Temperature Input Unit Functions

11-5-14 User Adjustment

Note
478
This function can be used to compensate for offsets in the input value caused
by factors such as the characteristics and connection methods of the input
sensor.
Conversion data
After
adjustment
0%
Before
adjustment
1. Temperature Input Units are properly adjusted at the factory before ship-
ment, so it is normally unnecessary to make adjustments. Use the User
Adjustment function only when absolutely necessary. OMRON is not re-
sponsible for the results of user adjustments. If a mistake is made in the
adjustments, the adjustment data can be cleared to return to the factory
default settings.
2. The Temperature Input Unit continues the temperature conversion opera-
tions even after user adjustments have been made. It is possible for tem-
perature data values to change suddenly from previous values after the
user adjustments are made, so always consider the effects on the operat-
ing environment before applying user adjustments.
Temperature
100%
input value
Section 11-5