I/O Memory Allocation
Address
Words
Bits
A426
A42600
Interrupt Task
to
Error, Task
A42611
Number
A42615 Interrupt Task
Error Cause
Flag
A427
A42700
CS/CJ-series
to
CPU Bus Unit
A42715
Setting Error,
Unit Number
Flags
A428 to
A42800
Special I/O
A433
to
Unit Setting
A43315
Error, Unit
Number Flags
Name
When A40213 is ON, the content
of these bits depends upon the
status of A42615 (the Interrupt
Task Error Cause Flag).
1) A42615 OFF:
An interrupt task was executed
for more than 10 ms during I/O
refreshing of a C200H Special
I/O Unit or a SYSMAC BUS
Remote I/O Unit. A42600 to
A42611: contain the interrupt
task number.
2) A42615 ON:
An attempt was made to re-
fresh a Special I/O Unit's I/O
from an interrupt task with
IORF(097) while the Unit's I/O
is being refreshed by cyclic I/O
refreshing (duplicate refresh-
ing). A42600 to A42611: con-
tain the Special I/O Unit's unit
number.
When A40213 (the Interrupt Task
Error Flag) is ON, this flag indi-
cates the cause of the error.
A42615 will be ON if a Special I/O
Unit was refreshed from the in-
terrupt task while it was already
being refreshed.
A42615 will be OFF if the inter-
rupt task was executed for more
than 10 ms during I/O refreshing
of a C200H Special I/O Unit or a
SYSMAC BUS Remote I/O Unit.
When a CS/CJ-series CPU Bus
Unit Setting Error occurs, A40203
and the bit in this word corre-
sponding to the Unit's unit num-
ber are turned ON. Bits 00 to 15
correspond to unit numbers 0 to
F.
The CPU Unit will continue oper-
ating and the ERR/ALM indicator
on the front of the CPU Unit will
flash.
When a Special I/O Unit Setting
Error occurs, A40202 and the bit
in these words corresponding to
the Unit's unit number are turned
ON. Bits 00 to 15 correspond to
unit numbers 0 to F.
CS/CJ-series PLC
Function
CX-Simulator
Settings
Function
Task num-
Not used.
ber:
000 to 0FF
(0 to 255)
Unit number:
000 to 05F (0
to 95)
1: Duplicated
Not used.
refreshing
0: Interrupt
task exe-
cuted over
10 ms
1: Setting
Not used.
error
0: No setting
error
1: Setting
Not used.
error
0: No setting
error