Omron EJ1G Datasheet page 7

Ej1g series modular temperature controller for gradient temperature control
Hide thumbs Also See for EJ1G:
Table of Contents

Advertisement

■ Communications Characteristics: Port C
Communications are not possible from port B on the End Unit. A connection is made between ports B when using distributed placement.
Transmission path connection
Communications method
Synchronization method
Baud rate
Transmission code
Data bit length
Stop bit length
Error detection
Flow control
Interface
Retry function
Communications response wait time
Number of Units that can be connected in
parallel (See notes 2 and 3.)
Note: 1. The communications method can be switched between RS-485 and RS-232C. Another model must be used for RS-422 communications.
2. For the number of Units that can be connected, refer to "Connection Precautions" on page 9.
3. When performing gradient temperature control, the number of control channels is limited by the group setting. For details, refer to "Gradient Group Settings"
on page 11.
End Unit/EJ1C-EDU
■ Ratings
Power supply voltage
Operating voltage range
Auxiliary output Outputs
Transistor outputs
Ambient temperature range
Ambient humidity range
■ Characteristics
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Weight
Degree of protection
Standards
Approved standards
Conformed standards
EMC Directive
■ Communications
Port A
Port A connector (See note.)
Note: Port A connector communications and port A terminal communications cannot be used at the same time.
RS-485/RS-422: Multi-point, RS-232C: Point-to-point (See note 1.)
RS-485/RS-422 (two-wire, half duplex), RS-232C
Start-stop synchronization
9.6, 19.2, 38.4, 57.6, or 115.2 kbps
ASCII
7 or 8 bits
1 or 2 bits
Vertical parity (none, even, or odd)
Block check character (BCC) with CompoWay/F
None
RS-485, RS-422, RS-232C (See note 1.)
None
1 to 99 ms (default: 5 ms)
16 Units (model numbers with TC4: 64 channels, model numbers with TC2: 32 channels)
24 VDC
85% to 110% of rated voltage
2
Max. operating voltage: 30 VDC, Max. load current: 50 mA
Operating: − 10 ° C to 55 ° C
− 25 ° C to 65 ° C (with no icing or condensation)
Storage:
Operating: 25% to 85% (with no condensation)
20 M Ω min. (at 500 VDC)
600 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
10 to 55 Hz, 20 m/s
2
150 m/s
max., 3 times each in 6 directions
70 g
End Unit case: IP20, Terminal section: IP00
UL61010C-1, CSA C22.2 No.1010-1
EN61010-1 (IEC61010-1): Pollution level 2, overvoltage category II
Same as for the Basic Unit. Refer to page 3.
Basic Unit Communications (Refer to "Communications Specifications" on page 4.)
E58-CIFQ1
Modular Temperature Controller for Gradient Temperature Control
2
for 2 hours each in X, Y, and Z directions
EJ1G