E5EK-DRT
Specifications
Ratings
Supply voltage
Operating voltage range
Power consumption
Input
Input impedance
Auxiliary output
Control method
Setting method
Indication method
Control output
Remote SP input
Current Transformer input
Other functions
Note: 1. To conform to EN50081-2 (FCC Class A) for ratings of noise terminal voltages, attach a noise filter (TDK ZCB2206-11 or equivalent)
to the AC power supply line.
2. Fuzzy self-tuning is not provided with the E5EK-DRT.
100 to 240 VAC, 50/60 Hz, 24 VAC/DC
85% to 110% of rated supply voltage
15 VA (100 to 240 VAC), 12 VA (24 VAC), 8 W (24 VDC)
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: JPt100, Pt100
Current input:
4 to 20 mA, 0 to 20 mA (Input impedance: 150 )
Voltage input:
1 to 5 V, 0 to 5 V, 0 to 10 V (Input impedance: 1 M )
Current input:
150
Voltage input:
1 M min.
SPST-NO, 3 A at 250 VAC (resistive load)
ON/OFF or advanced PID control (with auto-tuning)
Digital setting using front panel keys
7-segment digital display and LEDs (Character height: PV: 14 mm, SV: 9.5 mm)
According to Output Unit (see Output Unit Ratings and Characteristics)
(Attach an Output Unit that is sold separately.)
Current input: 4 to 20 mA (Input impedance: 150 )
Connect an exclusive Current Transformer (E54-CT1 or E54-CT3)
Standard
Manual output, heating/cooling control, SP limiter, loop burnout alarm, SP ramp, MV limiter,
MV change rate limiter, input digital filter, input shift, run/stop, protect functions
Option
Run/Stop selection, etc.
E5EK-DRT
3