OPERATION & MAINTENANCE Versatec 500 7-30 Ton OMV5-0005W 60HZ All Versatec 500 Series models are safety listed under UL 60335-2-40 through ETL, and performance listed with AHRI in accordance with ASHRAE/ANSI/AHRI/ISO Standard 13256-1.
Definition of Warnings and Symbols WARNING Indicates a situation that results in death or DANGER serious injury. WARNING: Before performing service or maintenance Indicates a situation that could result in WARNING operations on the system, turn off main power switches death or serious injury.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE General Installation Information NOTICE: Do not store or install units in corrosive environments No person carrying out work in relation to a REFRIGERATING or in locations subject to temperature or humidity extremes. SYSTEM which involves exposing any pipe work shall use any Corrosive conditions and high temperature or humidity can sources of ignition in such a manner that it may lead to the risk of...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE General Installation Information Installation Space Requirements WARNING Ventilated Area: ensure that the area is in the open or that it NOTE: Equipment with refrigerant charge less than 64 oz does is adequately ventilated before breaking into the system of not require have a minimum floor area requirement and does not conducting any hot work.
Nomenclatures Nomenclature: Versatec 500 Series Water-to-Air 7-30 Ton (V5) Drawing Number: 96D674-01 Rev: A V5AV120BD3*N5CTLAANN31NSSS 24-26 Brand Non-Standard Options V – WaterFurnace SSS – None Versatec Future Option Model N – Future 5 – 500 Series Air Coil Option Option Type 1 –...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Physical Data Dual Capacity Compressor and Fan Two Compressors and Fan Two Compressors and Two Fans Model Compressor Scroll (1 each) Scroll (2 each) Scroll (2 each) Factory Charge R454B, oz [kg] (each circuit), Vertical Factory Charge R454B, oz [kg] (each circuit), Horizontal...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Dimensional Data LEFT RETURN SHOWN "N" "J" "M" "B" 2' SERVICE ACCESS "L" "H" 2' SERVICE ACCESS TOP DISCHARGE 2' SERVICE ACCESS FIELD REMOVABLE BLOWER PANEL INSERT 1.00 "G" "L" "M" "N" BLOWER ACCESS PANEL...
Page 10
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Dimensional Data cont. "H" LEFT RETURN "F" END DISCHARGE SHOWN FIELD REMOVABLE BRACKETS AND DUCT FLANGES 2' SERVICE ACCESS DRAIN CONNECTION "J" "J" "K" "N" DUCT FLANGE "G" "L" 2' SERVICE ACCESS AIR COIL "M"...
Page 11
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Dimensional Data cont. V*240-360 240-360 RIGHT RETURN POWER SUPPLY RIGHT RETURN 16.88 LEFT RETURN SHOWN SHOWN 3.40 8.10 1.50 16.08 48.08 71.90 2' SERVICE ACCESS 2' SERVICE ACCESS 2' SERVICE ACCESS POWER SUPPLY 20.00 RIGHT RETURN 8.10 REF...
Page 12
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Dimensional Data cont. "H" L E F T R E T U R N "F" END DISCHARGE S H O W N FIELD REMOVABLE BRACKETS AND SIDE DISCHARGE DRAIN CONNECTIONS DUCT FLANGES FIELD REMOVABLE "J"...
Page 13
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Dimensional Data cont. "H" R I G H T R E T U R N END DISCHARGE S H O W N FIELD REMOVABLE BRACKETS AND DUCT FLANGES "J" SIDE DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES "J"...
Page 14
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Dimensional Data cont. U D V 0 8 4-1 8 0 T O P F L O W E C O N O M I Z E R O P T I O N L R "N"...
Page 15
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Dimensional Data cont. U D V 0 8 4-1 8 0 T O P F L O W E C O N O M I Z E R O P T I O N R R "N"...
