematics cont. Fixed Speed High Voltage - 50 Ton...
  • Page 43 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Wiring Schematics cont. Variable Speed High Voltage - 50 Ton...
  • Page 44 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Wiring Schematics cont. ABC and AXB Controllers Status Status Status Status Modbus Add. ID Modbus Add. ID Modbus Add. ID Modbus Add. ID Future Use...
  • Page 45 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Wiring Schematics cont. HydroLink Controllers NET+ NET- NET+ NET-...
  • Page 46: Single Point Disconnect Panel Accessories

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Single Point Disconnect Panel Accessories HAZARDOUS VOLTAGE! Disconnect power before performing any work in the high-volt panel. Failure to disconnect power before servicing could result in death or serious injury.
  • Page 47 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Single Point Disconnect Panel Accessories cont. Mixed Bank of 50Ton Hybrex Chiller Single Point Panel Uniform Bank 50Ton Hybrex Chiller Variable Speed Fixed Speed Panel Information...
  • Page 48 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Single Point Disconnect Panel Accessories cont. Single Point Disconnect Panel...
  • Page 49: Refrigerant And Water Circuit Overview

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Refrigerant and Water Circuit Overview Each Chiller is equipped with two independent circuits. Each circuit can operate independently. Both circuits are controlled from dedicated controllers, thermistors and transducers, so in case of a controller or sensor failure, the system retains the ability to operate even with one circuit.
  • Page 50 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Refrigerant and Water Circuit Overview cont. Source Inlet Header Source Inlet Header Sour Sour Source Inlet Header urce urce nlet nlet eade eade Source Outlet Header...
  • Page 51: Application Requirements

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Application Requirements Heat Exchangers The Condenser and Evaporator heat exchangers utilize a single wall design. Do not install use for potable water ap- plications without intermediate heat exchanger.
  • Page 52: Chiller Installation

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Installation General Recommendations: Unit Storage and Environmental Requirements • It is recommended to install the chiller plant on a set NOTE: The chiller must be stored in dry location. Failure to...
  • Page 53 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Installation cont. Installation Procedure Chiller Plants with Single Point Disconnect Panel: 1. Installation of banks with single point disconnect panel requires the units to be installed in sequence order based on the label provided in the high volt panel.
  • Page 54 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Installation cont. C. Right and Left Single Point Panel When installing a chiller plant with two single point panels, one will be attached to the primary unit (always labelled as chiller 1), and the second panel will be attached to a secondary unit.
  • Page 55 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Installation cont. MOUNTING HOLE 10.04 0.88 18.02 LOCATION FRONT 0.88 MOUNTING HOLE 10.04 18.02 LOCATION REAR...
  • Page 56 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Installation cont. Water Connections The two available fl ow confi gurations are Reverse Return and Direct Flow. The Reverse Return confi guration provides Water Piping must be installed in accordance with applica- better fl...
  • Page 57 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Installation cont. Temperature Header Installation Individual Unit Power Feed The chiller has knockout provision for 1.5 in electrical The chiller plant requires global temperature read- conduit.
  • Page 58: Chiller Plant With Single Point Disconnect Panel

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Plant with Single Point Disconnect Panel Wiring Procedures (Single Point Disconnect Options) Remove top panels from each chiller to gain clear access to the high volt wiring path between each chiller and the single point panel.
  • Page 59 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Plant with Single Point Disconnect Panel cont.
  • Page 60: Chiller Plant Controls Wiring

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Plant Controls Wiring Wiring Procedures • The differential pressure sensor pressure range need to match the DIP switch settings in the sensor controller. The adjustment can be made through the Primary Unit HMI.
  • Page 61: Operation & Connection, Reference Calculations, Legend And Chiller Plant Startup

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Operation and Connection Operation and Connection BACnet Connection With a DDC device the chiller may be controlled by a build- The BAS will land a single shielded twisted pair cable (22 ing management system.
  • Page 62 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Plant Startup Procedure (cont)
  • Page 63: Scroll Refrigeration Cycle Analysis

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Scroll Refrigeration Cycle Analysis PSIG = Condenser Discharge Filter Suction Drier Compressor Evaporator PSIG = Unit Amp Draw Entering Hot Water Line Voltage Entering Water Pressure...
  • Page 64: Chiller Maintenance

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Chiller Maintenance Once circulation time is completed, begin the fl ushing Quarterly Checks process. • Compressor oil levels Ensure that the pH levels are safe for discharge and •...
  • Page 65: Troubleshooting Form

    TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller WC Commercial Scroll Chiller Troubleshooting Form Company Name: _________________________________ Company Phone No: ______________________________ Technician Name: ________________________________ Date: __________________________________________ Model No: ______________________________________ Serial No:_______________________________________ Owner’s Name: __________________________________...
  • Page 66 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller Revision Guide Pages: Description: Date: Misc. Implemented new product name 12 Jan 2022 Misc. Added 50 Ton capacity 21 Sept 2021 Document Creation 20 Mar 2021...
  • Page 67 TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL - Formerly the WC Hybrex Chiller...
  • Page 68 30-50 Ton Document: Installation Manual IM1910WW 01/22 ©2022 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifi cations without notice.