Page 16
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Dimensional Data cont. U D V 2 4 0-3 6 0 POWER SUPPLY R I G H T R E T U R N 16.88 LEFT RETURN S H O W N 3.40 8.10 1.50...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Electrical Data WARNING WARNING Do not apply any permanent inductive or capacitance During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being loads to the circuit with out ensuring that this will not exceed the permissible voltage and current permitted for worked upon prior to any removal of sealed covers, etc.
Page 22
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Blower Performance Data cont. Setting Blower Speed - Variable Speed ECM ECM Speed Setup - These screens allow the technician to select the G, low, high, and auxiliary heat blower speed for The ABC board’s Yellow Config LED will flash the current the ECM blower motor.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Antifreeze Corrections Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given. Antifreeze Cooling Heating Antifreeze Type Pressure Drop % by wt Capacity Capacity EWT - degF [DegC] 90 [32.2] 30 [-1.1]...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Correction Factor Tables Air Flow Corrections (Part Load) Airflow Cooling Heating CFM Per Ton % of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext of Clg 0.922 0.778 0.956...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Water Quality Material Copper 90/10 Cupronickel 316 Stainless Steel Acidity/Alkalinity 7 - 9 7 - 9 7 - 9 Calcium and (Total Hardness) (Total Hardness) (Total Hardness) Scaling Magnesium Carbonate less than 350 ppm less than 350 ppm less than 350 ppm Less than 0.5 ppm (rotten egg...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Operating Limits Cooling Heating Fluid Limit Min Entering Water Min Entering Brine -1.1 -6.7 Min Leaving Brine 20.0 -9.4 Min Leaving Water 20.0 Max Entering Water/Brine 50.6 32.2 Max Leaving Water/Brine 54.4 29.4 Min Differential Temperature Max Differential Temperature...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Operating Parameters cont. Second Stage Operation Cooling -- No Hot Water Generation Entering Water Water Flow Suction Pressure Discharge Water Temp Rise Superheat Subcooling Air Temp Drop °F DB Temp °F gpm/ton psig Pressure psig °F...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Operation Logic Data Table Heating Cooling Operation Logic Table STG1 STG2 STG3 EMERG Fan Only STG1 STG2 Reheat Fan Only Compressor Reversing Valve Aux Heat Staged Staged Acc Relay Fan Relay (PSC) Loop Pump Hot Water 5-Speed ECM Speed...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Aurora Control System Aurora Controls The Aurora Control System is a complete commercial comfort system that can bring all aspects of the HVAC system into one cohesive module network. The Aurora System is available in two configurations: Aurora Base Control and Aurora Advanced and Aurora Premium Control both with optional Aurora UPC for DDC applications.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Aurora Control System cont. Aurora ‘Base’ Control Control Features Software ABC Standard Version 4.0 Single or Dual Capacity Compressors Either single or dual capacity compressors can be operated. Variable Speed ECM Blower Motor Option (If Applicable) A Variable Speed ECM blower motor can be driven directly using the onboard PWM output.
Page 31
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Aurora Control System cont. Field Selectable Options via Hardware DIP Switch (SW2) SW2-1 FP1 Selection – Low water coil temperature limit DIP Switch (SW1) – Test/Configuration Button (See SW1 setting for freeze detection. On = 30°F; Off = 15°F. Operation Table) SW2-2 FP2 Selection –...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Aurora Control System cont. Field Selectable Options via Software removed, all of the emergency heat outputs will turn off, and the ECM blower will shift to “G” speed and PSC blower motor (Selectable via the Aurora AID Tool) output will remain on.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Aurora Control System cont. Operation Description Single Compressor Cooling, 2nd Stage (Y1, Y2, 0) The compressor will be staged to full capacity 20 seconds Power Up - The unit will not operate until all the inputs and after Y2 input was received.
Page 34
Red (69) Red (66) Yellow (63) Yellow (70) Yellow (67) Black (71) Bro wn (64) LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Black (68) Gray (65) Black Black/White Aurora Control System cont. Blue Yellow Aurora ‘Base’ Control LED Displays Aurora Interface and Diagnostics (AID) Tool Black/White (16) Black/White (17)
Page 35
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Aurora Control System cont. Aurora Advanced and Aurora Premium Aurora Advanced And Aurora Premium Control Features Controls The Aurora ‘Advanced’ Control system expands on the capability of the Aurora ‘Base’ Control (ABC) by adding the Aurora Expansion Board (AXB).
Page 36
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Aurora Control System cont. Variable Speed Pump Performance Monitoring (Standard with Premium Controls) This input and output are provided to drive and monitor Performance Monitoring Kit includes three temperature a variable speed pump. The VS pump output is a PWM sensors, entering and leaving water, leaving air signal to drive the variable speed pump.
Page 37
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Aurora Control System cont. Aurora ‘Advanced’ Control LED Displays These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Refrigerant Circuit Guideline Head Suction Compressor Air Temp. Water Temp. Symptom Superheat Subcooling Pressure Pressure Amp Draw Differential Differential Under Charged System (Possible Leak) High Over Charged System High High High Normal High Normal/Low Normal...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE System Cleaning and Flushing Cleaning and Flushing Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly Prior to start up of any heat pump, the water circulating alkaline (pH 7.5 to 8.5).
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Open Loop Ground Water Systems Typical open loop piping is shown below. Always maintain differences in flow rate from low to high, only one solenoid water pressure in the heat exchanger by placing water valve should be used.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Troubleshooting Checklist Equipment will not start or operate • Return air temperature may be below 50°F. Block off air coil temporarily to improve flow of refrigerant through the system. Air • Follow the troubleshooting flow charts to find root cause. below 50°F cannot be tolerated on a continuing basis.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Steps 1) General Check Other items to check when troubleshooting a water flow lockout are superheat, water flow through the coaxial heat exchanger and • If any new device was installed, or any wiring was changed, antifreeze composition.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Steps cont. 4) Other Faults Auxiliary Heater Does Not Function – Measure the voltage output between P3-1, P3-2, and P3-3, P3-4. The output should be 24 VDC. If ECM Motor Will Not Start voltage is not present, check thermostat operation and wiring.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts Use the following flow charts to aid in troubleshooting the control board. Compressor Will Not Start Without AID Tool Compressor will not start Count the number of Put control into te Is LED3 (green) lit Is LED1 (red)
Page 47
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. Notes: Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. 1. When measuring 24VAC actual value may be between 18 and 30VAC. Put control into test Check 24VAC Check 24VAC...
Page 48
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. Compressor Will Not Start With AID Tool Compressor will not start Check current fault. Connect the AID Is the control in Correct fault and try to Tool Lockout? restart.
Page 49
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. Notes: Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. 1. When measuring 24VAC actual value may be between 18 and 30VAC. Check 24VAC Check 24VAC Check for correct...
Page 50
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. ECM Blower Will Not Start Without AID Tool Blower will not start Check for correct voltage Remove P1 and place a Put control into test Is LED3 (green) Lit between orange and Does the b jumper between R and...
Page 51
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. Notes: Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. 1. When measuring 24VAC actual value may be between 18 and 30VAC. There is a problem Does the blower with the thermostat or...
Page 52
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. ECM Blower Will Not Start With AID Tool Blower will not start Check for correct voltage Connect AID Tool. Put control in test Is LED3 (green) Lit between orange and Remove P1 and put a mode and wait 1...
Page 53
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. Notes: Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. 1. When measuring 24VAC actual value may be between 18 and 30VAC. Put control into test Check 24VAC Check 24VAC...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. Loop Pump Will Not Start Variable Speed Pump Loop Pump will not start Check pump wiring to Is AXB LED1 Is AXB LED1 AXB. Check (Green) Flashing flashing fast? communication wiring from ABC to AXB.
Page 55
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. Notes: 2. When measuring 240VAC actual value may be between 190 and 250VAC. 1.
Page 56
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. Loop Pump Will Not Start Non Variable Speed Pump Loop Pump will not start Check pump wiring to Is AXB LED1 Is AXB LED1 AXB. Check (Green) Flashing flashing fast? communication wiring...
Page 57
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Troubleshooting Flow Charts cont. Notes: 1. When measuring 24VAC actual value may be between 18 and 30VAC. Notes: 2. When measuring 240VAC actual value may be between 190 and 250VAC. 1.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Communicating Thermostat Troubleshooting Guide Communicating Troubleshooting Guide Communicating Troubleshooting Guide TPCC32U01*, TPCM32U03A* and TPCM32U04A* TPCC32U01*, TPCM32U03A* and TPCM32U04A* (*GSR, GSM, E, YRK) Thermostat not (*GSR, GSM, E, YRK) Thermostat not communicating communicating Wire non- Wire non- Are you using a...
Page 59
Which of these do you have LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Communicating Thermostat Troubleshooting Guide cont. Are all Remove what is applicable not needed or add devices present what is needed. Is Issue resolved on Configure the thermostat Aurora System communicating? screen...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Signals To Check for 24VAC between R and C a signal and the contactor is not pulled in, check voltage across the contactor coil. If you have voltage across the contractor coil, replace the contactor.
Page 61
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Signals cont. To Check Operation of the Accessory Relay Put gauges on the unit to monitor high/low pressure. Place a jumper between “R” and “CC” as shown. This will bypass the safety circuit and the compressor will run whether the board is calling for it or not.
Page 62
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Control Board Signals cont. To Check the Condensate Sensor To Check the ECM Blower Motor Enable Signal 24 VAC VOLTS VOLTS OHMS With the AID Tool go to the “Thermostat Inputs” Menu under “Diagnostics”...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Jumping the Control Board Stage 1 Heating Stage 2 Heating With the AID Tool go to the “Thermostat Inputs” Menu under With the AID Tool go to the “Thermostat Inputs” Menu under “Diagnostics”...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Jumping the Control Board cont. Emergency Heat Stage 1 Cooling With the AID Tool go to the “Thermostat Inputs” Menu under With the AID Tool go to the “Thermostat Inputs” Menu under “Diagnostics”...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Jumping the Control Board cont. Reheat Mode With the AID Tool go to the “Thermostat Inputs” Menu under “Diagnostics” and over-ride the “DH” input to ON. If an AID Tool is not available remove the P1 connector to disconnect the thermostat from the board.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Preventative Maintenance Water Coil Maintenance Other Maintenance Filters 1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to Filters must be clean to obtain maximum performance.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Troubleshooting Should a major problem develop, refer to the following information for possible causes and corrective steps. If compressor won’t run: The fuse may be open or the circuit breaker is tripped. Check electrical circuits and motor windings for shorts or grounds. Investigate for possible overloading.
Page 68
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Troubleshooting Checklist Company Name: _________________________________ Company Phone No: ______________________________ Technician Name: ________________________________ Date: __________________________________________ Model No: ______________________________________ Serial No:_______________________________________ Owner’s Name: __________________________________ Open or Closed Loop: _____________________________ Installation Address: ______________________________ Installation Date: _________________________________ Check One Start up/Check-out for new installation Troubleshooting...
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Decommissioning Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refriger- ants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Refrigerant Recovery When removing refrigerant from a system, either for servicing The recovered refrigerant shall be processed according to or decommissioning, it is recommended good practice that all local legislation in the correct recovery cylinder, and the refrigerants are removed safely.
LARGE CAPACITY WATER-SOURCE/GEOTHERMAL HEAT PUMP OPERATION & MAINTENANCE Charging procedures In addition to conventional charging procedures, the following requirements shall be followed. • Ensure that contamination of different refrigerants does not occur when using charging equipment. • Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.